The RISH LM 1380 multifunction meter is a 96 x 96 mm panel multifunction meter that measures voltage, current, power, power factor, frequency, harmonics and energy on 3-phase 4-wire, 3-phase 3-wire or single-phase networks. Its RS-485 port speaks Modbus RTU and every reading is a 32-bit IEEE float in two registers. This map covers the regular per-phase and system parameters (Table 1.1) and the float energy registers (Table 1.3), plus the main setup registers (system type, CT/PT ratios, demand period, communication and word-order settings).

This page lists 277 Modbus registers for the Rishabh Instruments RISH LM 1380 multifunction meter — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.

Manufacturer
Rishabh Instruments
Model
RISH LM 1380 multifunction meter
Equipment type
Power meter
Registers
277 (12 writable)
Transport
Modbus RTU
Default unit ID
1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RISH LM 1380, LM1380
Source document
Rish LM1380 Interface Manual · DMAN-00IM-0925 Rev. A · rev. 2022-04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Rishabh Instruments RISH LM 1380 multifunction meter

Integration in brief

Read measured values with FC04 (or FC03 at the 4X copies) in pairs of registers and decode them as ABCD floats. Settings are floats too and are written with FC16.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Voltage L1 (Voltage L12 for 3P3W)FLOAT32 ABCDVoltage L1Read
IR 6Current L1FLOAT32 ABCDCurrent L1Read
IR 52Watt SumFLOAT32 ABCDTotal active power (Watt Sum)Read
IR 70FreqFLOAT32 ABCDFrequencyRead
IR 62PF AvgFLOAT32 ABCDAverage power factorRead
IR 1800Sys Active Energy ImportFLOAT32 ABCDSystem active energy importRead
IR 72Wh importFLOAT32 ABCDActive energy import (Wh import)Read

Enable Modbus control & writes

Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.

Byte order & addressing

Network setup

Watch out for

Rishabh Instruments RISH LM 1380 multifunction meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

