Energy meter · Modbus register map

Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters Modbus register map

Updated 17 November 2026

Short answer

The RISH EM13xx / EM23xx is a 96 x 96 mm panel multifunction energy meter that measures voltage, current, power, energy, demand and THD on 3-phase 4-wire, 3-phase 3-wire or single-phase networks. Its RS-485 port speaks Modbus RTU and every reading is a 32-bit IEEE float in two registers. This map covers per-phase and system values, utility/generator energies and demands (EM 2340 dual source), overflow counters, THD, hour counters and relay status, plus the main setup registers (system type, CT/PT ratios, demand period, communication and word-order settings).

This page lists 137 Modbus registers for the Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.

Manufacturer
Rishabh Instruments
Model
RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters
Equipment type
Energy meter
Registers
137 (12 writable)
Transport
Modbus RTU
Default unit ID
1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RISH EM 1320, RISH EM 1330, RISH EM 1340, RISH EM 2320, RISH EM 2330, RISH EM 2340, EM2340DS
Source document
RISH EM 2340/1320/30/40 Interface Definition · DMAN-00IM-0721 Rev. B · rev. 2020-06
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters

Integration in brief

Read measured values with FC04 (or FC03 at the 4X copies) in pairs of registers and decode them as ABCD floats. Settings are floats too and are written with FC16.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Volts 1FLOAT32 ABCDVoltage L1Read
IR 6Current 1FLOAT32 ABCDCurrent L1Read
IR 52Watt SumFLOAT32 ABCDTotal active power (Watt Sum)Read
IR 70FreqFLOAT32 ABCDFrequencyRead
IR 72Wh Import / UtilityFLOAT32 ABCDActive energy importRead
IR 62PF AvgFLOAT32 ABCDAverage power factorRead

Enable Modbus control & writes

Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.

