The RISH EM DC 6001/6002 is a 96 x 96 mm programmable DC energy meter with one voltage input and up to four shunt current channels. Modbus RTU on RS-485 returns each value as a 32-bit float. This map covers voltage, per-channel current, power, import/export energy and ampere-hours, demands and min/max values, plus the main setup registers.
This page lists 223 Modbus registers for the Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter — 24 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.
- Manufacturer
- Rishabh Instruments
- Model
- RISH EM DC 6001 / 6002 multi-channel DC energy meter
- Equipment type
- Energy meter (DC)
- Registers
- 223 (24 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RISH EM DC 6001, RISH EM DC 6002, EM DC 6001, EM DC 6002
Integration notes: Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter
Read measured values with FC04 (or FC03 at the 4X copies) in pairs of registers and decode them as ABCD floats. Settings are floats too and are written with FC16.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Voltage | FLOAT32 ABCD | DC voltage | Read |
| IR 2 | Current Ch1 | FLOAT32 ABCD | Channel 1 current | Read |
| IR 10 | Power Ch1 | FLOAT32 ABCD | Channel 1 power | Read |
| IR 18 | Total Import Power | FLOAT32 ABCD | Total import power | Read |
| IR 38 | Total Import Energy | FLOAT32 ABCD | Total import energy | Read |
| IR 40 | Total Export Energy | FLOAT32 ABCD | Total export energy | Read |
Enable Modbus control & writes
Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.
Byte order & addressing
- Each parameter is two registers; reading or writing only half of a float returns an Illegal Data Address exception.
- Addresses are Modicon-style: subtract 30001 or 40001 for the wire address.
- Limit each read to 40 parameters (80 registers) or less.
Network setup
- Slave address range 1-247; broadcast (address 0) is not supported.
- Allow about 200 ms for the meter to answer before retrying.
Watch out for
- If a password lock is set, write the valid password to the Password register before changing any 4X setting; a wrong password returns exception code 2.
Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Voltage | FLOAT32 | ABCD | V | Read | |||
| IR | 2doc 30003 | Current Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 4doc 30005 | Current Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 6doc 30007 | Current Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 8doc 30009 | Current Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 10doc 30011 | Power Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 12doc 30013 | Power Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 14doc 30015 | Power Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 16doc 30017 | Power Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 18doc 30019 | Total Import Power | FLOAT32 | ABCD | Read | ||||
| IR | 20doc 30021 | Total export Power | FLOAT32 | ABCD | Read | ||||
| IR | 22doc 30023 | Energy Imp Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 24doc 30025 | Energy Imp Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 26doc 30027 | Energy Imp Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 28doc 30029 | Energy Imp Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 30doc 30031 | Energy Exp Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 32doc 30033 | Energy Exp Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 34doc 30035 | Energy Exp Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 36doc 30037 | Energy Exp Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 38doc 30039 | Total Import Energy | FLOAT32 | ABCD | Read | ||||
| IR | 40doc 30041 | Total Export Energy | FLOAT32 | ABCD | Read | ||||
| IR | 58doc 30059 | Amp Hour Imp Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 60doc 30061 | Amp Hour Imp Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 62doc 30063 | Amp Hour Imp Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 64doc 30065 | Amp Hour Imp Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 66doc 30067 | Amp Hour Exp Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 68doc 30069 | Amp Hour Exp Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 70doc 30071 | Amp Hour Exp Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 72doc 30073 | Amp Hour Exp Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 74doc 30075 | Total Import AH | FLOAT32 | ABCD | Read | ||||
