Power meter (multi-circuit) · Modbus register map

Setra Systems Setra Power Meter (SPM) multi-circuit power meter Modbus register map

Updated 17 November 2026

Short answer

The Setra Power Meter is a multi-circuit meter with two voltage inputs and up to 48 configurable loads, each with three phases of CT inputs, reachable over Modbus RTU or Modbus TCP. Values are 32-bit floats and unsigned integers, most significant byte first. This map covers device identity and settings, both voltage inputs (voltages, angles, THD, frequency, service type) and the full Load 1 block with its three phases; Loads 2-48 repeat the same layout at higher addresses.

This page lists 132 Modbus registers for the Setra Systems Setra Power Meter (SPM) multi-circuit power meter — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Setra Systems’s own free documentation (linked below) and checked against it.

Manufacturer
Setra Systems
Model
Setra Power Meter (SPM) multi-circuit power meter
Equipment type
Power meter (multi-circuit)
Registers
132 (0 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
SPM, Setra Power Meter, SS-SPM-MODBUS_G
Source document
Setra Power Meter Modbus Register Master List · SS-SPM-MODBUS_G
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Setra Systems Setra Power Meter (SPM) multi-circuit power meter

Integration in brief

Read input registers with function 04: voltages from absolute 104, Load 1 totals from 324-369 and phases from 404, decoding floats high word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 104Vin1_L1-NFLOAT32 ABCDVin1 L1-N voltageRead
IR 128Vin1_FreqFLOAT32 ABCDFrequencyRead
IR 324Load 1 total_kWhFLOAT32 ABCDLoad 1 net kWhRead
IR 352Load 1 total_amperageFLOAT32 ABCDLoad 1 total currentRead
IR 354Load 1 total_kWFLOAT32 ABCDLoad 1 total kWRead
IR 360Load 1 total_aPFFLOAT32 ABCDLoad 1 power factorRead

Enable Modbus control & writes

The list does not describe setup. It shows the meter can run Modbus TCP (the slave address row reads 0 in that mode) as well as a serial slave address.

Byte order & addressing

Network setup

Watch out for

Setra Systems Setra Power Meter (SPM) multi-circuit power meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

