Power meter · Modbus register map

Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter Modbus register map

Updated 17 November 2026

Short answer

The RISH Master 3440 is a 96 x 96 mm panel multifunction meter (class 0.2S) that measures voltage, current, power, power factor, frequency, harmonics and energy on 3-phase 4-wire, 3-phase 3-wire or single-phase networks. Its RS-485 port speaks Modbus RTU and every reading is a 32-bit IEEE float in two registers. This map covers per-phase and system parameters, energies, demands, THD and hour counters (Table 1), plus the main setup registers (system type, CT/PT ratios, demand period, communication and word-order settings).

This page lists 290 Modbus registers for the Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.

Manufacturer
Rishabh Instruments
Model
RISH Master 3440 (class 0.2S) multifunction meter
Equipment type
Power meter
Registers
290 (13 writable)
Transport
Modbus RTU
Default unit ID
1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RISH Master 3440, RM3440, Master 3440 0.2S
Source document
RISH Master 3440 0.2S Interface Definition · DMAN-00IM-0711 Rev. C · rev. 2019-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter

Integration in brief

Read measured values with FC04 (or FC03 at the 4X copies) in pairs of registers and decode them as ABCD floats. Settings are floats too and are written with FC16.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0V1FLOAT32 ABCDVoltage L1Read
IR 6I1FLOAT32 ABCDCurrent L1Read
IR 52Watt SumFLOAT32 ABCDTotal active power (Watt Sum)Read
IR 70FreqFLOAT32 ABCDFrequencyRead
IR 62PF AvgFLOAT32 ABCDAverage power factorRead
IR 72Wh importFLOAT32 ABCDActive energy import (Wh import)Read

Enable Modbus control & writes

Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.