| IR | 76doc 30077 | Total Export AH | FLOAT32 | ABCD | Read | ||||
| IR | 78doc 30079 | Import Power Demand Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 80doc 30081 | Import Power Demand Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 82doc 30083 | Import Power Demand Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 84doc 30085 | Import Power Demand Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 86doc 30087 | Export Power Demand Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 88doc 30089 | Export Power Demand Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 90doc 30091 | Export Power Demand Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 92doc 30093 | Export Power Demand Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 94doc 30095 | Total Import Power Demand | FLOAT32 | ABCD | Read | ||||
| IR | 96doc 30097 | Total Export Power Demand | FLOAT32 | ABCD | Read | ||||
| IR | 98doc 30099 | Import Current Demand Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 100doc 30101 | Import Current Demand Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 102doc 30103 | Import Current Demand Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 104doc 30105 | Import Current Demand Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 106doc 30107 | Export Current Demand Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 108doc 30109 | Export Current Demand Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 110doc 30111 | Export Current Demand Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 112doc 30113 | Export Current Demand Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 114doc 30115 | Total Import Current Demand | FLOAT32 | ABCD | Read | ||||
| IR | 116doc 30117 | Total Export Current Demand | FLOAT32 | ABCD | Read | ||||
| IR | 118doc 30119 | Max Voltage | FLOAT32 | ABCD | Read | ||||
| IR | 120doc 30121 | Min Voltage | FLOAT32 | ABCD | Read | ||||
| IR | 122doc 30123 | Max Current Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 124doc 30125 | Max Current Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 126doc 30127 | Max Current Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 128doc 30129 | Max Current Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 130doc 30131 | Min Current Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 132doc 30133 | Min Current Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 134doc 30135 | Min Current Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 136doc 30137 | Min Current Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 138doc 30139 | Max Import Power Demand Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 140doc 30141 | Max Import Power Demand Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 142doc 30143 | Max Import Power Demand Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 144doc 30145 | Max Import Power Demand Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 146doc 30147 | Max Export Power Demand Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 148doc 30149 | Max Export Power Demand Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 150doc 30151 | Max Export Power Demand Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 152doc 30153 | Max Export Power Demand Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 154doc 30155 | Max Import Current Demand Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 156doc 30157 | Max Import Current Demand Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 158doc 30159 | Max Import Current Demand Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 160doc 30161 | Max Import Current Demand Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 162doc 30163 | Max Export Current Demand Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 164doc 30165 | Max Export Current Demand Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 166doc 30167 | Max Export Current Demand Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 168doc 30169 | Max Export Current Demand Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 170doc 30171 | Energy Imp Ch1 on update rate | FLOAT32 | ABCD | Read | ||||
| IR | 172doc 30173 | Energy Imp Ch2 on update rate | FLOAT32 | ABCD | Read | ||||
| IR | 174doc 30175 | Energy Imp Ch3 on update rate | FLOAT32 | ABCD | Read | ||||