277 of 277 shown
Rishabh Instruments RISH LM 1380 multifunction meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Voltage L1 (Voltage L12 for 3P3W)FLOAT32ABCDRead
IR2doc 30003Voltage L2 (Voltage L23 for 3P3W)FLOAT32ABCDRead
IR4doc 30005Voltage L3 (Voltage L31 for 3P3W)FLOAT32ABCDRead
IR6doc 30007Current L1FLOAT32ABCDRead
IR8doc 30009Current L2FLOAT32ABCDRead
IR10doc 30011Current L3FLOAT32ABCDRead
IR12doc 30013Watt L1FLOAT32ABCDRead
IR14doc 30015Watt L2FLOAT32ABCDRead
IR16doc 30017Watt L3FLOAT32ABCDRead
IR18doc 30019VA L1FLOAT32ABCDRead
IR20doc 30021VA L2FLOAT32ABCDRead
IR22doc 30023VA L3FLOAT32ABCDRead
IR24doc 30025VAR L1FLOAT32ABCDRead
IR26doc 30027VAR L2FLOAT32ABCDRead
IR28doc 30029VAR L3FLOAT32ABCDRead
IR30doc 30031Power Factor L1FLOAT32ABCDRead
IR32doc 30033Power Factor L2FLOAT32ABCDRead
IR34doc 30035Power Factor L3FLOAT32ABCDRead
IR36doc 30037Phase Angle L1FLOAT32ABCDRead
IR38doc 30039Phase Angle L2FLOAT32ABCDRead
IR40doc 30041Phase Angle L3FLOAT32ABCDRead
IR42doc 30043Voltage AvgFLOAT32ABCDRead
IR44doc 30045Voltage SumFLOAT32ABCDRead
IR46doc 30047Current AvgFLOAT32ABCDRead
IR48doc 30049Current SumFLOAT32ABCDRead
IR50doc 30051Watt AvgFLOAT32ABCDRead
IR52doc 30053Watt SumFLOAT32ABCDRead
IR54doc 30055VA AvgFLOAT32ABCDRead
IR56doc 30057VA SumFLOAT32ABCDRead
IR58doc 30059VAR AvgFLOAT32ABCDRead
IR60doc 30061VAr SumFLOAT32ABCDRead
IR62doc 30063PF AvgFLOAT32ABCDRead
IR64doc 30065PF SumFLOAT32ABCDRead
IR66doc 30067Phase Angle AvgFLOAT32ABCDRead
IR68doc 30069Phase Angle SumFLOAT32ABCDRead
IR70doc 30071FreqFLOAT32ABCDRead
IR72doc 30073Wh importFLOAT32ABCDRead
IR74doc 30075Wh exportFLOAT32ABCDRead
IR76doc 30077VArh CapacitiveFLOAT32ABCDRead
IR78doc 30079VArh InductiveFLOAT32ABCDRead
IR80doc 30081VAhFLOAT32ABCDRead
IR84doc 30085kW imp demandFLOAT32ABCDRead
IR86doc 30087max kW imp demandFLOAT32ABCDRead
IR88doc 30089kW exp demandFLOAT32ABCDRead
IR90doc 30091max kW exp demandFLOAT32ABCDRead
IR92doc 30093kVAr Cap. demandFLOAT32ABCDRead
IR94doc 30095max kVAr Cap. demandFLOAT32ABCDRead
IR96doc 30097kVAr Ind. demandFLOAT32ABCDRead
IR98doc 30099max kVAr Ind. demandFLOAT32ABCDRead
IR100doc 30101KVA demandFLOAT32ABCDRead
IR102doc 30103max KVA demandFLOAT32ABCDRead
IR104doc 30105current demandFLOAT32ABCDRead
IR106doc 30107max current demandFLOAT32ABCDRead
IR108doc 30109Wh import Overflow countFLOAT32ABCDRead
IR110doc 30111Wh ImportFLOAT32ABCDRead
IR112doc 30113Wh export Overflow countFLOAT32ABCDRead
IR114doc 30115Wh exportFLOAT32ABCDRead
IR116doc 30117VArh Cap. Overflow countFLOAT32ABCDRead
IR118doc 30119VArh CapacitiveFLOAT32ABCDRead
IR120doc 30121VArh Ind. Overflow countFLOAT32ABCDRead
IR122doc 30123VARh InductiveFLOAT32ABCDRead
IR124doc 30125VAh Overflow countFLOAT32ABCDRead
IR126doc 30127VAhFLOAT32ABCDRead
IR132doc 30133System Voltage MaxFLOAT32ABCDRead
IR134doc 30135System Voltage MinFLOAT32ABCDRead
IR136doc 30137RPMFLOAT32ABCDRead
IR138doc 30139Impulse RateFLOAT32ABCDRead
IR140doc 30141System Current MaxFLOAT32ABCDRead
IR142doc 30143System Current MinFLOAT32ABCDRead
IR144doc 30145Wh imp. depending on update rate*FLOAT32ABCDRead
IR146doc 30147Wh exp. depending on update rate*FLOAT32ABCDRead
IR148doc 30149VArh cap. depending on update rate*FLOAT32ABCDRead
IR150doc 30151VArh ind. depending on update rate*FLOAT32ABCDRead