Byte order & addressing

Network setup

Watch out for

Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

290 of 290 shown
Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001V1FLOAT32ABCDRead
IR2doc 30003V2FLOAT32ABCDRead
IR4doc 30005V3FLOAT32ABCDRead
IR6doc 30007I1FLOAT32ABCDRead
IR8doc 30009I2FLOAT32ABCDRead
IR10doc 30011I3FLOAT32ABCDRead
IR12doc 30013W1FLOAT32ABCDRead
IR14doc 30015W2FLOAT32ABCDRead
IR16doc 30017W3FLOAT32ABCDRead
IR18doc 30019VA1FLOAT32ABCDRead
IR20doc 30021VA2FLOAT32ABCDRead
IR22doc 30023VA3FLOAT32ABCDRead
IR24doc 30025VAR1FLOAT32ABCDRead
IR26doc 30027VAR2FLOAT32ABCDRead
IR28doc 30029VAR3FLOAT32ABCDRead
IR30doc 30031PF1FLOAT32ABCDRead
IR32doc 30033PF2FLOAT32ABCDRead
IR34doc 30035PF3FLOAT32ABCDRead
IR36doc 30037Angle1FLOAT32ABCDRead
IR38doc 30039Angle2FLOAT32ABCDRead
IR40doc 30041Angle3FLOAT32ABCDRead
IR42doc 30043Volt AvgFLOAT32ABCDRead
IR44doc 30045Volt SumFLOAT32ABCDRead
IR46doc 30047Current AvgFLOAT32ABCDRead
IR48doc 30049Current SumFLOAT32ABCDRead
IR50doc 30051Watt AvgFLOAT32ABCDRead
IR52doc 30053Watt SumFLOAT32ABCDRead
IR54doc 30055VA AvgFLOAT32ABCDRead
IR56doc 30057VA SumFLOAT32ABCDRead
IR58doc 30059VAr AvgFLOAT32ABCDRead
IR60doc 30061VAr SumFLOAT32ABCDRead
IR62doc 30063PF AvgFLOAT32ABCDRead
IR64doc 30065PF SumFLOAT32ABCDRead
IR66doc 30067Phase Angle AvgFLOAT32ABCDRead
IR68doc 30069Phase Angle SumFLOAT32ABCDRead
IR70doc 30071FreqFLOAT32ABCDRead
IR72doc 30073Wh importFLOAT32ABCDRead
IR74doc 30075Wh exportFLOAT32ABCDRead
IR76doc 30077VArh CapacitiveFLOAT32ABCDRead
IR78doc 30079VArh InductiveFLOAT32ABCDRead
IR80doc 30081VAhFLOAT32ABCDRead
IR84doc 30085kW imp demandFLOAT32ABCDRead
IR86doc 30087max kW imp demandFLOAT32ABCDRead
IR88doc 30089kW exp demandFLOAT32ABCDRead
IR90doc 30091max kW exp demandFLOAT32ABCDRead
IR92doc 30093kVAr Cap. demandFLOAT32ABCDRead
IR94doc 30095max kVAr Cap. demandFLOAT32ABCDRead
IR96doc 30097kVAr Ind. demandFLOAT32ABCDRead
IR98doc 30099max kVAr Ind. demandFLOAT32ABCDRead
IR100doc 30101KVA demandFLOAT32ABCDRead
IR102doc 30103max KVA demandFLOAT32ABCDRead
IR104doc 30105current demandFLOAT32ABCDRead
IR106doc 30107max current demandFLOAT32ABCDRead
IR108doc 30109Wh import Overflow countFLOAT32ABCDRead
IR110doc 30111Wh ImportFLOAT32ABCDRead
IR112doc 30113Wh export Overflow countFLOAT32ABCDRead
IR114doc 30115Wh exportFLOAT32ABCDRead
IR116doc 30117VArh Cap. Overflow countFLOAT32ABCDRead
IR118doc 30119VArh CapacitiveFLOAT32ABCDRead
IR120doc 30121VArh Ind. Overflow countFLOAT32ABCDRead
IR122doc 30123VARh InductiveFLOAT32ABCDRead
IR124doc 30125VAh Overflow countFLOAT32ABCDRead
IR126doc 30127VAhFLOAT32ABCDRead
IR132doc 30133System Voltage MaxFLOAT32ABCDRead
IR134doc 30135System Voltage MinFLOAT32ABCDRead
IR136doc 30137RPMFLOAT32ABCDRead
IR138doc 30139Impulse RateFLOAT32ABCDRead
IR140doc 30141System Current MaxFLOAT32ABCDRead
IR142doc 30143System Current MinFLOAT32ABCDRead
IR144doc 30145Wh imp. depending on update rate*FLOAT32ABCDRead