| IR | 176doc 30177 | Energy Imp Ch4 on update rate | FLOAT32 | ABCD | Read | ||||
| IR | 178doc 30179 | Energy Import Ch1 on update rate OF | FLOAT32 | ABCD | Read | ||||
| IR | 180doc 30181 | Energy Import Ch2 on update rate OF | FLOAT32 | ABCD | Read | ||||
| IR | 182doc 30183 | Energy Import Ch3 on update rate OF | FLOAT32 | ABCD | Read | ||||
| IR | 184doc 30185 | Energy Import Ch4 on update rate OF | FLOAT32 | ABCD | Read | ||||
| IR | 186doc 30187 | Energy Exp Ch1 on update rate | FLOAT32 | ABCD | Read | ||||
| IR | 188doc 30189 | Energy Exp Ch2 on update rate | FLOAT32 | ABCD | Read | ||||
| IR | 190doc 30191 | Energy Exp Ch3 on update rate | FLOAT32 | ABCD | Read | ||||
| IR | 192doc 30193 | Energy Exp Ch4 on update rate | FLOAT32 | ABCD | Read | ||||
| IR | 194doc 30195 | Energy Export Ch1 on update rate OF | FLOAT32 | ABCD | Read | ||||
| IR | 196doc 30197 | Energy Export Ch2 on update rate OF | FLOAT32 | ABCD | Read | ||||
| IR | 198doc 30199 | Energy Export Ch3 on update rate OF | FLOAT32 | ABCD | Read | ||||
| IR | 200doc 30201 | Energy Export Ch4 on update rate OF | FLOAT32 | ABCD | Read | ||||
| IR | 202doc 30203 | On Hour | FLOAT32 | ABCD | Read | ||||
| IR | 204doc 30205 | Run Hour Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 206doc 30207 | Run Hour Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 208doc 30209 | Run Hour Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 210doc 30211 | Run Hour Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 212doc 30213 | No. of Interruptions | FLOAT32 | ABCD | Read | ||||
| IR | 214doc 30215 | Old Energy Imp Ch 1 | FLOAT32 | ABCD | Read | ||||
| IR | 216doc 30217 | Old Energy Imp Ch 2 | FLOAT32 | ABCD | Read | ||||
| IR | 218doc 30219 | Old Energy Imp Ch 3 | FLOAT32 | ABCD | Read | ||||
| IR | 220doc 30221 | Old Energy Imp Ch 4 | FLOAT32 | ABCD | Read | ||||
| IR | 222doc 30223 | Old Energy Import Ch1 OF | FLOAT32 | ABCD | Read | ||||
| IR | 224doc 30225 | Old Energy Import Ch2 OF | FLOAT32 | ABCD | Read | ||||
| IR | 226doc 30227 | Old Energy Import Ch3 OF | FLOAT32 | ABCD | Read | ||||
| IR | 228doc 30229 | Old Energy Import Ch4 OF | FLOAT32 | ABCD | Read | ||||
| IR | 230doc 30231 | Old Energy Exp Ch 1 | FLOAT32 | ABCD | Read | ||||
| IR | 232doc 30233 | Old Energy Exp Ch 2 | FLOAT32 | ABCD | Read | ||||
| IR | 234doc 30235 | Old Energy Exp Ch 3 | FLOAT32 | ABCD | Read | ||||
| IR | 236doc 30237 | Old Energy Exp Ch 4 | FLOAT32 | ABCD | Read | ||||
| IR | 238doc 30239 | Old Energy Export Ch1 OF | FLOAT32 | ABCD | Read | ||||
| IR | 240doc 30241 | Old Energy Export Ch2 OF | FLOAT32 | ABCD | Read | ||||
| IR | 242doc 30243 | Old Energy Export Ch3 OF | FLOAT32 | ABCD | Read | ||||
| IR | 244doc 30245 | Old Energy Export Ch4 OF | FLOAT32 | ABCD | Read | ||||
| IR | 246doc 30247 | Old Amp Hour Imp Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 248doc 30249 | Old Amp Hour Imp Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 250doc 30251 | Old Amp Hour Imp Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 252doc 30253 | Old Amp Hour Imp Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 254doc 30255 | Old Amp Hour Exp Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 256doc 30257 | Old Amp Hour Exp Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 258doc 30259 | Old Amp Hour Exp Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 260doc 30261 | Old Amp Hour Exp Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 262doc 30263 | Old Max Import Power Demand Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 264doc 30265 | Old Max Import Power Demand Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 266doc 30267 | Old Max Import Power Demand Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 268doc 30269 | Old Max Import Power Demand Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 270doc 30271 | Old Max Export Power Demand Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 272doc 30273 | Old Max Export Power Demand Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 274doc 30275 | Old Max Export Power Demand Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 276doc 30277 | Old Max Export Power Demand Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 278doc 30279 | Old Max Import Current Demand Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 280doc 30281 | Old Max Import Current Demand Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 282doc 30283 | Old Max Import Current Demand Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 284doc 30285 | Old Max Import Current Demand Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 286doc 30287 | Old Max Export Current Demand Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 288doc 30289 | Old Max Export Current Demand Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 290doc 30291 | Old Max Export Current Demand Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 292doc 30293 | Old Max Export Current Demand Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 294doc 30295 | Old On Hour | FLOAT32 | ABCD | Read | ||||
| IR | 296doc 30297 | Old Run Hour Ch1 | FLOAT32 | ABCD | Read | ||||
| IR | 298doc 30299 | Old Run Hour Ch2 | FLOAT32 | ABCD | Read | ||||
| IR | 300doc 30301 | Old Run Hour Ch3 | FLOAT32 | ABCD | Read | ||||
| IR | 302doc 30303 | Old Run Hour Ch4 | FLOAT32 | ABCD | Read | ||||
| IR | 304doc 30305 | Old No. of Interruptions | FLOAT32 | ABCD | Read | ||||
| IR | 306doc 30307 | Energy Import Ch1 OF | FLOAT32 | ABCD | Read | ||||
| IR | 308doc 30309 | Energy Import Ch2 OF | FLOAT32 | ABCD | Read | ||||
| IR | 310doc 30311 | Energy Import Ch3 OF | FLOAT32 | ABCD | Read | ||||
| IR | 312doc 30313 | Energy Import Ch4 OF | FLOAT32 | ABCD | Read | ||||
| IR | 314doc 30315 | Energy Export Ch1 OF | FLOAT32 | ABCD | Read | ||||
| IR | 316doc 30317 | Energy Export Ch2 OF | FLOAT32 | ABCD | Read | ||||
| IR | 318doc 30319 | Energy Export Ch3 OF | FLOAT32 | ABCD | Read | ||||
| IR | 320doc 30321 | Energy Export Ch4 OF | FLOAT32 | ABCD | Read | ||||
| IR | 322doc 30323 | Total Import Energy OF | FLOAT32 | ABCD | Read | ||||
| IR | 324doc 30325 | Total Export Energy OF | FLOAT32 | ABCD | Read | ||||
| IR | 326doc 30327 | AH Import Ch1 OF | FLOAT32 | ABCD | Read | ||||
| IR | 328doc 30329 | AH Import Ch2 OF | FLOAT32 | ABCD | Read | ||||
| IR | 330doc 30331 | AH Import Ch3 OF | FLOAT32 | ABCD | Read | ||||
| IR | 332doc 30333 | AH Import Ch4 OF | FLOAT32 | ABCD | Read | ||||
| IR | 334doc 30335 | AH Export Ch1 OF | FLOAT32 | ABCD | Read | ||||
| IR | 336doc 30337 | AH Export Ch2 OF | FLOAT32 | ABCD | Read | ||||
| IR | 338doc 30339 | AH Export Ch3 OF | FLOAT32 | ABCD | Read | ||||
| IR | 340doc 30341 | AH Export Ch4 OF | FLOAT32 | ABCD | Read | ||||
| IR | 342doc 30343 | Total Import AH OF | FLOAT32 | ABCD | Read | ||||
| IR | 344doc 30345 | Total Export AH OF | FLOAT32 | ABCD | Read | ||||
| IR | 346doc 30347 | Old AH Import Ch1 OF | FLOAT32 | ABCD | Read | ||||
| IR | 348doc 30349 | Old AH Import Ch2 OF | FLOAT32 | ABCD | Read | ||||
| IR | 350doc 30351 | Old AH Import Ch3 OF | FLOAT32 | ABCD | Read | ||||
| IR | 352doc 30353 | Old AH Import Ch4 OF | FLOAT32 | ABCD | Read | ||||
| IR | 354doc 30355 | Old AH Export Ch1 OF | FLOAT32 | ABCD | Read | ||||
| IR | 356doc 30357 | Old AH Export Ch2 OF | FLOAT32 | ABCD | Read | ||||
| IR | 358doc 30359 | Old AH Export Ch3 OF | FLOAT32 | ABCD | Read | ||||
| IR | 360doc 30361 | Old AH Export Ch4 OF | FLOAT32 | ABCD | Read | ||||
| IR | 362doc 30363 | Relay 1 Status | FLOAT32 | ABCD | Read | ||||
| IR | 364doc 30365 | Relay 2 Status | FLOAT32 | ABCD | Read | ||||
| IR | 366doc 30367 | Relay 3 Status | FLOAT32 | ABCD | Read | ||||
| IR | 368doc 30369 | Relay 4 Status | FLOAT32 | ABCD | Read | ||||
| IR | 370doc 30371 | Timer 1 On Delay | FLOAT32 | ABCD | Read | ||||
| IR | 372doc 30373 | Timer 2 On Delay | FLOAT32 | ABCD | Read | ||||
| IR | 374doc 30375 | Timer 3 On Delay | FLOAT32 | ABCD | Read | ||||
| IR | 376doc 30377 | Timer 4 On Delay | FLOAT32 | ABCD | Read | ||||
| IR | 378doc 30379 | Timer 1 Off Delay | FLOAT32 | ABCD | Read | ||||
| IR | 380doc 30381 | Timer 2 Off Delay | FLOAT32 | ABCD | Read | ||||
| IR | 382doc 30383 | Timer 3 Off Delay | FLOAT32 | ABCD | Read | ||||
| IR | 384doc 30385 | Timer 4 Off Delay | FLOAT32 | ABCD | Read | ||||
| IR | 386doc 30387 | Timer 1 No of Cycles | FLOAT32 | ABCD | Read | ||||
| IR | 388doc 30389 | Timer 2 No of Cycles | FLOAT32 | ABCD | Read | ||||
| IR | 390doc 30391 | Timer 3 No of Cycles | FLOAT32 | ABCD | Read | ||||
| IR | 392doc 30393 | Timer 4 No of Cycles | FLOAT32 | ABCD | Read | ||||
| IR | 394doc 30395 | RTC Min | FLOAT32 | ABCD | Read | ||||
| IR | 396doc 30397 | RTC Hour | FLOAT32 | ABCD | Read | ||||
