Energy meter module · Modbus register map

Peacefair PZEM-014 / PZEM-016 Modbus register map

Updated 17 November 2026

Short answer

Peacefair's PZEM-014/016 are display-less single-phase AC measuring modules that report voltage, current, power, energy, frequency and power factor over RS485 Modbus RTU. Ten input registers hold the readings, with current, power and energy as 32-bit values whose low word comes first. Two holding registers set the over-power alarm threshold and the slave address, and a custom function 0x42 resets energy.

This page lists 9 Modbus registers for the Peacefair PZEM-014 / PZEM-016 — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Peacefair’s own free documentation (linked below) and checked against it.

Manufacturer
Peacefair
Model
PZEM-014 / PZEM-016
Equipment type
Energy meter module
Registers
9 (2 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
32-bit word order
CDAB low word first (word-swapped)
Also known as
PZEM-014, PZEM-016, PZEM-004T V3.0, PZEM-004T-10A, PZEM-004T-100A
Source document
PZEM-014/016 AC communication module · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Peacefair PZEM-014 / PZEM-016

Integration in brief

Read 10 input registers from 0x0000 with function 04 in one request; combine current, power and energy pairs low word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0VoltageUINT16VoltageRead
IR 1CurrentUINT32 CDABCurrentRead
IR 3Active powerUINT32 CDABActive powerRead
IR 5Active energyUINT32 CDABEnergy (Wh)Read
IR 8Power factorUINT16Power factorRead

Enable Modbus control & writes

No enable step; the module answers Modbus RTU as soon as it is powered from the measured AC line.

Byte order & addressing

Network setup

Watch out for

Peacefair PZEM-014 / PZEM-016 Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

9 of 9 shown
Peacefair PZEM-014 / PZEM-016 Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 0x0000VoltageUINT16× 0.1VRead
IR1doc 0x0001-0x0002CurrentLow 16 bits at 0x0001, high 16 bits at 0x0002.UINT32CDAB× 0.001ARead
IR3doc 0x0003-0x0004Active powerLow word first.UINT32CDAB× 0.1WRead
IR5doc 0x0005-0x0006Active energyLow word first. Reset with function 0x42.UINT32CDABWhRead
IR7doc 0x0007FrequencyUINT16× 0.1HzRead
IR8doc 0x0008Power factorUINT16× 0.01Read
IR9doc 0x0009Alarm statusOver-power alarm.UINT16Read0 = No alarm; 65535 = Alarm (0xFFFF)
HR1doc 0x0001Power alarm thresholdUINT16WRead/write
HR2doc 0x0002Modbus-RTU address0x0001-0x00F7.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Peacefair PZEM-014 / PZEM-016

What Modbus registers does the Peacefair PZEM-014 / PZEM-016 have?

This map lists 9 registers: 7 input registers, 2 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Peacefair PZEM-014 / PZEM-016 Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register addresses are given in hex and sent as-is; the datasheet's example reads 10 registers starting at 0x0000 and decodes voltage from the first register.

What byte order does the Peacefair PZEM-014 / PZEM-016 use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Peacefair PZEM-014 / PZEM-016?

Start with IR 0 Voltage (Voltage); IR 1 Current (Current); IR 3 Active power (Active power); IR 5 Active energy (Energy (Wh)); IR 8 Power factor (Power factor).

How do I enable Modbus control of the Peacefair PZEM-014 / PZEM-016?

No enable step; the module answers Modbus RTU as soon as it is powered from the measured AC line.

Where is the official Peacefair PZEM-014 / PZEM-016 Modbus documentation?

The source is PZEM-014/016 AC communication module. Peacefair doesn't publish it on its own website, so this map was re-typed from a free copy at https://rcscomponents.kiev.ua/datasheets/pzem-014_16.pdf. It may be an older revision, so check it against the live unit.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: PZEM-014/016 AC communication module · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.