IR146doc 30147Wh exp. depending on update rate*FLOAT32ABCDRead
IR148doc 30149VArh cap. depending on update rate*FLOAT32ABCDRead
IR150doc 30151VArh ind. depending on update rate*FLOAT32ABCDRead
IR152doc 30153VAh depending on update rate*FLOAT32ABCDRead
IR156doc 30157Wh imp OFC depending on update rate*FLOAT32ABCDRead
IR158doc 30159Wh exp OFC depending on update rate*FLOAT32ABCDRead
IR160doc 30161VArh Cap. OFC depending on update rate *FLOAT32ABCDRead
IR162doc 30163VArh Ind. OFC depending on update rate *FLOAT32ABCDRead
IR164doc 30165VAh OFC depending on update rate*FLOAT32ABCDRead
IR200doc 30201V12FLOAT32ABCDRead
IR202doc 30203V23FLOAT32ABCDRead
IR204doc 30205V31FLOAT32ABCDRead
IR206doc 30207VTHD-RFLOAT32ABCDRead
IR208doc 30209VTHD-YFLOAT32ABCDRead
IR210doc 30211VTHD-BFLOAT32ABCDRead
IR212doc 30213ITHD-RFLOAT32ABCDRead
IR214doc 30215ITHD-YFLOAT32ABCDRead
IR216doc 30217ITHD-BFLOAT32ABCDRead
IR218doc 30219System V-THDFLOAT32ABCDRead
IR220doc 30221System I-THDFLOAT32ABCDRead
IR224doc 30225Neutral CurrentFLOAT32ABCDRead
IR226doc 30227Run hourFLOAT32ABCDRead
IR228doc 30229On HourFLOAT32ABCDRead
IR230doc 30231No. of interruptsFLOAT32ABCDRead
IR266doc 30267Relay 1 statusFLOAT32ABCDRead
IR268doc 30269Relay 2 statusFLOAT32ABCDRead
IR332doc 30333Phase indicateFLOAT32ABCDRead
IR400doc 30401VR Harmonic-1FLOAT32ABCDRead
IR402doc 30403IR Harmonic-1FLOAT32ABCDRead
IR404doc 30405VR Harmonic-2FLOAT32ABCDRead
IR406doc 30407IR Harmonic-2FLOAT32ABCDRead
IR408doc 30409VR Harmonic-3FLOAT32ABCDRead
IR410doc 30411IR Harmonic-3FLOAT32ABCDRead
IR412doc 30413VR Harmonic-4FLOAT32ABCDRead
IR414doc 30415IR Harmonic-4FLOAT32ABCDRead
IR416doc 30417VR Harmonic-5FLOAT32ABCDRead
IR418doc 30419IR Harmonic-5FLOAT32ABCDRead
IR420doc 30421VR Harmonic-6FLOAT32ABCDRead
IR422doc 30423IR Harmonic-6FLOAT32ABCDRead
IR424doc 30425VR Harmonic-7FLOAT32ABCDRead
IR426doc 30427IR Harmonic-7FLOAT32ABCDRead
IR428doc 30429VR Harmonic-8FLOAT32ABCDRead
IR430doc 30431IR Harmonic-8FLOAT32ABCDRead
IR432doc 30433VR Harmonic-9FLOAT32ABCDRead
IR434doc 30435IR Harmonic-9FLOAT32ABCDRead
IR436doc 30437VR Harmonic-10FLOAT32ABCDRead
IR438doc 30439IR Harmonic-10FLOAT32ABCDRead
IR440doc 30441VR Harmonic-11FLOAT32ABCDRead
IR442doc 30443IR Harmonic-11FLOAT32ABCDRead
IR444doc 30445VR Harmonic-12FLOAT32ABCDRead
IR446doc 30447IR Harmonic-12FLOAT32ABCDRead
IR448doc 30449VR Harmonic-13FLOAT32ABCDRead
IR450doc 30451IR Harmonic-13FLOAT32ABCDRead
IR452doc 30453VR Harmonic-14FLOAT32ABCDRead
IR454doc 30455IR Harmonic-14FLOAT32ABCDRead
IR456doc 30457VR Harmonic-15FLOAT32ABCDRead
IR458doc 30459IR Harmonic-15FLOAT32ABCDRead
IR460doc 30461VR Harmonic-16FLOAT32ABCDRead
IR462doc 30463IR Harmonic-16FLOAT32ABCDRead
IR464doc 30465VR Harmonic-17FLOAT32ABCDRead
IR466doc 30467IR Harmonic-17FLOAT32ABCDRead
IR468doc 30469VR Harmonic-18FLOAT32ABCDRead
IR470doc 30471IR Harmonic-18FLOAT32ABCDRead
IR472doc 30473VR Harmonic-19FLOAT32ABCDRead