| IR | 398doc 30399 | RTC Day of Week | FLOAT32 | ABCD | Read | ||||
| IR | 400doc 30401 | RTC Date | FLOAT32 | ABCD | Read | ||||
| IR | 402doc 30403 | RTC Month | FLOAT32 | ABCD | Read | ||||
| IR | 404doc 30405 | RTC Year | FLOAT32 | ABCD | Read | ||||
| IR | 406doc 30407 | RTC Complete Date* | FLOAT32 | ABCD | Read | ||||
| IR | 408doc 30409 | RTC Complete Time* | FLOAT32 | ABCD | Read | ||||
| HR | 2doc 40003 | Demand Integration Time | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 4doc 40005 | Reset parameters | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6doc 40007 | RS485 Setup Code | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 8doc 40009 | Mod address | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 26doc 40027 | Nominal Voltage | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 28doc 40029 | Auto Detect Nominal Voltage | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 30doc 40031 | Channel Select | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 32doc 40033 | Current - Full Scale Ch1 | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 34doc 40035 | Current - Full Scale Ch2 | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 36doc 40037 | Current - Full Scale Ch3 | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 38doc 40039 | Current - Full Scale Ch4 | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 40doc 40041 | Current - Shunt Ch1 | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 42doc 40043 | Current - Shunt Ch2 | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 44doc 40045 | Current - Shunt Ch3 | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 46doc 40047 | Current - Shunt Ch4 | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 60doc 40061 | Energy Output Ch1 | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 62doc 40063 | Energy Output Ch2 | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 64doc 40065 | Energy Output Ch3 | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 66doc 40067 | Energy Output Ch4 | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 72doc 40073 | Register order | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 74doc 40075 | Auto Scroll | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 94doc 40095 | Password | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 96doc 40097 | Serial Number | Read-only identification value (float). | FLOAT32 | ABCD | Read | |||
| HR | 98doc 40099 | Model Number | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 100doc 40101 | Firmware Version Number | Read-only identification value (float). | FLOAT32 | ABCD | Read | |||
| HR | 360doc 40361 | Password for Energy Starting Count | Setup parameter (float). | FLOAT32 | ABCD | Read/write |
Notes on this map
- Measured values are IEEE-754 32-bit floats in two registers. The manual's example responses (e.g. data bytes 43 5B 41 21 for a current reading) put the most significant register first, so ABCD is the default order.
- Register 40073 (Word Order) can switch the meter to reversed register order; the manual says to write 2141.0 to it and the meter detects which order was used. If floats look wrong, check this setting.
- Rows whose printed hex address does not match the decimal 3X/4X address in the manual were left out rather than guessed.
- Left out: the 32-bit integer energy tables (their integer word order is not demonstrated in the manual), user-assignable registers and data-log blocks.
- Where the register table has no unit column, units are left blank; energy registers follow the energy unit (Wh/kWh/MWh) configured on the meter, and 'OF' / overflow registers count roll-overs of the matching energy register.
- The manual's 4X copies of measured values start at 44097 (hex 0x1000), not at 40001; this map lists the 3X addresses only.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter
What Modbus registers does the Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter have?
This map lists 223 registers: 197 input registers, 26 holding registers. 24 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 30001/40001-style addresses next to the hex start address actually sent (30001 = 0x0000). Wire address = printed number - 30001 (input registers) or - 40001 (holding registers); every value here was cross-checked against the printed hex address.