IR152doc 30153VAh depending on update rate*FLOAT32ABCDRead
IR156doc 30157Wh imp OFC depending on update rate*FLOAT32ABCDRead
IR158doc 30159Wh exp OFC depending on update rate*FLOAT32ABCDRead
IR160doc 30161VArh Cap. OFC depending on update rate *FLOAT32ABCDRead
IR162doc 30163VArh Ind. OFC depending on update rate *FLOAT32ABCDRead
IR164doc 30165VAh OFC depending on update rate*FLOAT32ABCDRead
IR168doc 30169Re-Active Power Factor L1FLOAT32ABCDRead
IR170doc 30171Re-Active Power Factor L2FLOAT32ABCDRead
IR172doc 30173Re-Active Power Factor L3FLOAT32ABCDRead
IR174doc 30175Average Re-Active Power FactorFLOAT32ABCDRead
IR176doc 30177Sum Re-Active Power FactorFLOAT32ABCDRead
IR178doc 30179LF Factor SgnQ(1-(P/S)) L1FLOAT32ABCDRead
IR180doc 30181LF Factor SgnQ(1-(P/S)) L2FLOAT32ABCDRead
IR182doc 30183LF Factor SgnQ(1-(P/S)) L3FLOAT32ABCDRead
IR184doc 30185Average LF Factor SgnQ(1-(P/S))FLOAT32ABCDRead
IR186doc 30187Sum LF Factor SgnQ(1-(P/S))FLOAT32ABCDRead
IR188doc 30189Displacement Power Factor L1FLOAT32ABCDRead
IR190doc 30191Displacement Power Factor L2FLOAT32ABCDRead
IR192doc 30193Displacement Power Factor L3FLOAT32ABCDRead
IR194doc 30195Average Displacement Power FactorFLOAT32ABCDRead
IR196doc 30197Sum Displacement Power FactorFLOAT32ABCDRead
IR200doc 30201V12FLOAT32ABCDRead
IR202doc 30203V23FLOAT32ABCDRead
IR204doc 30205V31FLOAT32ABCDRead
IR206doc 30207VTHD-RFLOAT32ABCDRead
IR208doc 30209VTHD-YFLOAT32ABCDRead
IR210doc 30211VTHD-BFLOAT32ABCDRead
IR212doc 30213ITHD-RFLOAT32ABCDRead
IR214doc 30215ITHD-YFLOAT32ABCDRead
IR216doc 30217ITHD-BFLOAT32ABCDRead
IR218doc 30219System V-THDFLOAT32ABCDRead
IR220doc 30221System I-THDFLOAT32ABCDRead
IR224doc 30225Neutral Current (3P4W only)FLOAT32ABCDRead
IR226doc 30227Run hourFLOAT32ABCDRead
IR228doc 30229On HourFLOAT32ABCDRead
IR230doc 30231No. of interruptsFLOAT32ABCDRead
IR242doc 30243Phase indicate**FLOAT32ABCDRead
IR248doc 30249VLN Unbalance (3P4W only)FLOAT32ABCDRead
IR250doc 30251VLL Unbalance (3P4W and 3P3W only)FLOAT32ABCDRead
IR252doc 30253Curr. Unbalance (3P4W and 3P3W only)FLOAT32ABCDRead
IR254doc 30255Distortion VAr L1FLOAT32ABCDRead
IR256doc 30257Distortion VAr L2FLOAT32ABCDRead
IR258doc 30259Distortion VAr L3FLOAT32ABCDRead
IR260doc 30261Distortion VAr AVGFLOAT32ABCDRead
IR262doc 30263Distortion VAr SUMFLOAT32ABCDRead
IR264doc 30265Fundamental VAr L1FLOAT32ABCDRead
IR266doc 30267Fundamental VAr L2FLOAT32ABCDRead
IR268doc 30269Fundamental VAr L3FLOAT32ABCDRead
IR270doc 30271Fundamental VAr AVGFLOAT32ABCDRead
IR272doc 30273Fundamental VAr SUMFLOAT32ABCDRead
IR274doc 30275RTC Complete Date (DDMMYY)FLOAT32ABCDRead
IR276doc 30277RTC Complete Time (HH:MM 24 Hour format)FLOAT32ABCDRead
IR1800doc 31801Sys Active Energy ImportFLOAT32ABCDRead
IR1802doc 31803Sys Active Energy ExportFLOAT32ABCDRead
IR1804doc 31805Sys Reactive Energy CapacitiveFLOAT32ABCDRead
IR1806doc 31807Sys Reactive Energy InductiveFLOAT32ABCDRead
IR1808doc 31809Sys Apparent EnergyFLOAT32ABCDRead
IR1812doc 31813Sys Active Energy Import OVF CountFLOAT32ABCDRead
IR1814doc 31815Sys Active Energy Export OVF CountFLOAT32ABCDRead
IR1816doc 31817Sys Reactive Energy Capacitive OVF CountFLOAT32ABCDRead
IR1818doc 31819Sys Reactive Energy Inductive OVF CountFLOAT32ABCDRead
IR1820doc 31821Sys Apparent Energy OVF CountFLOAT32ABCDRead
