Energy meter (heat / cooling meter) · Modbus register map

Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module Modbus register map

Updated 17 November 2026

Short answer

Sontex's Supercal 531 integrator and the Superstatic 440/449 heat and cooling meters take an optional RS-485 plug-in module that makes them a Modbus RTU or ASCII slave. Settings and the clock are holding registers, meter values are input registers and error flags are discrete inputs. This map covers the settings block, device information, error flags and the IEEE-754 float copies of energy, volume, pulse inputs, power, flow and temperatures, including the Set-Day stored values.

This page lists 79 Modbus registers for the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Sontex’s own free documentation (linked below) and checked against it.

Manufacturer
Sontex
Model
Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module
Equipment type
Energy meter (heat / cooling meter)
Registers
79 (17 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Firmware
Integrator / meter firmware FW 3.7 or higher
Also known as
Supercal 531, Superstatic 440, Superstatic 449, Sontex Modbus EIA-485 module, 0531P217
Source document
Modbus EIA-485 Module for Supercal 531 and Superstatic 440/449 - Instructions for Use · 0531P217 V05 · rev. 2019-09 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module

Integration in brief

Fit the Modbus module, wire D0/D1/Common, and poll input registers with function 04 using low-word-first floats: energy 30103, volume 30303, power 30703, flow 30713 and temperatures 30723/30725/30733, plus their unit codes. Discrete inputs 10001-10016 report meter errors.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 100Energy unit (float block)UINT16Energy unit codeRead
IR 102Energy totalizer heatingFLOAT32 CDABEnergy totalizer (float)Read
IR 302VolumeFLOAT32 CDABVolume (float)Read
IR 702PowerFLOAT32 CDABPower (float)Read
IR 712FlowFLOAT32 CDABFlow (float)Read
IR 722High temperatureFLOAT32 CDABHigh temperatureRead
IR 724Low temperatureFLOAT32 CDABLow temperatureRead
DI 2Error status: flowBITFlow error flagRead

Enable Modbus control & writes

The integrator detects the module automatically once it is plugged into a module slot; no setting is needed. Baud rate is set with DIP switch S2 (default 19200), bias and termination with DIP switch S1.

