- Home
- Modbus register maps
- Rishabh Instruments
- RISH Delta VAF NX volt/amp/frequency panel meter
Power meter · Modbus register map
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter Modbus register map
Updated 19 November 2026
The RISH Delta VAF NX is a 96 x 96 mm panel meter that shows voltage, current, power factor and frequency on 1-phase and 3-phase networks, with an RS-485 Modbus RTU port. Every value is an IEEE 754 float in two registers: measurements are input registers (FC04) from 30001, mirrored as holding registers at 40001+, and setup parameters sit at 46003-46085. This map covers the measured values, run/on hours and the setup block.
This page lists 52 Modbus registers for the Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.
- Manufacturer
- Rishabh Instruments
- Model
- RISH Delta VAF NX volt/amp/frequency panel meter
- Equipment type
- Power meter
- Registers
- 52 (21 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RISH Delta VAF NX, Delta VAF NX, RISH Delta VAF
Integration notes: Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
Read 30001-30072 with FC04 and decode each register pair as a big-endian float. Settings are floats at 46003+ written with FC16.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | V1 | FLOAT32 ABCD | Voltage L1 | Read |
| IR 6 | I1 | FLOAT32 ABCD | Current L1 | Read |
| IR 42 | Volt average | FLOAT32 ABCD | Average voltage | Read |
| IR 62 | PF average | FLOAT32 ABCD | Average power factor | Read |
| IR 70 | System frequency | FLOAT32 ABCD | Frequency | Read |
Enable Modbus control & writes
Set the Modbus address (46047, default 1) and Comsetup code (46045, default 8 = 9600 8N1) from the front panel or over Modbus.
Byte order & addressing
- Setup values are floats too: system type 3 reads back as 40 40 00 00.
- Reading or writing half a float returns exception 02.
- If a password is set, write it to 46033 before changing setup registers.
Network setup
- Comsetup (46045) packs baud 4800-57600, parity and stop bits into one code; see the value list.
Watch out for
- Per-phase PF and line-to-line voltages are only valid for the wiring types noted in each description.
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | V1 | L1 voltage (L-N on 4-wire, L-L on 3-wire). | FLOAT32 | ABCD | Read | |||
| IR | 2doc 30003 | V2 | Not on 1P2W. | FLOAT32 | ABCD | Read | |||
| IR | 4doc 30005 | V3 | 3P4W and 3P3W only. | FLOAT32 | ABCD | Read | |||
| IR | 6doc 30007 | I1 | FLOAT32 | ABCD | Read | ||||
| IR | 8doc 30009 | I2 | Not on 1P2W. | FLOAT32 | ABCD | Read | |||
| IR | 10doc 30011 | I3 | 3P4W and 3P3W only. | FLOAT32 | ABCD | Read | |||
| IR | 30doc 30031 | PF1 | Not on 3P3W. | FLOAT32 | ABCD | Read | |||
| IR | 32doc 30033 | PF2 | 3P4W and 1P3W only. | FLOAT32 | ABCD | Read | |||
| IR | 34doc 30035 | PF3 | 3P4W only. | FLOAT32 | ABCD | Read | |||
| IR | 42doc 30043 | Volt average | FLOAT32 | ABCD | Read | ||||
| IR | 44doc 30045 | Volt sum | Not on 1P2W. | FLOAT32 | ABCD | Read | |||
| IR | 46doc 30047 | Current average | FLOAT32 | ABCD | Read | ||||
| IR | 48doc 30049 | Current sum | Not on 1P2W. | FLOAT32 | ABCD | Read | |||
| IR | 62doc 30063 | PF average | FLOAT32 | ABCD | Read | ||||
| IR | 64doc 30065 | PF sum | 3P4W and 1P3W only. | FLOAT32 | ABCD | Read | |||