IR1824doc 31825Sys Active Energy Import on update rateFLOAT32ABCDRead
IR1826doc 31827Sys Active Energy Export on update rateFLOAT32ABCDRead
IR1828doc 31829Sys Reactive Energy Capacitive on update rateFLOAT32ABCDRead
IR1830doc 31831Sys Reactive Energy Inductive on update rateFLOAT32ABCDRead
IR1832doc 31833Sys Apparent Energy on timeFLOAT32ABCDRead
IR1836doc 31837Sys Active Energy Imp OVF Count on update Rate*FLOAT32ABCDRead
IR1838doc 31839Sys Active Energy Exp OVF Count on update Rate*FLOAT32ABCDRead
IR1840doc 31841Sys Reactive Energy Cap OVF Count on update Rate*FLOAT32ABCDRead
IR1842doc 31843Sys Reactive Energy Ind OVF Count on update Rate*FLOAT32ABCDRead
IR1844doc 31845Sys Apparent Energy OVF Count on update Rate*FLOAT32ABCDRead
IR1848doc 31849Sys Total Active EnergyFLOAT32ABCDRead
IR1850doc 31851Sys Total Reactive EnergyFLOAT32ABCDRead
IR1852doc 31853Sys Total Apparent EnergyFLOAT32ABCDRead
IR1854doc 31855Sys Total Active Energy OFL CountFLOAT32ABCDRead
IR1856doc 31857Sys Total Reactive Energy OFL CountFLOAT32ABCDRead
IR1858doc 31859Sys Total Apparent Energy OFL CountFLOAT32ABCDRead
IR1860doc 31861Sys Total Active Energy on update Rate*FLOAT32ABCDRead
IR1862doc 31863Sys Total Reactive Energy on update Rate*FLOAT32ABCDRead
IR1864doc 31865Sys Total Apparent Energy on update Rate*FLOAT32ABCDRead
IR1866doc 31867Sys Total Active Energy OFL Count on update Rate*FLOAT32ABCDRead
IR1868doc 31869Sys Total Reactive Energy OFL Count on update Rate*FLOAT32ABCDRead
IR1870doc 31871Sys Total Apparent Energy OFL Count on update Rate*FLOAT32ABCDRead
IR1872doc 31873Active Energy Import L1FLOAT32ABCDRead
IR1874doc 31875Active Energy Import L2FLOAT32ABCDRead
IR1876doc 31877Active Energy Import L3FLOAT32ABCDRead
IR1878doc 31879Active Energy Export L1FLOAT32ABCDRead
IR1880doc 31881Active Energy Export L2FLOAT32ABCDRead
IR1882doc 31883Active Energy Export L3FLOAT32ABCDRead
IR1884doc 31885Reactive Energy Capacitive L1FLOAT32ABCDRead
IR1886doc 31887Reactive Energy Capacitive L2FLOAT32ABCDRead
IR1888doc 31889Reactive Energy Capacitive L3FLOAT32ABCDRead
IR1890doc 31891Reactive Energy Inductive L1FLOAT32ABCDRead
IR1892doc 31893Reactive Energy Inductive L2FLOAT32ABCDRead
IR1894doc 31895Reactive Energy Inductive L3FLOAT32ABCDRead
IR1896doc 31897Apparent Energy L1FLOAT32ABCDRead
IR1898doc 31899Apparent Energy L2FLOAT32ABCDRead
IR1900doc 31901Apparent Energy L3FLOAT32ABCDRead
IR1908doc 31909Total Active Energy L1FLOAT32ABCDRead
IR1910doc 31911Total Active Energy L2FLOAT32ABCDRead
IR1912doc 31913Total Active Energy L3FLOAT32ABCDRead
IR1914doc 31915Total Reactive Energy L1FLOAT32ABCDRead
IR1916doc 31917Total Reactive Energy L2FLOAT32ABCDRead
IR1918doc 31919Total Reactive Energy L3FLOAT32ABCDRead
IR1920doc 31921Total Apparent Energy L1FLOAT32ABCDRead
IR1922doc 31923Total Apparent Energy L2FLOAT32ABCDRead
IR1924doc 31925Total Apparent Energy L3FLOAT32ABCDRead
IR1926doc 31927OVF Count Active Energy Import L1FLOAT32ABCDRead
IR1928doc 31929OVF Count Active Energy Import L2FLOAT32ABCDRead
IR1930doc 31931OVF Count Active Energy Import L3FLOAT32ABCDRead
IR1932doc 31933OVF Count Active Energy Export L1FLOAT32ABCDRead
IR1934doc 31935OVF Count Active Energy Export L2FLOAT32ABCDRead
IR1936doc 31937OVF Count Active Energy Export L3FLOAT32ABCDRead
