Power meter (demand controller) · Modbus register map

Rishabh Instruments RISH DMCi touch-screen demand controller with TOD Modbus register map

Updated 19 November 2026

Short answer

The RISH DMCi is a panel demand controller that measures voltage, current, power, PF, energy and six kinds of demand and sheds non-priority loads through relays before a contracted demand is exceeded; it also keeps time-of-day (TOD) tariff data. Its optional RS-485 port speaks Modbus RTU and every value is an IEEE 754 float in two registers. This map covers the main measured values, demand, energy, RTC and current-zone TOD registers (30001-30199) and the main setup registers.

This page lists 114 Modbus registers for the Rishabh Instruments RISH DMCi touch-screen demand controller with TOD — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.

Manufacturer
Rishabh Instruments
Model
RISH DMCi touch-screen demand controller with TOD
Equipment type
Power meter (demand controller)
Registers
114 (14 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RISH DMCi, DMCi, Rish DMCi demand controller
Source document
Interface Definition RISH DMCi Touch Screen Demand Controller with TOD · DMAN-00IM-0578 Rev. A · rev. 2016-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Rishabh Instruments RISH DMCi touch-screen demand controller with TOD

Integration in brief

Read 30001-30072 for instantaneous values and 30073-30128 for energy and demand with FC04, decoding each pair as a big-endian float. Settings are floats in the 4X area written with FC16.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Volts 1FLOAT32 ABCDVoltage L1Read
IR 6Current 1FLOAT32 ABCDCurrent L1Read
IR 52Watt sumFLOAT32 ABCDTotal active powerRead
IR 70FrequencyFLOAT32 ABCDFrequencyRead
IR 84kW Demand ( Import )FLOAT32 ABCDkW import demandRead
IR 110Wh ImportFLOAT32 ABCDWh importRead

Enable Modbus control & writes

Modbus is an optional output. Set node address and baud/parity in the communication menu, or over Modbus at 40021 and 40019.

Byte order & addressing

Network setup

Watch out for

Rishabh Instruments RISH DMCi touch-screen demand controller with TOD Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