Byte order & addressing

Network setup

Watch out for

Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

79 of 79 shown
Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
DI0doc 10001Error status: temp. sensor 11 = error active.BITRead
DI1doc 10002Error status: temp. sensor 21 = error active.BITRead
DI2doc 10003Error status: flow1 = error active.BITRead
DI3doc 10004Error status: MET access1 = error active.BITRead
DI4doc 10005Error status: MIO access1 = error active.BITRead
DI5doc 10006Error status: EEPROM blank / invalid1 = error active.BITRead
DI6doc 10007Error status: AD converter1 = error active.BITRead
DI7doc 10008Error status: hardware1 = error active.BITRead
DI8doc 10009Error status: supply power1 = error active.BITRead
DI9doc 10010Error status: option 11 = error active.BITRead
DI10doc 10011Error status: option 21 = error active.BITRead
DI11doc 10012Error status: A11 = error active.BITRead
DI12doc 10013Error status: A21 = error active.BITRead
DI13doc 10014Error status: internal HW1 = error active.BITRead
DI14doc 10015Error status: CRC error1 = error active.BITRead
DI15doc 10016Error status: configuration error1 = error active.BITRead
IR0doc 30001 - 30002Fabrication number METMeter serial number.UINT32CDABRead
IR2doc 30003Firmware versionUINT16Read
IR3doc 30004 - 30005Baud rateUINT32CDABRead
IR5doc 30006 - 30007Running hoursUINT32CDABhRead
IR7doc 30008Last Set-Day 1: monthUINT16Read
IR8doc 30009Last Set-Day 1: dayUINT16Read
IR9doc 30010Last Set-Day 2: monthUINT16Read
IR10doc 30011Last Set-Day 2: dayUINT16Read
IR11doc 30012Last monthly data: dayUINT16Read
IR100doc 30101Energy unit (float block)Unit code for the energy floats.UINT16Read18 = Wh; 19 = kWh; 20 = BTU; 126 = MJ; 146 = MWh; 226 = GJ
IR102doc 30103 - 30104Energy totalizer heatingUnit per 30101.FLOAT32CDABRead
IR104doc 30105 - 30106Energy totalizer tariff 1Unit per 30101.FLOAT32CDABRead
IR106doc 30107 - 30108Energy totalizer tariff 2Unit per 30101.FLOAT32CDABRead
IR108doc 30109 - 30110Energy stored ST1Energy at Set-Day 1; unit per 30101.FLOAT32CDABRead
IR110doc 30111 - 30112Energy tariff 1 stored ST1FLOAT32CDABRead
IR112doc 30113 - 30114Energy tariff 2 stored ST1FLOAT32CDABRead
IR114doc 30115 - 30116Energy stored ST2Energy at Set-Day 2; unit per 30101.FLOAT32CDABRead
IR116doc 30117 - 30118Energy tariff 1 stored ST2FLOAT32CDABRead
IR118doc 30119 - 30120Energy tariff 2 stored ST2FLOAT32CDABRead
IR300doc 30301Volume unit (float block)UINT16Read80 = m3; 83 = US gallon
IR302doc 30303 - 30304VolumeUnit per 30301.FLOAT32CDABRead
IR304doc 30305 - 30306Volume tariff 1FLOAT32CDABRead
IR306doc 30307 - 30308Volume tariff 2FLOAT32CDABRead
IR308doc 30309 - 30310Volume stored ST1FLOAT32CDABRead
IR310doc 30311 - 30312Volume tariff 1 stored ST1FLOAT32CDABRead
IR312doc 30313 - 30314Volume tariff 2 stored ST1FLOAT32CDABRead
IR314doc 30315 - 30316Volume stored ST2FLOAT32CDABRead
IR316doc 30317 - 30318Volume tariff 1 stored ST2FLOAT32CDABRead
IR318doc 30319 - 30320Volume tariff 2 stored ST2FLOAT32CDABRead
IR500doc 30501Auxiliary A1 unit (float block)UINT16Read0 = No unit; 18 = Wh; 19 = kWh; 20 = BTU; 80 = m3; 83 = US gallon; 126 = MJ; 146 = MWh; 226 = GJ
IR502doc 30503 - 30504Auxiliary A1Pulse input A1 counter; unit per 30501.FLOAT32CDABRead
IR504doc 30505 - 30506Auxiliary A1 stored ST1FLOAT32CDABRead
IR506doc 30507 - 30508Auxiliary A1 stored ST2FLOAT32CDABRead
IR510doc 30511Auxiliary A2 unit (float block)UINT16Read0 = No unit; 18 = Wh; 19 = kWh; 20 = BTU; 80 = m3; 83 = US gallon; 126 = MJ; 146 = MWh; 226 = GJ
IR512doc 30513 - 30514Auxiliary A2Pulse input A2 counter; unit per 30511.FLOAT32CDABRead
IR514doc 30515 - 30516Auxiliary A2 stored ST1FLOAT32CDABRead
IR516doc 30517 - 30518Auxiliary A2 stored ST2FLOAT32CDABRead
IR700doc 30701Power unit (float block)UINT16Read47 = W; 48 = kW
IR702doc 30703 - 30704PowerUnit per 30701.FLOAT32CDABRead
IR710doc 30711Flow unit (float block)UINT16Read135 = m3/h
IR712doc 30713 - 30714FlowFLOAT32CDABm3/hRead
IR720doc 30721Temperature unit (float block)UINT16Read62 = °C
IR722doc 30723 - 30724High temperatureHot-side temperature.FLOAT32CDAB°CRead
IR724doc 30725 - 30726Low temperatureCold-side temperature.FLOAT32CDAB°CRead
IR730doc 30731Delta temperature unit (float block)UINT16Read63 = K
IR732doc 30733 - 30734Delta temperatureFLOAT32CDABKRead
HR10doc 40011Actual date: yearUINT16Read/write
HR11doc 40012Actual date: monthUINT16Read/write
HR12doc 40013Actual date: dayUINT16Read/write
HR13doc 40014Actual time: hourUINT16Read/write
HR14doc 40015Actual time: minuteUINT16Read/write
HR15doc 40016Actual time: secondUINT16Read/write
HR16doc 40017Password 'Communication'Must be written (1234) in the same telegram as new comm settings.UINT16Read/write
HR17doc 40018Modbus address1-247.UINT16Read/write
HR18doc 40019ParityUINT16Read/write0 = None; 1 = Odd; 2 = Even
HR19doc 40020Flow control (transmission mode)Source lists 'MB_RTU=0, MB_RTU=1'; see notes.UINT16Read/write
HR20doc 40021Stop bits1 or 2.UINT16Read/write
HR22doc 40023 - 40024Custom IDOEM serial number.UINT32CDABRead/write
HR24doc 40025Password 'Set Day'UINT16Read/write
HR25doc 40026Set-Day 1: monthUINT16Read/write
HR26doc 40027Set-Day 1: dayUINT16Read/write
HR27doc 40028Set-Day 2: monthUINT16Read/write
HR28doc 40029Set-Day 2: dayUINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module

What Modbus registers does the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module have?

This map lists 79 registers: 16 discrete inputs, 46 input registers, 17 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual says register numbering starts at 1, which is physical address 0 in the telegram, and prints Modicon-style references: 40011 is holding wire address 10, 30103 is input wire address 102, 10001 is discrete input 0. Its own Modbus Poll / ModScan screenshots use the same 30713/30103 references.

What byte order does the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module?

Start with IR 100 Energy unit (float block) (Energy unit code); IR 102 Energy totalizer heating (Energy totalizer (float)); IR 302 Volume (Volume (float)); IR 702 Power (Power (float)); IR 712 Flow (Flow (float)); IR 722 High temperature (High temperature); IR 724 Low temperature (Low temperature); DI 2 Error status: flow (Flow error flag).

How do I enable Modbus control of the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module?

The integrator detects the module automatically once it is plugged into a module slot; no setting is needed. Baud rate is set with DIP switch S2 (default 19200), bias and termination with DIP switch S1.

Where is the official Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module Modbus documentation?

The source is Modbus EIA-485 Module for Supercal 531 and Superstatic 440/449 - Instructions for Use (0531P217 V05), revision 2019-09. Sontex doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.neovac.ch/downloadcenter/document-a9b1ddfb-1182-446f-b1b9-132bdb729345.pdf. It may be an older revision, so check it against the live unit.

Other power & energy meters register maps

All power & energy meters Modbus register maps →