IR474doc 30475IR Harmonic-19FLOAT32ABCDRead
IR476doc 30477VR Harmonic-20FLOAT32ABCDRead
IR478doc 30479IR Harmonic-20FLOAT32ABCDRead
IR480doc 30481VR Harmonic-21FLOAT32ABCDRead
IR482doc 30483IR Harmonic-21FLOAT32ABCDRead
IR484doc 30485VR Harmonic-22FLOAT32ABCDRead
IR486doc 30487IR Harmonic-22FLOAT32ABCDRead
IR488doc 30489VR Harmonic-23FLOAT32ABCDRead
IR490doc 30491IR Harmonic-23FLOAT32ABCDRead
IR492doc 30493VR Harmonic-24FLOAT32ABCDRead
IR494doc 30495IR Harmonic-24FLOAT32ABCDRead
IR496doc 30497VR Harmonic-25FLOAT32ABCDRead
IR498doc 30499IR Harmonic-25FLOAT32ABCDRead
IR500doc 30501VR Harmonic-26FLOAT32ABCDRead
IR502doc 30503IR Harmonic-26FLOAT32ABCDRead
IR504doc 30505VR Harmonic-27FLOAT32ABCDRead
IR506doc 30507IR Harmonic-27FLOAT32ABCDRead
IR508doc 30509VR Harmonic-28FLOAT32ABCDRead
IR510doc 30511IR Harmonic-28FLOAT32ABCDRead
IR512doc 30513VR Harmonic-29FLOAT32ABCDRead
IR514doc 30515IR Harmonic-29FLOAT32ABCDRead
IR516doc 30517VR Harmonic-30FLOAT32ABCDRead
IR518doc 30519IR Harmonic-30FLOAT32ABCDRead
IR520doc 30521VR Harmonic-31FLOAT32ABCDRead
IR522doc 30523IR Harmonic-31FLOAT32ABCDRead
IR528doc 30529VY Harmonic-1FLOAT32ABCDRead
IR530doc 30531IY Harmonic-1FLOAT32ABCDRead
IR532doc 30533VY Harmonic-2FLOAT32ABCDRead
IR534doc 30535IY Harmonic-2FLOAT32ABCDRead
IR536doc 30537VY Harmonic-3FLOAT32ABCDRead
IR538doc 30539IY Harmonic-3FLOAT32ABCDRead
IR540doc 30541VY Harmonic-4FLOAT32ABCDRead
IR542doc 30543IY Harmonic-4FLOAT32ABCDRead
IR544doc 30545VY Harmonic-5FLOAT32ABCDRead
IR546doc 30547IY Harmonic-5FLOAT32ABCDRead
IR548doc 30549VY Harmonic-6FLOAT32ABCDRead
IR550doc 30551IY Harmonic-6FLOAT32ABCDRead
IR552doc 30553VY Harmonic-7FLOAT32ABCDRead
IR554doc 30555IY Harmonic-7FLOAT32ABCDRead
IR556doc 30557VY Harmonic-8FLOAT32ABCDRead
IR558doc 30559IY Harmonic-8FLOAT32ABCDRead
IR560doc 30561VY Harmonic-9FLOAT32ABCDRead
IR562doc 30563IY Harmonic-9FLOAT32ABCDRead
IR564doc 30565VY Harmonic-10FLOAT32ABCDRead
IR566doc 30567IY Harmonic-10FLOAT32ABCDRead
IR568doc 30569VY Harmonic-11FLOAT32ABCDRead
IR570doc 30571IY Harmonic-11FLOAT32ABCDRead
IR572doc 30573VY Harmonic-12FLOAT32ABCDRead
IR574doc 30575IY Harmonic-12FLOAT32ABCDRead
IR576doc 30577VY Harmonic-13FLOAT32ABCDRead
IR578doc 30579IY Harmonic-13FLOAT32ABCDRead
IR580doc 30581VY Harmonic-14FLOAT32ABCDRead
IR582doc 30583IY Harmonic-14FLOAT32ABCDRead
IR584doc 30585VY Harmonic-15FLOAT32ABCDRead
IR586doc 30587IY Harmonic-15FLOAT32ABCDRead
IR588doc 30589VY Harmonic-16FLOAT32ABCDRead
IR590doc 30591IY Harmonic-16FLOAT32ABCDRead
IR592doc 30593VY Harmonic-17FLOAT32ABCDRead
IR594doc 30595IY Harmonic-17FLOAT32ABCDRead
IR596doc 30597VY Harmonic-18FLOAT32ABCDRead
IR598doc 30599IY Harmonic-18FLOAT32ABCDRead
IR600doc 30601VY Harmonic-19FLOAT32ABCDRead
IR602doc 30603IY Harmonic-19FLOAT32ABCDRead
IR604doc 30605VY Harmonic-20FLOAT32ABCDRead
IR606doc 30607IY Harmonic-20FLOAT32ABCDRead
IR608doc 30609VY Harmonic-21FLOAT32ABCDRead
IR610doc 30611IY Harmonic-21FLOAT32ABCDRead