| IR | 70doc 30071 | System frequency | FLOAT32 | ABCD | Read | ||||
| IR | 136doc 30137 | System voltage max | FLOAT32 | ABCD | Read | ||||
| IR | 138doc 30139 | System voltage min | FLOAT32 | ABCD | Read | ||||
| IR | 140doc 30141 | RPM | Generator speed from 46039 poles. | FLOAT32 | ABCD | Read | |||
| IR | 142doc 30143 | Impulse rate | FLOAT32 | ABCD | Read | ||||
| IR | 144doc 30145 | System current max | FLOAT32 | ABCD | Read | ||||
| IR | 146doc 30147 | System current min | FLOAT32 | ABCD | Read | ||||
| IR | 200doc 30201 | V12 | 3P4W only. | FLOAT32 | ABCD | Read | |||
| IR | 202doc 30203 | V23 | 3P4W only. | FLOAT32 | ABCD | Read | |||
| IR | 204doc 30205 | V31 | 3P4W only. | FLOAT32 | ABCD | Read | |||
| IR | 224doc 30225 | Neutral current | 3P4W only. | FLOAT32 | ABCD | Read | |||
| IR | 226doc 30227 | Run hour | FLOAT32 | ABCD | Read | ||||
| IR | 228doc 30229 | On hour | FLOAT32 | ABCD | Read | ||||
| IR | 230doc 30231 | No. of interrupts | FLOAT32 | ABCD | Read | ||||
| IR | 262doc 30263 | Relay 1 status | FLOAT32 | ABCD | Read | ||||
| HR | 6002doc 46003 | System type | Default 3. | FLOAT32 | ABCD | Read/write | 1 = 1-phase 2-wire; 2 = 3-phase 3-wire; 3 = 3-phase 4-wire; 4 = 1-phase 3-wire | ||
| HR | 6004doc 46005 | PT primary | Max 1200 kV L-L (also limited by 1000 MVA per phase); default 415. | FLOAT32 | ABCD | Read/write | |||
| HR | 6006doc 46007 | CT primary | 1-9999; default 5. | FLOAT32 | ABCD | Read/write | |||
| HR | 6008doc 46009 | PT secondary | 100-500 V L-L; default 415. | FLOAT32 | ABCD | Read/write | |||
| HR | 6010doc 46011 | CT secondary | FLOAT32 | ABCD | Read/write | 1 = 1 A; 5 = 5 A | |||
| HR | 6030doc 46031 | Reset parameters | FLOAT32 | ABCD | Write | 1 = Lo (min); 2 = Hi (max); 4 = Run hour; 5 = On hour; 6 = No. of interrupts; 7 = Reset all | |||
| HR | 6032doc 46033 | Password | 0000-9999; reads 0 when locked, 1 when unlocked. | FLOAT32 | ABCD | Read/write | |||
| HR | 6034doc 46035 | Factory reset | Write 5555 to restore factory defaults. | FLOAT32 | ABCD | Write | |||
| HR | 6038doc 46039 | No. of poles | Generator poles for RPM, 2-40 even. | FLOAT32 | ABCD | Read/write | |||
| HR | 6040doc 46041 | Autoscroll | FLOAT32 | ABCD | Read/write | 0 = Off; 1 = On | |||
| HR | 6042doc 46043 | Noise cutoff | FLOAT32 | ABCD | Read/write | 0 = 0 mA; 30 = 30 mA | |||
| HR | 6044doc 46045 | Comsetup (RS485 set-up code) | Default 8 (9600 bps, no parity, 1 stop). | FLOAT32 | ABCD | Read/write | 4 = 4800 bps, no parity, 1 stop; 5 = 4800 bps, no parity, 2 stop; 6 = 4800 bps, even, 1 stop; 7 = 4800 bps, odd, 1 stop; 8 = 9600 bps, no parity, 1 stop; 9 = 9600 bps, no parity, 2 stop; 10 = 9600 bps, even, 1 stop; 11 = 9600 bps, odd, 1 stop; 12 = 19200 bps, no parity, 1 stop; 13 = 19200 bps, no parity, 2 stop; 14 = 19200 bps, even, 1 stop; 15 = 19200 bps, odd, 1 stop; 16 = 38400 bps, no parity, 1 stop; 17 = 38400 bps, no parity, 2 stop; 18 = 38400 bps, even, 1 stop; 19 = 38400 bps, odd, 1 stop; 20 = 57600 bps, no parity, 1 stop; 21 = 57600 bps, no parity, 2 stop; 22 = 57600 bps, even, 1 stop; 23 = 57600 bps, odd, 1 stop | ||
| HR | 6046doc 46047 | Modbus address | 1-247; default 1. | FLOAT32 | ABCD | Read/write | |||
| HR | 6048doc 46049 | Register order / word order | Write 2141.0 in the wanted order to switch normal/reversed float word order. | FLOAT32 | ABCD | Read/write | |||