Byte order & addressing

Network setup

Watch out for

Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

137 of 137 shown
Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Volts 1FLOAT32ABCDRead
IR2doc 30003Volts 2FLOAT32ABCDRead
IR4doc 30005Volts 3FLOAT32ABCDRead
IR6doc 30007Current 1FLOAT32ABCDRead
IR8doc 30009Current 2FLOAT32ABCDRead
IR10doc 30011Current 3FLOAT32ABCDRead
IR12doc 30013W1FLOAT32ABCDRead
IR14doc 30015W2FLOAT32ABCDRead
IR16doc 30017W3FLOAT32ABCDRead
IR18doc 30019VA 1FLOAT32ABCDRead
IR20doc 30021VA 2FLOAT32ABCDRead
IR22doc 30023VA 3FLOAT32ABCDRead
IR24doc 30025VAR 1FLOAT32ABCDRead
IR26doc 30027VAR 2FLOAT32ABCDRead
IR28doc 30029VAR 3FLOAT32ABCDRead
IR30doc 30031PF 1FLOAT32ABCDRead
IR32doc 30033PF 2FLOAT32ABCDRead
IR34doc 30035PF 3FLOAT32ABCDRead
IR36doc 30037Phase Angle 1FLOAT32ABCDRead
IR38doc 30039Phase Angle 2FLOAT32ABCDRead
IR40doc 30041Phase Angle 3FLOAT32ABCDRead
IR42doc 30043Volts AvgFLOAT32ABCDRead
IR44doc 30045Volts SumFLOAT32ABCDRead
IR46doc 30047Current AvgFLOAT32ABCDRead
IR48doc 30049Current SumFLOAT32ABCDRead
IR50doc 30051Watt AvgFLOAT32ABCDRead
IR52doc 30053Watt SumFLOAT32ABCDRead
IR54doc 30055VA AvgFLOAT32ABCDRead
IR56doc 30057VA SumFLOAT32ABCDRead
IR58doc 30059VAR AvgFLOAT32ABCDRead
IR60doc 30061VAR SumFLOAT32ABCDRead
IR62doc 30063PF AvgFLOAT32ABCDRead
IR64doc 30065PF SumFLOAT32ABCDRead
IR66doc 30067Phase Angle AvgFLOAT32ABCDRead
IR68doc 30069Phase Angle SumFLOAT32ABCDRead
IR70doc 30071FreqFLOAT32ABCDRead
IR72doc 30073Wh Import / UtilityFLOAT32ABCDRead
IR74doc 30075Wh Export / GenFLOAT32ABCDRead
IR76doc 30077Capacitive / Utility VARhFLOAT32ABCDRead
IR78doc 30079Inductive / Gen VARhFLOAT32ABCDRead
IR80doc 30081VAh / Vah UtilityFLOAT32ABCDRead
IR82doc 30083VAh Gen (Only 2340)FLOAT32ABCDRead
IR84doc 30085W Demand (Import / Utility / Gen)FLOAT32ABCDRead
IR86doc 30087W Max Demand (Import / Utility)FLOAT32ABCDRead
IR88doc 30089W Demand (Export)FLOAT32ABCDRead
IR90doc 30091W Max Demand (Export / Gen)FLOAT32ABCDRead
IR92doc 30093Old W Max Demand (Import / Utility)FLOAT32ABCDRead
IR94doc 30095Old W Max Demand (Export / Gen)FLOAT32ABCDRead
IR96doc 30097Old VA Utility Max DemandFLOAT32ABCDRead
IR98doc 30099Old A Utility Max DemandFLOAT32ABCDRead
IR100doc 30101VA Demand (Utility / Gen)FLOAT32ABCDRead
IR102doc 30103VA Max Demand (Utility)FLOAT32ABCDRead
IR104doc 30105A Demand (Utility / Gen)FLOAT32ABCDRead
IR106doc 30107A Max Demand (Utility)FLOAT32ABCDRead
IR108doc 30109Wh Import / Utility Overflow countFLOAT32ABCDRead
IR112doc 30113Wh Export / Gen Overflow countFLOAT32ABCDRead
IR116doc 30117Capacitive / Utility VARh Overflow countFLOAT32ABCDRead
IR120doc 30121Inductive / Gen VARh Overflow countFLOAT32ABCDRead
IR124doc 30125Vah / VAh Utility Overflow countFLOAT32ABCDRead
IR128doc 30129VAh Gen Overflow count (only 2340)FLOAT32ABCDRead
IR132doc 30133System Max VoltageFLOAT32ABCDRead
IR134doc 30135System Min VoltageFLOAT32ABCDRead
IR136doc 30137RPMFLOAT32ABCDRead
IR140doc 30141System Max CurrentFLOAT32ABCDRead
IR142doc 30143System Min CurrentFLOAT32ABCDRead
IR144doc 30145Wh Import / Utility depending on update rateFLOAT32ABCDRead
IR146doc 30147Wh Export / Gen depending on update rateFLOAT32ABCDRead
IR148doc 30149Capacitive / Utility VArh depending on update rateFLOAT32ABCDRead
IR150doc 30151Inductive / Gen VArh depending on update rateFLOAT32ABCDRead
IR154doc 30155VAh Gen depending on update rate (only 2340)FLOAT32ABCDRead
IR156doc 30157Wh Import / Utility Overflow count depending on update rateFLOAT32ABCDRead
IR158doc 30159Wh Export / Gen Overflow count depending on update rateFLOAT32ABCDRead
IR160doc 30161Capacitive / Utility VArh Overflow count depending on update rateFLOAT32ABCDRead
IR162doc 30163Inductive / Gen VArh Overflow count depending on update rateFLOAT32ABCDRead
IR164doc 30165VAh Utility Overflow count depending on update rateFLOAT32ABCDRead
IR166doc 30167VAh Gen Overflow count depending on update rate (only 2340)FLOAT32ABCDRead
IR168doc 30169Old Wh Import / Utility Overflow countFLOAT32ABCDRead
IR172doc 30173Old Wh Export / Gen Overflow countFLOAT32ABCDRead
IR176doc 30177Old Capacitive / Utility VArh Overflow countFLOAT32ABCDRead
IR178doc 30179Old Capacitive / Utility VArhFLOAT32ABCDRead
IR180doc 30181Old Inductive / Gen VArh Overflow countFLOAT32ABCDRead
IR182doc 30183Old Inductive / Gen VArhFLOAT32ABCDRead
IR184doc 30185Old VAh / VAh Utility Overflow countFLOAT32ABCDRead
IR186doc 30187Old VAh / VAh UtilityFLOAT32ABCDRead
IR188doc 30189Old VAh Gen Overflow count (only 2340)FLOAT32ABCDRead