IR1938doc 31939OVF Count Reactive Energy Capacitive L1FLOAT32ABCDRead
IR1940doc 31941OVF Count Reactive Energy Capacitive L2FLOAT32ABCDRead
IR1942doc 31943OVF Count Reactive Energy Capacitive L3FLOAT32ABCDRead
IR1944doc 31945OVF Count Reactive Energy Inductive L1FLOAT32ABCDRead
IR1946doc 31947OVF Count Reactive Energy Inductive L2FLOAT32ABCDRead
IR1948doc 31949OVF Count Reactive Energy Inductive L3FLOAT32ABCDRead
IR1950doc 31951OVF Count Apparent Energy L1FLOAT32ABCDRead
IR1952doc 31953OVF Count Apparent Energy L2FLOAT32ABCDRead
IR1954doc 31955OVF Count Apparent Energy L3FLOAT32ABCDRead
IR1962doc 31963Total Active Energy OVF Count L1FLOAT32ABCDRead
IR1964doc 31965Total Active Energy OVF Count L2FLOAT32ABCDRead
IR1966doc 31967Total Active Energy OVF Count L3FLOAT32ABCDRead
IR1968doc 31969Total Reactive Energy OVF Count L1FLOAT32ABCDRead
IR1970doc 31971Total Reactive Energy OVF Count L2FLOAT32ABCDRead
IR1972doc 31973Total Reactive Energy OVF Count L3FLOAT32ABCDRead
IR1974doc 31975Total Apparent Energy OVF Count L1FLOAT32ABCDRead
IR1976doc 31977Total Apparent Energy OVF Count L2FLOAT32ABCDRead
IR1978doc 31979Total Apparent Energy OVF Count L3FLOAT32ABCDRead
IR1980doc 31981Active Energy Import L1 On Update Rate*FLOAT32ABCDRead
IR1982doc 31983Active Energy Import L2 On Update Rate*FLOAT32ABCDRead
IR1984doc 31985Active Energy Import L3 On Update Rate*FLOAT32ABCDRead
IR1986doc 31987Active Energy Export L1 On Update Rate*FLOAT32ABCDRead
IR1988doc 31989Active Energy Export L2 On Update Rate*FLOAT32ABCDRead
IR1990doc 31991Active Energy Export L3 On Update Rate*FLOAT32ABCDRead
IR1992doc 31993Reactive Energy Capacitive L1 On Update Rate*FLOAT32ABCDRead
IR1994doc 31995Reactive Energy Capacitive L2 On Update Rate*FLOAT32ABCDRead
IR1996doc 31997Reactive Energy Capacitive L3 On Update Rate*FLOAT32ABCDRead
IR1998doc 31999Reactive Energy Inductive L1 On Update Rate*FLOAT32ABCDRead
IR2000doc 32001Reactive Energy Inductive L2 On Update Rate*FLOAT32ABCDRead
IR2002doc 32003Reactive Energy Inductive L3 On Update Rate*FLOAT32ABCDRead
IR2004doc 32005Apparent Energy L1 On Update Rate*FLOAT32ABCDRead
IR2006doc 32007Apparent Energy L2 On Update Rate*FLOAT32ABCDRead
IR2008doc 32009Apparent Energy L3 On Update Rate*FLOAT32ABCDRead
IR2016doc 32017Total Active Energy L1 On Update Rate*FLOAT32ABCDRead
IR2018doc 32019Total Active Energy L2 On Update Rate*FLOAT32ABCDRead
IR2020doc 32021Total Active Energy L3 On Update Rate*FLOAT32ABCDRead
IR2022doc 32023Total Reactive Energy L1 On Update Rate*FLOAT32ABCDRead
IR2024doc 32025Total Reactive Energy L2 On Update Rate*FLOAT32ABCDRead
IR2026doc 32027Total Reactive Energy L3 On Update Rate*FLOAT32ABCDRead
IR2028doc 32029Total Apparent Energy L1 On Update Rate*FLOAT32ABCDRead
IR2030doc 32031Total Apparent Energy L2 On Update Rate*FLOAT32ABCDRead
IR2032doc 32033Total Apparent Energy L3 On Update Rate*FLOAT32ABCDRead
IR2034doc 32035OVF Active Energy Import L1 On Update Rate*FLOAT32ABCDRead
IR2036doc 32037OVF Active Energy Import L2 On Update Rate*FLOAT32ABCDRead
IR2038doc 32039OVF Active Energy Import L3 On Update Rate*FLOAT32ABCDRead
IR2040doc 32041OVF Active Energy Export L1 On Update Rate*FLOAT32ABCDRead
IR2042doc 32043OVF Active Energy Export L2 On Update Rate*FLOAT32ABCDRead