114 of 114 shown
Rishabh Instruments RISH DMCi touch-screen demand controller with TOD Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Volts 1FLOAT32ABCDRead
IR2doc 30003Volts 2FLOAT32ABCDRead
IR4doc 30005Volts 3FLOAT32ABCDRead
IR6doc 30007Current 1FLOAT32ABCDRead
IR8doc 30009Current 2FLOAT32ABCDRead
IR10doc 30011Current 3FLOAT32ABCDRead
IR12doc 30013W1FLOAT32ABCDRead
IR14doc 30015W2FLOAT32ABCDRead
IR16doc 30017W3FLOAT32ABCDRead
IR18doc 30019VA 1FLOAT32ABCDRead
IR20doc 30021VA 2FLOAT32ABCDRead
IR22doc 30023VA 3FLOAT32ABCDRead
IR24doc 30025VAR 1FLOAT32ABCDRead
IR26doc 30027VAR 2FLOAT32ABCDRead
IR28doc 30029VAR 3FLOAT32ABCDRead
IR30doc 30031PF 1FLOAT32ABCDRead
IR32doc 30033PF 2FLOAT32ABCDRead
IR34doc 30035PF 3FLOAT32ABCDRead
IR36doc 30037Phase Angle 1FLOAT32ABCDRead
IR38doc 30039Phase Angle 2FLOAT32ABCDRead
IR40doc 30041Phase Angle 3FLOAT32ABCDRead
IR42doc 30043Volts AvgFLOAT32ABCDRead
IR44doc 30045Volts SumFLOAT32ABCDRead
IR46doc 30047Current AvgFLOAT32ABCDRead
IR48doc 30049Current SumFLOAT32ABCDRead
IR50doc 30051Watt avgFLOAT32ABCDRead
IR52doc 30053Watt sumFLOAT32ABCDRead
IR54doc 30055VA avgFLOAT32ABCDRead
IR56doc 30057VA sumFLOAT32ABCDRead
IR58doc 30059VAr avgFLOAT32ABCDRead
IR60doc 30061VAr sumFLOAT32ABCDRead
IR62doc 30063PF avgFLOAT32ABCDRead
IR64doc 30065PF sumFLOAT32ABCDRead
IR66doc 30067Phase angle avgFLOAT32ABCDRead
IR68doc 30069Phase angle sumFLOAT32ABCDRead
IR70doc 30071FrequencyFLOAT32ABCDRead
IR72doc 30073Wh (Import)FLOAT32ABCDRead
IR74doc 30075Wh (Export)FLOAT32ABCDRead
IR76doc 30077VARh(Import)FLOAT32ABCDRead
IR78doc 30079VARh(Export)FLOAT32ABCDRead
IR80doc 30081VAhFLOAT32ABCDRead
IR82doc 30083AhFLOAT32ABCDRead
IR84doc 30085kW Demand ( Import )FLOAT32ABCDRead
IR86doc 30087kW Max Demand (Import)FLOAT32ABCDRead
IR88doc 30089W Demand (Export)FLOAT32ABCDRead
IR90doc 30091W Max Demand (Export)FLOAT32ABCDRead
IR92doc 30093kVAr Demand(Import)FLOAT32ABCDRead
IR94doc 30095kVAr Max Demand(Import)FLOAT32ABCDRead
IR96doc 30097kVAr Demand(Export)FLOAT32ABCDRead
IR98doc 30099kVAr Max Demand (Export)FLOAT32ABCDRead
IR100doc 30101VA DemandFLOAT32ABCDRead
IR102doc 30103VA Max DemandFLOAT32ABCDRead
IR104doc 30105A DemandFLOAT32ABCDRead
IR106doc 30107A Max DemandFLOAT32ABCDRead
IR108doc 30109Wh Import Overflow countRoll-overs of the matching energy register.FLOAT32ABCDRead
IR110doc 30111Wh ImportFLOAT32ABCDRead
IR112doc 30113Wh Export Overflow countRoll-overs of the matching energy register.FLOAT32ABCDRead
IR114doc 30115Wh ExportFLOAT32ABCDRead
IR116doc 30117VARh Import Overflow countRoll-overs of the matching energy register.FLOAT32ABCDRead
IR118doc 30119VARh ImportFLOAT32ABCDRead
IR120doc 30121VARh Export Overflow countRoll-overs of the matching energy register.FLOAT32ABCDRead
IR122doc 30123VARh ExportFLOAT32ABCDRead
IR124doc 30125VAh Overflow countRoll-overs of the matching energy register.FLOAT32ABCDRead
IR126doc 30127VAhFLOAT32ABCDRead
IR128doc 30129Predictive DemandFLOAT32ABCDRead
IR130doc 30131Time remainingFLOAT32ABCDRead
IR132doc 30133Max system VoltageFLOAT32ABCDRead
IR134doc 30135Min system VoltageFLOAT32ABCDRead
IR140doc 30141Max System CurrentFLOAT32ABCDRead
IR142doc 30143Min System CurrentFLOAT32ABCDRead
IR144doc 30145Wh Import (update-rate copy)Refreshed at the energy update rate (40081).FLOAT32ABCDRead
IR146doc 30147Wh Export (update-rate copy)Refreshed at the energy update rate (40081).FLOAT32ABCDRead
IR148doc 30149VArh Import (update-rate copy)Refreshed at the energy update rate (40081).FLOAT32ABCDRead
IR150doc 30151VArh Export (update-rate copy)Refreshed at the energy update rate (40081).FLOAT32ABCDRead
IR152doc 30153VAh (update-rate copy)Refreshed at the energy update rate (40081).FLOAT32ABCDRead
IR158doc 30159Relay Trip IndicationFLOAT32ABCDRead
IR160doc 30161Demand Prole numberFLOAT32ABCDRead
IR162doc 30163season numberFLOAT32ABCDRead
IR164doc 30165Day typeFLOAT32ABCDRead
IR166doc 30167zone numberFLOAT32ABCDRead
IR168doc 30169Prole rateFLOAT32ABCDRead
IR170doc 30171RTC minuteFLOAT32ABCDRead
IR172doc 30173RTC HourFLOAT32ABCDRead
IR174doc 30175RTC dateFLOAT32ABCDRead
IR176doc 30177RTC monthFLOAT32ABCDRead
IR178doc 30179RTC YearFLOAT32ABCDRead
IR180doc 30181current zone active Import energyTime-of-day data for the active tariff zone.FLOAT32ABCDRead
IR182doc 30183current zone active Import costTime-of-day data for the active tariff zone.FLOAT32ABCDRead
IR184doc 30185current zone active Export energyTime-of-day data for the active tariff zone.FLOAT32ABCDRead
IR186doc 30187current zone active Export costTime-of-day data for the active tariff zone.FLOAT32ABCDRead
IR188doc 30189current zone reactive Import energyTime-of-day data for the active tariff zone.FLOAT32ABCDRead
IR190doc 30191current zone reactive import costTime-of-day data for the active tariff zone.FLOAT32ABCDRead
IR192doc 30193current zone reactive Export energyTime-of-day data for the active tariff zone.FLOAT32ABCDRead
IR194doc 30195current zone reactive Export costTime-of-day data for the active tariff zone.FLOAT32ABCDRead
IR196doc 30197current zone apparent energyTime-of-day data for the active tariff zone.FLOAT32ABCDRead
IR198doc 30199current zone apparent costTime-of-day data for the active tariff zone.FLOAT32ABCDRead
HR4doc 40005Energy resolutionDefault 1.FLOAT32ABCDRead/write1 = Wh; 2 = kWh; 3 = MWh
HR6doc 40007System voltageNominal system voltage.FLOAT32ABCDRead
HR8doc 40009System currentNominal system current.FLOAT32ABCDRead
HR10doc 40011System typeDefault 3. Read-only and reads 1 on 1-phase 2-wire units.FLOAT32ABCDRead/write2 = 3-phase 3-wire; 3 = 3-phase 4-wire
HR14doc 40015Reset parametersFLOAT32ABCDWrite0 = Energy; 1 = Demand; 2 = System max values; 3 = System min values; 4 = Run hour and on hour; 5 = No. of interruptions; 7 = Time-of-day data; 8 = All data; 9 = Factory reset
HR18doc 40019RS 485 set-up codeBaud, parity and stop bits in one code; default 5.FLOAT32ABCDRead/write0 = 4800 bps, no parity, 1 stop; 1 = 4800 bps, no parity, 2 stop; 2 = 4800 bps, even, 1 stop; 3 = 4800 bps, odd, 1 stop; 4 = 9600 bps, no parity, 1 stop; 5 = 9600 bps, no parity, 2 stop; 6 = 9600 bps, even, 1 stop; 7 = 9600 bps, odd, 1 stop; 8 = 19200 bps, no parity, 1 stop; 9 = 19200 bps, no parity, 2 stop; 10 = 19200 bps, even, 1 stop; 11 = 19200 bps, odd, 1 stop; 12 = 38400 bps, no parity, 1 stop; 13 = 38400 bps, no parity, 2 stop; 14 = 38400 bps, even, 1 stop; 15 = 38400 bps, odd, 1 stop
HR20doc 40021Node addressModbus slave address; default 1.FLOAT32ABCDRead/write
HR32doc 40033PT primaryDefault 500.FLOAT32ABCDRead/write
HR34doc 40035CT primaryDefault 5.FLOAT32ABCDRead/write
HR36doc 40037System powerNominal system power.FLOAT32ABCDRead
HR38doc 40039Energy digit reset countEnergy roll-over digits, 7, 8 or 9; default 7.FLOAT32ABCDRead/write
HR40doc 40041Register order / word orderWrite 2141.0 in the wanted order to switch normal/reversed float word order.FLOAT32ABCDRead/write
HR42doc 40043CT secondaryDefault 5.FLOAT32ABCDRead/write1 = 1 A; 5 = 5 A
HR44doc 40045PT secondaryDefault 500.FLOAT32ABCDRead/write
HR70doc 40071PasswordFLOAT32ABCDRead/write
HR78doc 40079Low current noise cut-offDefault 0.FLOAT32ABCDRead/write0 = Off; 30 = 30 mA cut-off on
HR80doc 40081Energy update rateDefault 1.FLOAT32ABCDRead/write
HR98doc 40099Model numberModel identifier; the manual prints both 3482 and 3490.FLOAT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Rishabh Instruments RISH DMCi touch-screen demand controller with TOD