IR612doc 30613VY Harmonic-22FLOAT32ABCDRead
IR614doc 30615IY Harmonic-22FLOAT32ABCDRead
IR616doc 30617VY Harmonic-23FLOAT32ABCDRead
IR618doc 30619IY Harmonic-23FLOAT32ABCDRead
IR620doc 30621VY Harmonic-24FLOAT32ABCDRead
IR622doc 30623IY Harmonic-24FLOAT32ABCDRead
IR624doc 30625VY Harmonic-25FLOAT32ABCDRead
IR626doc 30627IY Harmonic-25FLOAT32ABCDRead
IR628doc 30629VY Harmonic-26FLOAT32ABCDRead
IR630doc 30631IY Harmonic-26FLOAT32ABCDRead
IR632doc 30633VY Harmonic-27FLOAT32ABCDRead
IR634doc 30635IY Harmonic-27FLOAT32ABCDRead
IR636doc 30637VY Harmonic-28FLOAT32ABCDRead
IR638doc 30639IY Harmonic-28FLOAT32ABCDRead
IR640doc 30641VY Harmonic-29FLOAT32ABCDRead
IR642doc 30643IY Harmonic-29FLOAT32ABCDRead
IR644doc 30645VY Harmonic-30FLOAT32ABCDRead
IR646doc 30647IY Harmonic-30FLOAT32ABCDRead
IR648doc 30649VY Harmonic-31FLOAT32ABCDRead
IR650doc 30651IY Harmonic-31FLOAT32ABCDRead
IR656doc 30657VB Harmonic-1FLOAT32ABCDRead
IR658doc 30659IB Harmonic-1FLOAT32ABCDRead
IR660doc 30661VB Harmonic-2FLOAT32ABCDRead
IR662doc 30663IB Harmonic-2FLOAT32ABCDRead
IR664doc 30665VB Harmonic-3FLOAT32ABCDRead
IR666doc 30667IB Harmonic-3FLOAT32ABCDRead
IR668doc 30669VB Harmonic-4FLOAT32ABCDRead
IR670doc 30671IB Harmonic-4FLOAT32ABCDRead
IR672doc 30673VB Harmonic-5FLOAT32ABCDRead
IR674doc 30675IB Harmonic-5FLOAT32ABCDRead
IR676doc 30677VB Harmonic-6FLOAT32ABCDRead
IR678doc 30679IB Harmonic-6FLOAT32ABCDRead
IR680doc 30681VB Harmonic-7FLOAT32ABCDRead
IR682doc 30683IB Harmonic-7FLOAT32ABCDRead
IR684doc 30685VB Harmonic-8FLOAT32ABCDRead
IR686doc 30687IB Harmonic-8FLOAT32ABCDRead
IR688doc 30689VB Harmonic-9FLOAT32ABCDRead
IR690doc 30691IB Harmonic-9FLOAT32ABCDRead
IR692doc 30693VB Harmonic-10FLOAT32ABCDRead
IR694doc 30695IB Harmonic-10FLOAT32ABCDRead
IR696doc 30697VB Harmonic-11FLOAT32ABCDRead
IR698doc 30699IB Harmonic-11FLOAT32ABCDRead
IR700doc 30701VB Harmonic-12FLOAT32ABCDRead
IR702doc 30703IB Harmonic-12FLOAT32ABCDRead
IR704doc 30705VB Harmonic-13FLOAT32ABCDRead
IR706doc 30707IB Harmonic-13FLOAT32ABCDRead
IR708doc 30709VB Harmonic-14FLOAT32ABCDRead
IR710doc 30711IB Harmonic-14FLOAT32ABCDRead
IR712doc 30713VB Harmonic-15FLOAT32ABCDRead
IR714doc 30715IB Harmonic-15FLOAT32ABCDRead
IR716doc 30717VB Harmonic-16FLOAT32ABCDRead
IR718doc 30719IB Harmonic-16FLOAT32ABCDRead
IR720doc 30721VB Harmonic-17FLOAT32ABCDRead
IR722doc 30723IB Harmonic-17FLOAT32ABCDRead
IR724doc 30725VB Harmonic-18FLOAT32ABCDRead
IR726doc 30727IB Harmonic-18FLOAT32ABCDRead
IR728doc 30729VB Harmonic-19FLOAT32ABCDRead
IR730doc 30731IB Harmonic-19FLOAT32ABCDRead
IR732doc 30733VB Harmonic-20FLOAT32ABCDRead
IR734doc 30735IB Harmonic-20FLOAT32ABCDRead
IR736doc 30737VB Harmonic-21FLOAT32ABCDRead
IR738doc 30739IB Harmonic-21FLOAT32ABCDRead
IR740doc 30741VB Harmonic-22FLOAT32ABCDRead
IR742doc 30743IB Harmonic-22FLOAT32ABCDRead
IR744doc 30745VB Harmonic-23FLOAT32ABCDRead
IR746doc 30747IB Harmonic-23FLOAT32ABCDRead