What byte order does the Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter?
Start with IR 0 Voltage (DC voltage); IR 2 Current Ch1 (Channel 1 current); IR 10 Power Ch1 (Channel 1 power); IR 18 Total Import Power (Total import power); IR 38 Total Import Energy (Total import energy); IR 40 Total Export Energy (Total export energy).
How do I enable Modbus control of the Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter?
Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.
Where is the official Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter Modbus documentation?
The source is RISH EM DC Interface Definition (2-60-006-00-00627 Rev. 0), revision 2015-10, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/multi-channel-dc-energy-meter-rish-em-dc-6001-6002-146/RISH_EM_DC__Interface_definition.pdf.
More Rishabh Instruments Modbus register maps
- Energy meter (DC)
Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter
Rishabh RISH DC2111 MOD single-channel DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-1669 Rev. D (08/25).
Also known as: RISH DC2111 MOD, DC2111 - Energy meter
Rishabh Instruments RISH Delta Energy NX multifunction energy meter
Rishabh RISH Delta Energy NX panel energy meters with RS-485 Modbus RTU, per the operating manual on the product page (standard CT version).
Also known as: RISH Delta Energy NX, Delta Energy NX, RISH Delta Energy - Power meter
Rishabh Instruments RISH Delta Power NX multifunction power meter
Rishabh RISH Delta Power NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0117 Rev. E.
Also known as: RISH Delta Power NX, Delta Power NX, RISH Delta Power - Power meter
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
Rishabh RISH Delta VAF NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0118 Rev. F.
Also known as: RISH Delta VAF NX, Delta VAF NX, RISH Delta VAF - Power meter (demand controller)
Rishabh Instruments RISH DMCi touch-screen demand controller with TOD
Rishabh RISH DMCi 96 x 96 mm touch-screen demand controllers with the optional RS-485 Modbus output, per interface definition DMAN-00IM-0578 Rev. A (09/16).
Also known as: RISH DMCi, DMCi, Rish DMCi demand controller - Energy meter
Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters
Rishabh RISH EC43xx and ER43xx DIN-rail digital energy meters with RS-485 Modbus, per interface definition DMAN-00IM-09xx Rev. F (11/25).
Also known as: EC4311, EC4321, ER4311, ER4321, RISH EC43X1, EC43XX, ER43XX - Energy meter
Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters
Rishabh RISH ED11XX (direct), EC11XX (CT) and ER11XX (RJ12 CT) single-phase DIN-rail meters in their Modbus (x1) versions, per operating manual DMAN-00IM-1071 Rev. M.
Also known as: RISH ED11X1, RISH EC11X1, RISH ER11X1, ED1111, EC1111, ER1111, RISH ED11XX, RISH EC11XX, RISH ER11XX - Energy meter
Rishabh Instruments RISH ED21XX / EC21XX / ER21XX single-phase energy meters
Rishabh RISH ED21XX (direct), EC21XX (CT) and ER21XX (RJ12 CT) single-phase meters in their Modbus versions, per operating manual DMAN-00IM-1073 Rev. M.
Also known as: RISH ED21X1, RISH EC21X1, RISH ER21X1, RISH ED21XX, RISH EC21XX, RISH ER21XX - Energy meter
Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters
Rishabh RISH EM 1320/1330/1340 and EM 2320/2330/2340 panel energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0721 Rev. B (06/2020). Rows marked 'only 2340' apply to the dual-source EM 2340.
Also known as: RISH EM 1320, RISH EM 1330, RISH EM 1340, RISH EM 2320, RISH EM 2330, RISH EM 2340, EM2340DS - Energy meter
Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter
Rishabh RISH EM 3490 DS dual-source energy meters (separate utility and generator energy) with RS-485 Modbus, per manual Rev G.
Also known as: RISH EM 3490 DS, EM3490DS, EM 3490DS - Energy meter
Rishabh Instruments RISH EM 3490 SS single-phase energy meter
Rishabh RISH EM 3490 SS single-phase energy meters with the optional RS-485 Modbus output, per the 1-phase manual Rev D.