What Modbus registers does the Rishabh Instruments RISH DMCi touch-screen demand controller with TOD have?

This map lists 114 registers: 96 input registers, 18 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Rishabh Instruments RISH DMCi touch-screen demand controller with TOD Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The interface definition prints 3X/4X numbers next to the hex start address (30001 = 00 00, 40019 = 00 12). Wire address = number - 30001 (FC04) or - 40001 (FC03/FC16); every row here was checked against its printed hex and parameter number.

What byte order does the Rishabh Instruments RISH DMCi touch-screen demand controller with TOD use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Rishabh Instruments RISH DMCi touch-screen demand controller with TOD?

Start with IR 0 Volts 1 (Voltage L1); IR 6 Current 1 (Current L1); IR 52 Watt sum (Total active power); IR 70 Frequency (Frequency); IR 84 kW Demand ( Import ) (kW import demand); IR 110 Wh Import (Wh import).

How do I enable Modbus control of the Rishabh Instruments RISH DMCi touch-screen demand controller with TOD?

Modbus is an optional output. Set node address and baud/parity in the communication menu, or over Modbus at 40021 and 40019.

Where is the official Rishabh Instruments RISH DMCi touch-screen demand controller with TOD Modbus documentation?

The source is Interface Definition RISH DMCi Touch Screen Demand Controller with TOD (DMAN-00IM-0578 Rev. A), revision 2016-09, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/touch-screen-rish-dmci-144/Rish_DMCi_Interface_definition.pdf.

More Rishabh Instruments Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Interface Definition RISH DMCi Touch Screen Demand Controller with TOD · DMAN-00IM-0578 Rev. A · rev. 2016-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.