| HR | 6054doc 46055 | Relay 1 output select | FLOAT32 | ABCD | Read/write | 0 = None; 2 = Limit output | |||
| HR | 6056doc 46057 | Limit 1 parameter select | Parameter number per manual Table 2. | FLOAT32 | ABCD | Read/write | |||
| HR | 6058doc 46059 | Limit 1 configuration | FLOAT32 | ABCD | Read/write | 0 = Hi-alarm, energized relay; 1 = Hi-alarm, de-energized relay; 2 = Lo-alarm, energized relay; 3 = Lo-alarm, de-energized relay | |||
| HR | 6060doc 46061 | Limit 1 trip point | Percent; values per manual Table 2. | FLOAT32 | ABCD | Read/write | |||
| HR | 6062doc 46063 | Limit 1 hysteresis | Percent; printed as 0.5-50 % in Table 4 and 0-50 in the text; default 50. | FLOAT32 | ABCD | Read/write | |||
| HR | 6064doc 46065 | Limit 1 on delay | 1-10. | FLOAT32 | ABCD | Read/write | |||
| HR | 6066doc 46067 | Limit 1 off delay | 1-10. | FLOAT32 | ABCD | Read/write | |||
| HR | 6084doc 46085 | Version no. | Firmware version. | FLOAT32 | ABCD | Read |
Notes on this map
- The data-format table states IEEE 754 floats, most significant byte first; the Volts 3 example returns 43 5B 41 21 (219.25 V), so ABCD is the default. 46049 can switch to reversed order.
- Every 3X value can also be read with FC03 at the number plus 10000; only the 3X copies are listed (the manual misprints the 4X copy of 30225 as 402254).
- The register table has no unit column, so units are left blank.
- Left out: 30243 (printed with the same name as 30231), the min/max history from 31301 and the user-assignable registers (35201-35239).
- Up to 40 parameters (80 registers) per read request.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
What Modbus registers does the Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter have?
This map lists 52 registers: 30 input registers, 22 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 3X/4X register numbers. Wire address = number - 30001 (FC04) or - 40001 (FC03/FC16): the Volts 3 example (30005) starts at 00 04 and the system-type example (46003) starts at 17 72 (6002).
What byte order does the Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter?
Start with IR 0 V1 (Voltage L1); IR 6 I1 (Current L1); IR 42 Volt average (Average voltage); IR 62 PF average (Average power factor); IR 70 System frequency (Frequency).
How do I enable Modbus control of the Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter?
Set the Modbus address (46047, default 1) and Comsetup code (46045, default 8 = 9600 8N1) from the front panel or over Modbus.
Where is the official Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter Modbus documentation?
The source is Operating Manual RISH Delta VAF NX (AMAN-00IM-0118 Rev. F), revision 2025-02, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/rish-delta-vaf-nx-77/O%20M%20RISH_Delta_VAF_NXl_REV_F.pdf.
More Rishabh Instruments Modbus register maps
- Energy meter (DC)
Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter
Rishabh RISH DC2111 MOD single-channel DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-1669 Rev. D (08/25).
Also known as: RISH DC2111 MOD, DC2111 - Energy meter
Rishabh Instruments RISH Delta Energy NX multifunction energy meter
Rishabh RISH Delta Energy NX panel energy meters with RS-485 Modbus RTU, per the operating manual on the product page (standard CT version).