IR2044doc 32045OVF Active Energy Export L3 On Update Rate*FLOAT32ABCDRead
IR2046doc 32047OVF Reactive Energy Capacitive L1 On Update Rate*FLOAT32ABCDRead
IR2048doc 32049OVF Reactive Energy Capacitive L2 On Update Rate*FLOAT32ABCDRead
IR2050doc 32051OVF Reactive Energy Capacitive L3 On Update Rate*FLOAT32ABCDRead
IR2052doc 32053OVF Reactive Energy Inductive L1 On Update Rate*FLOAT32ABCDRead
IR2054doc 32055OVF Reactive Energy Inductive L2 On Update Rate*FLOAT32ABCDRead
IR2056doc 32057OVF Reactive Energy Inductive L3 On Update Rate*FLOAT32ABCDRead
IR2058doc 32059OVF Apparent Energy L1 On Update Rate*FLOAT32ABCDRead
IR2060doc 32061OVF Apparent Energy L2 On Update Rate*FLOAT32ABCDRead
IR2062doc 32063OVF Apparent Energy L3 On Update Rate*FLOAT32ABCDRead
IR2070doc 32071Total Active Energy OVF Count L1 On Update Rate*FLOAT32ABCDRead
IR2072doc 32073Total Active Energy OVF Count L2 On Update Rate*FLOAT32ABCDRead
IR2074doc 32075Total Active Energy OVF Count L3 On Update Rate*FLOAT32ABCDRead
IR2076doc 32077Total Reactive Energy OVF Count L1 On Update Rate*FLOAT32ABCDRead
IR2078doc 32079Total Reactive Energy OVF Count L2 On Update Rate*FLOAT32ABCDRead
IR2080doc 32081Total Reactive Energy OVF Count L3 On Update Rate*FLOAT32ABCDRead
IR2082doc 32083Total Apparent Energy OVF Count L1 On Update Rate*FLOAT32ABCDRead
IR2084doc 32085Total Apparent Energy OVF Count L2 On Update Rate*FLOAT32ABCDRead
IR2086doc 32087Total Apparent Energy OVF Count L3 On Update Rate*FLOAT32ABCDRead
IR2088doc 32089Digital Input Pulse Counter 1 ValueFLOAT32ABCDRead
IR2090doc 32091Digital Input Pulse Counter 2 ValueFLOAT32ABCDRead
IR2092doc 32093Digital Input Pulse Counter 3 ValueFLOAT32ABCDRead
IR2094doc 32095Digital Input Pulse Counter 4 ValueFLOAT32ABCDRead
IR2096doc 32097Digital Input Pulse Counter 1 OverflowFLOAT32ABCDRead
IR2098doc 32099Digital Input Pulse Counter 2 OverflowFLOAT32ABCDRead
IR2100doc 32101Digital Input Pulse Counter 3 OverflowFLOAT32ABCDRead
IR2102doc 32103Digital Input Pulse Counter 4 OverflowFLOAT32ABCDRead
IR2104doc 32105Run Hour UtilityFLOAT32ABCDRead
IR2106doc 32107On Hour UtilityFLOAT32ABCDRead
IR2112doc 32113No of InterruptionFLOAT32ABCDRead
HR6002doc 46003System TypeSetup parameter (float).FLOAT32ABCDRead/write
HR6004doc 46005PT PrimarySetup parameter (float).FLOAT32ABCDRead/write
HR6006doc 46007CT PrimarySetup parameter (float).FLOAT32ABCDRead/write
HR6008doc 46009PT SecondarySetup parameter (float).FLOAT32ABCDRead/write
HR6010doc 46011CT SecondarySetup parameter (float).FLOAT32ABCDRead/write
HR6018doc 46019Demand Integration TimeSetup parameter (float).FLOAT32ABCDRead/write
HR6036doc 46037Reset ParametersSetup parameter (float).FLOAT32ABCDRead/write
HR6038doc 46039PasswordSetup parameter (float).FLOAT32ABCDRead/write
HR6046doc 46047Auto ScrollSetup parameter (float).FLOAT32ABCDRead/write
HR6050doc 46051Node AddressSetup parameter (float).FLOAT32ABCDRead/write
HR6052doc 46053RS485 Setup CodeSetup parameter (float).FLOAT32ABCDRead/write
HR6054doc 46055Register Order/Word OrderSetup parameter (float).FLOAT32ABCDRead/write
HR6356doc 46357Firmware Version NumberRead-only identification value (float).FLOAT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Rishabh Instruments RISH LM 1380 multifunction meter