132 of 132 shown
Setra Systems Setra Power Meter (SPM) multi-circuit power meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 0 / 30000Device_NameMeter name, 80 characters.STRING[80]Read
IR42doc 42 / 30042Model_NumberSTRING[16]Read
IR50doc 50 / 30050Serial_NumberSTRING[16]Read
IR58doc 58 / 30058Firmware_RevisionSTRING[16]Read
IR78doc 78 / 30078Power_Factor_Sign_ConventionUINT32ABCDRead1 = IEC; 2 = IEEE
IR80doc 80 / 30080Demand_WindowUINT32ABCDminRead
IR82doc 82 / 30082Billing_Cycle_DayUINT32ABCDRead
IR84doc 84 / 30084Billing_Cycle_TimeUINT32ABCDsRead
IR102doc 102 / 30102Vin1_EnabledUINT32ABCDRead0 = Disabled; 1 = Enabled
IR104doc 104 / 30104Vin1_L1-NFLOAT32ABCDVRead
IR106doc 106 / 30106Vin1_L2-NFLOAT32ABCDVRead
IR108doc 108 / 30108Vin1_L3-NFLOAT32ABCDVRead
IR110doc 110 / 30110Vin1_L1-L2FLOAT32ABCDVRead
IR112doc 112 / 30112Vin1_L2-L3FLOAT32ABCDVRead
IR114doc 114 / 30114Vin1_L3-L1FLOAT32ABCDVRead
IR116doc 116 / 30116Vin1_L1_PAFLOAT32ABCD°Read
IR118doc 118 / 30118Vin1_L2_PAFLOAT32ABCD°Read
IR120doc 120 / 30120Vin1_L3_PAFLOAT32ABCD°Read
IR122doc 122 / 30122Vin1_L1_HDFLOAT32ABCD%Read
IR124doc 124 / 30124Vin1_L2_HDFLOAT32ABCD%Read
IR126doc 126 / 30126Vin1_L3_HDFLOAT32ABCD%Read
IR128doc 128 / 30128Vin1_FreqFLOAT32ABCDHzRead
IR130doc 130 / 30130Vin1_Expected_Line_VoltageUINT32ABCDVRead
IR132doc 132 / 30132Vin1_Service_TypeUINT32ABCDRead0 = None; 1 = 4-wire wye; 2 = 3-wire delta; 3 = Reserved; 4 = 3-wire single phase (split phase); 5 = 2-wire single phase
IR134doc 134 / 30134Vin1_ScalerUINT32ABCDVRead
IR150doc 150 / 30150Vin2_EnabledUINT32ABCDRead0 = Disabled; 1 = Enabled
IR152doc 152 / 30152Vin2_L1-NFLOAT32ABCDVRead
IR154doc 154 / 30154Vin2_L2-NFLOAT32ABCDVRead
IR156doc 156 / 30156Vin2_L3-NFLOAT32ABCDVRead
IR158doc 158 / 30158Vin2_L1-L2FLOAT32ABCDVRead
IR160doc 160 / 30160Vin2_L2-L3FLOAT32ABCDVRead
IR162doc 162 / 30162Vin2_L3-L1FLOAT32ABCDVRead
IR164doc 164 / 30164Vin2_L1_PAFLOAT32ABCD°Read
IR166doc 166 / 30166Vin2_L2_PAFLOAT32ABCD°Read
IR168doc 168 / 30168Vin2_L3_PAFLOAT32ABCD°Read
IR170doc 170 / 30170Vin2_L1_HDFLOAT32ABCD%Read
IR172doc 172 / 30172Vin2_L2_HDFLOAT32ABCD%Read
IR174doc 174 / 30174Vin2_L3_HDFLOAT32ABCD%Read
IR176doc 176 / 30176Vin_2_FreqFLOAT32ABCDHzRead
IR178doc 178 / 30178Vin2_Expected_Line_VoltageUINT32ABCDVRead
IR180doc 180 / 30180Vin2_Service_TypeUINT32ABCDRead0 = None; 1 = 4-wire wye; 2 = 3-wire delta; 3 = Reserved; 4 = 3-wire single phase (split phase); 5 = 2-wire single phase
IR182doc 182 / 30182Vin2_ScalerUINT32ABCDVRead
IR200doc 200 / 30200Pulse_in_1_EnabledUINT32ABCDRead
IR232doc 232 / 30232Pulse_in_2_EnabledUINT32ABCDRead
IR322doc 322 / 30322Load 1 enabledUINT32ABCDRead
IR324doc 324 / 30324Load 1 total_kWhFLOAT32ABCDkWhRead
IR326doc 326 / 30326Load 1 total_kWh+FLOAT32ABCDkWhRead
IR328doc 328 / 30328Load 1 total_kWh-FLOAT32ABCDkWhRead
IR330doc 330 / 30330Load 1 total_kvarhFLOAT32ABCDkvarhRead
IR332doc 332 / 30332Load 1 total_kvarh+FLOAT32ABCDkvarhRead
IR334doc 334 / 30334Load 1 total_kvarh-FLOAT32ABCDkvarhRead
IR336doc 336 / 30336Load 1 total_kvarh_Q1FLOAT32ABCDkvarhRead
IR338doc 338 / 30338Load 1 total_kvarh_Q2FLOAT32ABCDkvarhRead
IR340doc 340 / 30340Load 1 total_kvarh_Q3FLOAT32ABCDkvarhRead
IR342doc 342 / 30342Load 1 total_kvarh_Q4FLOAT32ABCDkvarhRead
IR344doc 344 / 30344Load 1 total_kVAhFLOAT32ABCDkVAhRead
IR350doc 350 / 30350Load 1 vrefUINT32ABCDRead
IR352doc 352 / 30352Load 1 total_amperageFLOAT32ABCDARead
IR354doc 354 / 30354Load 1 total_kWFLOAT32ABCDkWRead
IR356doc 356 / 30356Load 1 total_kvarFLOAT32ABCDkvarRead
IR358doc 358 / 30358Load 1 total_kVAFLOAT32ABCDkVARead
IR360doc 360 / 30360Load 1 total_aPFFLOAT32ABCDRead
IR362doc 362 / 30362Load 1 total_dPFFLOAT32ABCDRead
IR364doc 364 / 30364Load 1 total_THDFLOAT32ABCD%Read