Also known as: RISH Delta Energy NX, Delta Energy NX, RISH Delta Energy - Power meter
Rishabh Instruments RISH Delta Power NX multifunction power meter
Rishabh RISH Delta Power NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0117 Rev. E.
Also known as: RISH Delta Power NX, Delta Power NX, RISH Delta Power - Power meter (demand controller)
Rishabh Instruments RISH DMCi touch-screen demand controller with TOD
Rishabh RISH DMCi 96 x 96 mm touch-screen demand controllers with the optional RS-485 Modbus output, per interface definition DMAN-00IM-0578 Rev. A (09/16).
Also known as: RISH DMCi, DMCi, Rish DMCi demand controller - Energy meter
Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters
Rishabh RISH EC43xx and ER43xx DIN-rail digital energy meters with RS-485 Modbus, per interface definition DMAN-00IM-09xx Rev. F (11/25).
Also known as: EC4311, EC4321, ER4311, ER4321, RISH EC43X1, EC43XX, ER43XX - Energy meter
Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters
Rishabh RISH ED11XX (direct), EC11XX (CT) and ER11XX (RJ12 CT) single-phase DIN-rail meters in their Modbus (x1) versions, per operating manual DMAN-00IM-1071 Rev. M.
Also known as: RISH ED11X1, RISH EC11X1, RISH ER11X1, ED1111, EC1111, ER1111, RISH ED11XX, RISH EC11XX, RISH ER11XX - Energy meter
Rishabh Instruments RISH ED21XX / EC21XX / ER21XX single-phase energy meters
Rishabh RISH ED21XX (direct), EC21XX (CT) and ER21XX (RJ12 CT) single-phase meters in their Modbus versions, per operating manual DMAN-00IM-1073 Rev. M.
Also known as: RISH ED21X1, RISH EC21X1, RISH ER21X1, RISH ED21XX, RISH EC21XX, RISH ER21XX - Energy meter
Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters
Rishabh RISH EM 1320/1330/1340 and EM 2320/2330/2340 panel energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0721 Rev. B (06/2020). Rows marked 'only 2340' apply to the dual-source EM 2340.
Also known as: RISH EM 1320, RISH EM 1330, RISH EM 1340, RISH EM 2320, RISH EM 2330, RISH EM 2340, EM2340DS - Energy meter
Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter
Rishabh RISH EM 3490 DS dual-source energy meters (separate utility and generator energy) with RS-485 Modbus, per manual Rev G.
Also known as: RISH EM 3490 DS, EM3490DS, EM 3490DS - Energy meter
Rishabh Instruments RISH EM 3490 SS single-phase energy meter
Rishabh RISH EM 3490 SS single-phase energy meters with the optional RS-485 Modbus output, per the 1-phase manual Rev D.
Also known as: RISH EM 3490 SS 1P, EM3490SS 1P, EM 3490 SS single-phase - Energy meter
Rishabh Instruments RISH EM 3490 SS three-phase single-source energy meter
Rishabh RISH EM 3490 SS three-phase energy meters with the optional RS-485 Modbus output, per the 3-phase manual Rev E.
Also known as: RISH EM 3490 SS 3P, EM3490SS 3P, EM 3490 SS three-phase - Energy meter (DC)
Rishabh Instruments RISH EM DC 6000 programmable DC energy meter
Rishabh RISH EM DC 6000 single-channel programmable DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0862 Rev. 0 (12/2020).
Also known as: RISH EM DC 6000, EMDC 6000, EM DC6000 - Energy meter (DC)
Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter
Rishabh RISH EM DC 6001 / 6002 multi-channel DC energy meters with RS-485 Modbus, per interface definition 2-60-006-00-00627 Rev. 0 (10/2015).
Also known as: RISH EM DC 6001, RISH EM DC 6002, EM DC 6001, EM DC 6002 - Power meter
Rishabh Instruments RISH LM 1340 multifunction meter
Rishabh RISH LM 1340 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. D (03/2026).