What Modbus registers does the Rishabh Instruments RISH LM 1380 multifunction meter have?

This map lists 277 registers: 264 input registers, 13 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Rishabh Instruments RISH LM 1380 multifunction meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 30001/40001-style addresses next to the hex start address actually sent (30001 = 0x0000). Wire address = printed number - 30001 (input registers) or - 40001 (holding registers); every value here was cross-checked against the printed hex address.

What byte order does the Rishabh Instruments RISH LM 1380 multifunction meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Rishabh Instruments RISH LM 1380 multifunction meter?

Start with IR 0 Voltage L1 (Voltage L12 for 3P3W) (Voltage L1); IR 6 Current L1 (Current L1); IR 52 Watt Sum (Total active power (Watt Sum)); IR 70 Freq (Frequency); IR 62 PF Avg (Average power factor); IR 1800 Sys Active Energy Import (System active energy import); IR 72 Wh import (Active energy import (Wh import)).

How do I enable Modbus control of the Rishabh Instruments RISH LM 1380 multifunction meter?

Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.

Where is the official Rishabh Instruments RISH LM 1380 multifunction meter Modbus documentation?

The source is Rish LM1380 Interface Manual (DMAN-00IM-0925 Rev. A), revision 2022-04, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/rish-lm1380-96/Rish_LM1380_Interface_Manual.pdf.

More Rishabh Instruments Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Rish LM1380 Interface Manual · DMAN-00IM-0925 Rev. A · rev. 2022-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.