IR366doc 366 / 30366Load 1 total_Demand_KWFLOAT32ABCDkWRead
IR368doc 368 / 30368Load 1 total_PD_KWFLOAT32ABCDkWRead
IR402doc 402 / 30402Phase L1 enabledUINT32ABCDRead
IR404doc 404 / 30404Phase_L1_kWhFLOAT32ABCDkWhRead
IR406doc 406 / 30406Phase_L1_kWh+FLOAT32ABCDkWhRead
IR408doc 408 / 30408Phase_L1_kWh-FLOAT32ABCDkWhRead
IR410doc 410 / 30410Phase_L1_kvarhFLOAT32ABCDkvarhRead
IR412doc 412 / 30412Phase_L1_kvarh+FLOAT32ABCDkvarhRead
IR414doc 414 / 30414Phase_L1_kvarh-FLOAT32ABCDkvarhRead
IR416doc 416 / 30416Phase_L1_kvarh_Q1FLOAT32ABCDkvarhRead
IR418doc 418 / 30418Phase_L1_kvarh_Q2FLOAT32ABCDkvarhRead
IR420doc 420 / 30420Phase_L1_kvarh_Q3FLOAT32ABCDkvarhRead
IR422doc 422 / 30422Phase_L1_kvarh_Q4FLOAT32ABCDkvarhRead
IR424doc 424 / 30424Phase_L1_kVAhFLOAT32ABCDkVAhRead
IR430doc 430 / 30430Phase_L1_AmpsFLOAT32ABCDARead
IR432doc 432 / 30432Phase_L1_kWFLOAT32ABCDkWRead
IR434doc 434 / 30434Phase_L1_kvarFLOAT32ABCDkvarRead
IR436doc 436 / 30436Phase_L1_kVAFLOAT32ABCDkVARead
IR438doc 438 / 30438Phase_L1_aPFFLOAT32ABCDRead
IR440doc 440 / 30440Phase_L1_dPFFLOAT32ABCDRead
IR442doc 442 / 30442Phase_L1_THDFLOAT32ABCD%Read
IR444doc 444 / 30444Phase_L1_Demand_KWFLOAT32ABCDkWRead
IR446doc 446 / 30446Phase_L1_PD_KWFLOAT32ABCDkWRead
IR448doc 448 / 30448Phase_L1_PCUINT32ABCDRead
IR462doc 462 / 30462Phase L2 enabledUINT32ABCDRead
IR464doc 464 / 30464Phase_L2_kWhFLOAT32ABCDkWhRead
IR466doc 466 / 30466Phase_L2_kWh+FLOAT32ABCDkWhRead
IR468doc 468 / 30468Phase_L2_kWh-FLOAT32ABCDkWhRead
IR470doc 470 / 30470Phase_L2_kvarhFLOAT32ABCDkvarhRead
IR472doc 472 / 30472Phase_L2_kvarh+FLOAT32ABCDkvarhRead
IR474doc 474 / 30474Phase_L2_kvarh-FLOAT32ABCDkvarhRead
IR476doc 476 / 30476Phase_L2_kvarh_Q1FLOAT32ABCDkvarhRead
IR478doc 478 / 30478Phase_L2_kvarh_Q2FLOAT32ABCDkvarhRead
IR480doc 480 / 30480Phase_L2_kvarh_Q3FLOAT32ABCDkvarhRead
IR482doc 482 / 30482Phase_L2_kvarh_Q4FLOAT32ABCDkvarhRead
IR484doc 484 / 30484Phase_L2_kVAhFLOAT32ABCDkVAhRead
IR490doc 490 / 30490Phase_L2_AmpsFLOAT32ABCDARead
IR492doc 492 / 30492Phase_L2_kWFLOAT32ABCDkWRead
IR494doc 494 / 30494Phase_L2_kvarFLOAT32ABCDkvarRead
IR496doc 496 / 30496Phase_L2_kVAFLOAT32ABCDkVARead
IR498doc 498 / 30498Phase_L2_aPFFLOAT32ABCDRead
IR500doc 500 / 30500Phase_L2_dPFFLOAT32ABCDRead
IR502doc 502 / 30502Phase_L2_THDFLOAT32ABCD%Read
IR504doc 504 / 30504Phase_L2_Demand_KWFLOAT32ABCDkWRead
IR506doc 506 / 30506Phase_L2_PD_KWFLOAT32ABCDkWRead
IR508doc 508 / 30508Phase_L2_PCUINT32ABCDRead
IR522doc 522 / 30522Phase L3 enabledUINT32ABCDRead
IR524doc 524 / 30524Phase_L3_kWhFLOAT32ABCDkWhRead
IR526doc 526 / 30526Phase_L3_kWh+FLOAT32ABCDkWhRead
IR528doc 528 / 30528Phase_L3_kWh-FLOAT32ABCDkWhRead
IR530doc 530 / 30530Phase_L3_kvarhFLOAT32ABCDkvarhRead
IR532doc 532 / 30532Phase_L3_kvarh+FLOAT32ABCDkvarhRead
IR534doc 534 / 30534Phase_L3_kvarh-FLOAT32ABCDkvarhRead
IR536doc 536 / 30536Phase_L3_kvarh_Q1FLOAT32ABCDkvarhRead
IR538doc 538 / 30538Phase_L3_kvarh_Q2FLOAT32ABCDkvarhRead
IR540doc 540 / 30540Phase_L3_kvarh_Q3FLOAT32ABCDkvarhRead
IR542doc 542 / 30542Phase_L3_kvarh_Q4FLOAT32ABCDkvarhRead
IR544doc 544 / 30544Phase_L3_kVAhFLOAT32ABCDkVAhRead
IR550doc 550 / 30550Phase_L3_AmpsFLOAT32ABCDARead
IR552doc 552 / 30552Phase_L3_kWFLOAT32ABCDkWRead
IR554doc 554 / 30554Phase_L3_kvarFLOAT32ABCDkvarRead
IR556doc 556 / 30556Phase_L3_kVAFLOAT32ABCDkVARead
IR558doc 558 / 30558Phase_L3_aPFFLOAT32ABCDRead
IR560doc 560 / 30560Phase_L3_dPFFLOAT32ABCDRead
IR562doc 562 / 30562Phase_L3_THDFLOAT32ABCD%Read
IR564doc 564 / 30564Phase_L3_Demand_KWFLOAT32ABCDkWRead
IR566doc 566 / 30566Phase_L3_PD_KWFLOAT32ABCDkWRead
IR568doc 568 / 30568Phase_L3_PCUINT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Setra Systems Setra Power Meter (SPM) multi-circuit power meter