Also known as: RISH EM 3490 SS 1P, EM3490SS 1P, EM 3490 SS single-phase - Energy meter
Rishabh Instruments RISH EM 3490 SS three-phase single-source energy meter
Rishabh RISH EM 3490 SS three-phase energy meters with the optional RS-485 Modbus output, per the 3-phase manual Rev E.
Also known as: RISH EM 3490 SS 3P, EM3490SS 3P, EM 3490 SS three-phase - Energy meter (DC)
Rishabh Instruments RISH EM DC 6000 programmable DC energy meter
Rishabh RISH EM DC 6000 single-channel programmable DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0862 Rev. 0 (12/2020).
Also known as: RISH EM DC 6000, EMDC 6000, EM DC6000 - Power meter
Rishabh Instruments RISH LM 1340 multifunction meter
Rishabh RISH LM 1340 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. D (03/2026).
Also known as: RISH LM 1340, LM1340 - Power meter
Rishabh Instruments RISH LM 1360 load manager (LM 13xx)
Rishabh RISH LM 1360 panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0662 Rev. D (01/2024).
Also known as: RISH LM 1360, LM1360, LM 13xx, LM1360 RJ12 - Power meter
Rishabh Instruments RISH LM 1380 multifunction meter
Rishabh RISH LM 1380 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0925 Rev. A (04/2022).
Also known as: RISH LM 1380, LM1380 - Power meter
Rishabh Instruments RISH LM1360+ RJ12 smart energy meter
Rishabh RISH LM1360 PLUS RJ12 smart energy meters (RJ12 CT inputs) with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. A (01/2026).
Also known as: RISH LM 1360+, LM1360 PLUS RJ12, LM1360+ - Power meter
Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter
Rishabh RISH Master 3440 class 0.2S panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0711 Rev. C (05/2019).
Also known as: RISH Master 3440, RM3440, Master 3440 0.2S - Power meter
Rishabh Instruments RISH Master 3440i / 3440iDL (class 0.2S) touch-screen meter
Rishabh RISH Master 3440i and 3440iDL touch-screen class 0.2S meters with RS-485 Modbus, per interface definition DMAN-00IM-0712 Rev. F (10/2026).
Also known as: RISH Master 3440i, RISH Master 3440iDL, RM3440i, RM3440iDL - Power meter (multi-circuit energy meter)
Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)
RISH Multiload Monitor (12 current channels, 4 voltage channels) per interface definition DMAN-00IM-0795 Rev A (08/2020).
Also known as: RISH ML 1400, RISH ML 1410, RISH MLM, Multiload Monitor - Power meter (power factor controller)
Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller
Rishabh RISH PFC 96 and PFC 144 automatic power factor (APFC) controllers with RS-485 Modbus RTU, per interface definition version D (12/18).
Also known as: RISH PFC 96, RISH PFC 144, PFC96, PFC144, RISH PFC-12, APFC
Other power & energy meters register maps
- Power meter (power quality analyzer)
SATEC PM174 powermeter and power quality analyzer
SATEC PM174 from firmware 24.3.1, per Modbus reference guide BG0414 Rev. A7 (April 2013).
Also known as: PM174, SATEC PM174, PM 174 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Power meter (power quality)
Siemens SICAM P850 / P855 power monitoring and PQ device
SICAM P850 / P855 (7KG85x) with Modbus TCP or Modbus RTU, firmware V3.11, per communication manual E50417-C1040-C482-B1 (05.2024).
Also known as: 7KG85, 7KG85X, SICAM P850, SICAM P855 - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Energy meter (thermal / BTU meter)
Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP)
Belimo Thermal Energy Meter DN 15...50 version 4 (22PE..-1U.., 22PF-..U..), interface description V4.2.0 edition 2025-11.
Also known as: 22PE-1U, 22PEM-1UC, 22PE..-1U.., 22PF, Belimo Thermal Energy Meter, Belimo TEM
All power & energy meters Modbus register maps →
Source: RISH EM DC Interface Definition · 2-60-006-00-00627 Rev. 0 · rev. 2015-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.