Also known as: RISH LM 1340, LM1340 - Power meter
Rishabh Instruments RISH LM 1360 load manager (LM 13xx)
Rishabh RISH LM 1360 panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0662 Rev. D (01/2024).
Also known as: RISH LM 1360, LM1360, LM 13xx, LM1360 RJ12 - Power meter
Rishabh Instruments RISH LM 1380 multifunction meter
Rishabh RISH LM 1380 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0925 Rev. A (04/2022).
Also known as: RISH LM 1380, LM1380 - Power meter
Rishabh Instruments RISH LM1360+ RJ12 smart energy meter
Rishabh RISH LM1360 PLUS RJ12 smart energy meters (RJ12 CT inputs) with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. A (01/2026).
Also known as: RISH LM 1360+, LM1360 PLUS RJ12, LM1360+ - Power meter
Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter
Rishabh RISH Master 3440 class 0.2S panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0711 Rev. C (05/2019).
Also known as: RISH Master 3440, RM3440, Master 3440 0.2S - Power meter
Rishabh Instruments RISH Master 3440i / 3440iDL (class 0.2S) touch-screen meter
Rishabh RISH Master 3440i and 3440iDL touch-screen class 0.2S meters with RS-485 Modbus, per interface definition DMAN-00IM-0712 Rev. F (10/2026).
Also known as: RISH Master 3440i, RISH Master 3440iDL, RM3440i, RM3440iDL - Power meter (multi-circuit energy meter)
Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)
RISH Multiload Monitor (12 current channels, 4 voltage channels) per interface definition DMAN-00IM-0795 Rev A (08/2020).
Also known as: RISH ML 1400, RISH ML 1410, RISH MLM, Multiload Monitor - Power meter (power factor controller)
Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller
Rishabh RISH PFC 96 and PFC 144 automatic power factor (APFC) controllers with RS-485 Modbus RTU, per interface definition version D (12/18).
Also known as: RISH PFC 96, RISH PFC 144, PFC96, PFC144, RISH PFC-12, APFC
Other power & energy meters register maps
- Power meter (multi-circuit branch feeder monitor)
SATEC BFM136/036 branch feeder monitor
SATEC BFM136 and BFM036 multi-circuit meters per Modbus reference guide BG0395 Rev. A8 (July 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM136, BFM036, BFM 136, SATEC BFM136 - Power meter (circuit breaker trip unit)
Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)
Standard dataset registers 32000-32341 served by the IFM (Modbus RTU) or IFE (Modbus TCP) interface for ComPact NSX; the same table lists availability for ComPact NS / MasterPact NT/NW and MasterPact MTZ. Per DOCA0091EN-09 (07/2022).
Also known as: ComPact NSX, Compact NSX, MicroLogic 5.2 E, MicroLogic 6.2 E, MicroLogic 7.2 E, MicroLogic 5.3 A, MicroLogic 6.3 E, IFM LV434000, IFE LV434001, IFE LV434002, ComPact NS, MasterPact NT, MasterPact NW, MasterPact MTZ - Power meter
Siemens SENTRON PAC3200
SENTRON PAC3200 (7KM2111/7KM2112), Ethernet port and optional PAC RS485 expansion module, per manual edition 02/2008.
Also known as: 7KM2112-0BA00-2AA0, 7KM2112-0BA00-3AA0, 7KM2111-1BA00-3AA0, 7KM PAC3200 - Energy meter (S0 pulse counter / digital input module)
Teracom TDI340 4-channel S0 pulse counter with Modbus RTU
TDI340 per the Teracom TDI340 user manual Revision R1.11, firmware V1.06 or later.
Also known as: TDI340 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter
Accuenergy Acuvim-L Series
Accuenergy Acuvim-L series multifunction power and energy meters, user manual V4 (V 4.1.12, revised March 2026).
Also known as: Acuvim-CL, Acuvim-EL
All power & energy meters Modbus register maps →
Source: Operating Manual RISH Delta VAF NX · AMAN-00IM-0118 Rev. F · rev. 2025-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.