What Modbus registers does the Setra Systems Setra Power Meter (SPM) multi-circuit power meter have?

This map lists 132 registers: 132 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Setra Systems Setra Power Meter (SPM) multi-circuit power meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row gives an 'Absolute Address' and a 'Modbus Register'. The list starts at absolute address 0 (Device_Name, register 30000), and every register number is 30000 + the absolute address, so the absolute address is the wire address for an input-register read: Vin1 L1-N is absolute 104 (register 30104).

What byte order does the Setra Systems Setra Power Meter (SPM) multi-circuit power meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Setra Systems Setra Power Meter (SPM) multi-circuit power meter?

Start with IR 104 Vin1_L1-N (Vin1 L1-N voltage); IR 128 Vin1_Freq (Frequency); IR 324 Load 1 total_kWh (Load 1 net kWh); IR 352 Load 1 total_amperage (Load 1 total current); IR 354 Load 1 total_kW (Load 1 total kW); IR 360 Load 1 total_aPF (Load 1 power factor).

How do I enable Modbus control of the Setra Systems Setra Power Meter (SPM) multi-circuit power meter?

The list does not describe setup. It shows the meter can run Modbus TCP (the slave address row reads 0 in that mode) as well as a serial slave address.

Where is the official Setra Systems Setra Power Meter (SPM) multi-circuit power meter Modbus documentation?

The source is Setra Power Meter Modbus Register Master List (SS-SPM-MODBUS_G), published free by Setra Systems at https://content.setra.com/hubfs/modbus-register-list.pdf.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Setra Power Meter Modbus Register Master List · SS-SPM-MODBUS_G. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.