IR190doc 30191Old VAh Gen (only 2340)FLOAT32ABCDRead
IR192doc 30193VA Max Demand (Gen)FLOAT32ABCDRead
IR194doc 30195A Max Demand (Gen)FLOAT32ABCDRead
IR196doc 30197Old VA Max Demand (Gen)FLOAT32ABCDRead
IR198doc 30199Old A Max Demand (Gen)FLOAT32ABCDRead
IR200doc 30201VL 1 - 2 (Calculated)FLOAT32ABCDRead
IR202doc 30203VL 2 - 3 (Calculated)FLOAT32ABCDRead
IR204doc 30205VL 3- 1 (Calculated)FLOAT32ABCDRead
IR206doc 30207V1 THD (%)FLOAT32ABCDRead
IR208doc 30209V2 THD (%)FLOAT32ABCDRead
IR210doc 30211V3 THD (%)FLOAT32ABCDRead
IR212doc 30213I1 THD (%)FLOAT32ABCDRead
IR214doc 30215I2 THD (%)FLOAT32ABCDRead
IR216doc 30217I3 THD (%)FLOAT32ABCDRead
IR218doc 30219System Voltage THD (%)FLOAT32ABCDRead
IR220doc 30221System Current THD (%)FLOAT32ABCDRead
IR224doc 30225I NeutralFLOAT32ABCDRead
IR226doc 30227Run Hour UtilityFLOAT32ABCDRead
IR228doc 30229On Hour UtilityFLOAT32ABCDRead
IR230doc 30231No. of Interruptions UtilityFLOAT32ABCDRead
IR236doc 30237Run Hour Gen (only 2340)FLOAT32ABCDRead
IR238doc 30239On Hour Gen (only 2340)FLOAT32ABCDRead
IR240doc 30241No. of Interruptions Gen (only 2340)FLOAT32ABCDRead
IR242doc 30243Total Run Hour (only 2340)FLOAT32ABCDRead
IR244doc 30245Total On Hour (only 2340)FLOAT32ABCDRead
IR246doc 30247Old Wh Import / UtilityFLOAT32ABCDRead
IR248doc 30249Old Wh Export / GenFLOAT32ABCDRead
IR250doc 30251Old Run Hour UtilityFLOAT32ABCDRead
IR252doc 30253Old Run Hour Gen (only 2340)FLOAT32ABCDRead
IR254doc 30255Old On Hour UtilityFLOAT32ABCDRead
IR256doc 30257Old On Hour Gen (only 2340)FLOAT32ABCDRead
IR258doc 30259Old Total Run Hour (only 2340)FLOAT32ABCDRead
IR260doc 30261Old Total On Hour (only 2340)FLOAT32ABCDRead
IR262doc 30263Old No. of Interruptions UtilityFLOAT32ABCDRead
IR264doc 30265Old No. of Interruptions Gen (only 2340)FLOAT32ABCDRead
IR266doc 30267Relay Output 1 StatusFLOAT32ABCDRead
IR268doc 30269Relay Output 2 StatusFLOAT32ABCDRead
HR2doc 40003Demand Integration TimeSetup parameter (float).FLOAT32ABCDRead/write
HR4doc 40005Energy OutputSetup parameter (float).FLOAT32ABCDRead/write
HR10doc 40011System Type*Setup parameter (float).FLOAT32ABCDRead/write
HR14doc 40015Reset ParametersSetup parameter (float).FLOAT32ABCDRead/write
HR18doc 40019RS 485 Set-up CodeSetup parameter (float).FLOAT32ABCDRead/write
HR32doc 40033PT PrimarySetup parameter (float).FLOAT32ABCDRead/write
HR34doc 40035CT PrimarySetup parameter (float).FLOAT32ABCDRead/write
HR40doc 40041Register Order/Word OrderSetup parameter (float).FLOAT32ABCDRead/write
HR42doc 40043CT SecondarySetup parameter (float).FLOAT32ABCDRead/write
HR44doc 40045PT SecondarySetup parameter (float).FLOAT32ABCDRead/write
HR70doc 40071PasswordSetup parameter (float).FLOAT32ABCDRead/write
HR76doc 40077Auto ScrollSetup parameter (float).FLOAT32ABCDRead/write
HR96doc 40097Serial NumberRead-only identification value (float).FLOAT32ABCDRead
HR98doc 40099Model NumberRead-only identification value (float).FLOAT32ABCDRead
HR100doc 40101Version NumberRead-only identification value (float).FLOAT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters

What Modbus registers does the Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters have?

This map lists 137 registers: 122 input registers, 15 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 30001/40001-style addresses next to the hex start address actually sent (30001 = 0x0000). Wire address = printed number - 30001 (input registers) or - 40001 (holding registers); every value here was cross-checked against the printed hex address.

What byte order does the Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters?

Start with IR 0 Volts 1 (Voltage L1); IR 6 Current 1 (Current L1); IR 52 Watt Sum (Total active power (Watt Sum)); IR 70 Freq (Frequency); IR 72 Wh Import / Utility (Active energy import); IR 62 PF Avg (Average power factor).

How do I enable Modbus control of the Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters?

Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.

Where is the official Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters Modbus documentation?

The source is RISH EM 2340/1320/30/40 Interface Definition (DMAN-00IM-0721 Rev. B), revision 2020-06, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/rish-em-13203040-158/EM13XX__EM23XX__Interface_Definition_Rev_B.pdf.

More Rishabh Instruments Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: RISH EM 2340/1320/30/40 Interface Definition · DMAN-00IM-0721 Rev. B · rev. 2020-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.