IR748doc 30749VB Harmonic-24FLOAT32ABCDRead
IR750doc 30751IB Harmonic-24FLOAT32ABCDRead
IR752doc 30753VB Harmonic-25FLOAT32ABCDRead
IR754doc 30755IB Harmonic-25FLOAT32ABCDRead
IR756doc 30757VB Harmonic-26FLOAT32ABCDRead
IR758doc 30759IB Harmonic-26FLOAT32ABCDRead
IR760doc 30761VB Harmonic-27FLOAT32ABCDRead
IR762doc 30763IB Harmonic-27FLOAT32ABCDRead
IR764doc 30765VB Harmonic-28FLOAT32ABCDRead
HR6002doc 46003Demand integration timeSetup parameter (float).FLOAT32ABCDRead/write
HR6004doc 46005Energy Resolution / unitSetup parameter (float).FLOAT32ABCDRead/write
HR6010doc 46011System typeSetup parameter (float).FLOAT32ABCDRead/write
HR6014doc 46015Reset parametersSetup parameter (float).FLOAT32ABCDRead/write
HR6018doc 46019RS485 setup codeSetup parameter (float).FLOAT32ABCDRead/write
HR6020doc 46021Node addressSetup parameter (float).FLOAT32ABCDRead/write
HR6032doc 46033PT primarySetup parameter (float).FLOAT32ABCDRead/write
HR6034doc 46035CT primarySetup parameter (float).FLOAT32ABCDRead/write
HR6040doc 46041Register Order/Word OrderSetup parameter (float).FLOAT32ABCDRead/write
HR6042doc 46043CTSecondarySetup parameter (float).FLOAT32ABCDRead/write
HR6044doc 46045PTSecondarySetup parameter (float).FLOAT32ABCDRead/write
HR6070doc 46071PasswordSetup parameter (float).FLOAT32ABCDRead/write
HR6076doc 46077Auto scrollSetup parameter (float).FLOAT32ABCDRead/write
HR6180doc 46181Version no.Read-only identification value (float).FLOAT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter

What Modbus registers does the Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter have?

This map lists 290 registers: 276 input registers, 14 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 30001/40001-style addresses next to the hex start address actually sent (30001 = 0x0000). Wire address = printed number - 30001 (input registers) or - 40001 (holding registers); every value here was cross-checked against the printed hex address.

What byte order does the Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter?

Start with IR 0 V1 (Voltage L1); IR 6 I1 (Current L1); IR 52 Watt Sum (Total active power (Watt Sum)); IR 70 Freq (Frequency); IR 62 PF Avg (Average power factor); IR 72 Wh import (Active energy import (Wh import)).

How do I enable Modbus control of the Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter?

Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.

Where is the official Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter Modbus documentation?

The source is RISH Master 3440 0.2S Interface Definition (DMAN-00IM-0711 Rev. C), revision 2019-05, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/rish-master-3440-class-02s-130/ID-RM3440-0.2s.pdf.

More Rishabh Instruments Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: RISH Master 3440 0.2S Interface Definition · DMAN-00IM-0711 Rev. C · rev. 2019-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.