Energy meter (heat / cooling meter) · Modbus register map
Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module Modbus register map
Updated 17 November 2026
Sontex's Supercal 531 integrator and the Superstatic 440/449 heat and cooling meters take an optional RS-485 plug-in module that makes them a Modbus RTU or ASCII slave. Settings and the clock are holding registers, meter values are input registers and error flags are discrete inputs. This map covers the settings block, device information, error flags and the IEEE-754 float copies of energy, volume, pulse inputs, power, flow and temperatures, including the Set-Day stored values.
This page lists 79 Modbus registers for the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Sontex’s own free documentation (linked below) and checked against it.
- Manufacturer
- Sontex
- Model
- Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module
- Equipment type
- Energy meter (heat / cooling meter)
- Registers
- 79 (17 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- Integrator / meter firmware FW 3.7 or higher
- Also known as
- Supercal 531, Superstatic 440, Superstatic 449, Sontex Modbus EIA-485 module, 0531P217
Integration notes: Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module
Fit the Modbus module, wire D0/D1/Common, and poll input registers with function 04 using low-word-first floats: energy 30103, volume 30303, power 30703, flow 30713 and temperatures 30723/30725/30733, plus their unit codes. Discrete inputs 10001-10016 report meter errors.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 100 | Energy unit (float block) | UINT16 | Energy unit code | Read |
| IR 102 | Energy totalizer heating | FLOAT32 CDAB | Energy totalizer (float) | Read |
| IR 302 | Volume | FLOAT32 CDAB | Volume (float) | Read |
| IR 702 | Power | FLOAT32 CDAB | Power (float) | Read |
| IR 712 | Flow | FLOAT32 CDAB | Flow (float) | Read |
| IR 722 | High temperature | FLOAT32 CDAB | High temperature | Read |
| IR 724 | Low temperature | FLOAT32 CDAB | Low temperature | Read |
| DI 2 | Error status: flow | BIT | Flow error flag | Read |
Enable Modbus control & writes
The integrator detects the module automatically once it is plugged into a module slot; no setting is needed. Baud rate is set with DIP switch S2 (default 19200), bias and termination with DIP switch S1.
Byte order & addressing
- 32-bit values are low word first (CDAB) even though the tables say '(h-l)'.
- Each float block has a unit register two registers before the value; read it once to know whether energy is kWh, MWh or GJ.
Network setup
- Defaults: address 1, RTU, 19200 baud, 8 data bits, even parity, 1 stop bit.
- Address, parity, stop bits and RTU/ASCII can be changed over Modbus by writing 40017 (password) through the wanted register in one telegram; the module then reboots and is silent for 30-60 s. Do not power it down for 90-120 s.
- If settings are changed with Prog531/449 over the optical port, the module must be power-cycled (wait 15 s, power off at least 10 s) before they take effect.
- In ASCII mode with no parity the module uses 2 stop bits automatically.
Watch out for
- The module needs integrator firmware 3.7 or later.
- The module is powered from the integrator's mains supply board or an external 12 VDC / 150 mA supply; without that supply it will not answer.
Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| DI | 0doc 10001 | Error status: temp. sensor 1 | 1 = error active. | BIT | Read | ||||
| DI | 1doc 10002 | Error status: temp. sensor 2 | 1 = error active. | BIT | Read | ||||
| DI | 2doc 10003 | Error status: flow | 1 = error active. | BIT | Read | ||||
| DI | 3doc 10004 | Error status: MET access | 1 = error active. | BIT | Read | ||||
| DI | 4doc 10005 | Error status: MIO access | 1 = error active. | BIT | Read | ||||
| DI | 5doc 10006 | Error status: EEPROM blank / invalid | 1 = error active. | BIT | Read | ||||
| DI | 6doc 10007 | Error status: AD converter | 1 = error active. | BIT | Read | ||||
| DI | 7doc 10008 | Error status: hardware | 1 = error active. | BIT | Read | ||||
| DI | 8doc 10009 | Error status: supply power | 1 = error active. | BIT | Read | ||||
| DI | 9doc 10010 | Error status: option 1 | 1 = error active. | BIT | Read | ||||
| DI | 10doc 10011 | Error status: option 2 | 1 = error active. | BIT | Read | ||||
| DI | 11doc 10012 | Error status: A1 | 1 = error active. | BIT | Read | ||||
| DI | 12doc 10013 | Error status: A2 | 1 = error active. | BIT | Read | ||||
| DI | 13doc 10014 | Error status: internal HW | 1 = error active. | BIT | Read | ||||
| DI | 14doc 10015 | Error status: CRC error | 1 = error active. | BIT | Read | ||||
| DI | 15doc 10016 | Error status: configuration error | 1 = error active. | BIT | Read | ||||
| IR | 0doc 30001 - 30002 | Fabrication number MET | Meter serial number. | UINT32 | CDAB | Read | |||
| IR | 2doc 30003 | Firmware version | UINT16 | Read | |||||
| IR | 3doc 30004 - 30005 | Baud rate | UINT32 | CDAB | Read | ||||
| IR | 5doc 30006 - 30007 | Running hours | UINT32 | CDAB | h | Read | |||
| IR | 7doc 30008 | Last Set-Day 1: month | UINT16 | Read | |||||
| IR | 8doc 30009 | Last Set-Day 1: day | UINT16 | Read | |||||
| IR | 9doc 30010 | Last Set-Day 2: month | UINT16 | Read | |||||
| IR | 10doc 30011 | Last Set-Day 2: day | UINT16 | Read | |||||
| IR | 11doc 30012 | Last monthly data: day | UINT16 | Read | |||||
| IR | 100doc 30101 | Energy unit (float block) | Unit code for the energy floats. | UINT16 | Read | 18 = Wh; 19 = kWh; 20 = BTU; 126 = MJ; 146 = MWh; 226 = GJ | |||
| IR | 102doc 30103 - 30104 | Energy totalizer heating | Unit per 30101. | FLOAT32 | CDAB | Read | |||
| IR | 104doc 30105 - 30106 | Energy totalizer tariff 1 | Unit per 30101. | FLOAT32 | CDAB | Read | |||
| IR | 106doc 30107 - 30108 | Energy totalizer tariff 2 | Unit per 30101. | FLOAT32 | CDAB | Read | |||
| IR | 108doc 30109 - 30110 | Energy stored ST1 | Energy at Set-Day 1; unit per 30101. | FLOAT32 | CDAB | Read | |||
| IR | 110doc 30111 - 30112 | Energy tariff 1 stored ST1 | FLOAT32 | CDAB | Read | ||||
| IR | 112doc 30113 - 30114 | Energy tariff 2 stored ST1 | FLOAT32 | CDAB | Read | ||||
| IR | 114doc 30115 - 30116 | Energy stored ST2 | Energy at Set-Day 2; unit per 30101. | FLOAT32 | CDAB | Read | |||
| IR | 116doc 30117 - 30118 | Energy tariff 1 stored ST2 | FLOAT32 | CDAB | Read | ||||
| IR | 118doc 30119 - 30120 | Energy tariff 2 stored ST2 | FLOAT32 | CDAB | Read | ||||
| IR | 300doc 30301 | Volume unit (float block) | UINT16 | Read | 80 = m3; 83 = US gallon | ||||
| IR | 302doc 30303 - 30304 | Volume | Unit per 30301. | FLOAT32 | CDAB | Read | |||
| IR | 304doc 30305 - 30306 | Volume tariff 1 | FLOAT32 | CDAB | Read | ||||
| IR | 306doc 30307 - 30308 | Volume tariff 2 | FLOAT32 | CDAB | Read | ||||
| IR | 308doc 30309 - 30310 | Volume stored ST1 | FLOAT32 | CDAB | Read | ||||
| IR | 310doc 30311 - 30312 | Volume tariff 1 stored ST1 | FLOAT32 | CDAB | Read | ||||
| IR | 312doc 30313 - 30314 | Volume tariff 2 stored ST1 | FLOAT32 | CDAB | Read | ||||
| IR | 314doc 30315 - 30316 | Volume stored ST2 | FLOAT32 | CDAB | Read | ||||
| IR | 316doc 30317 - 30318 | Volume tariff 1 stored ST2 | FLOAT32 | CDAB | Read | ||||
| IR | 318doc 30319 - 30320 | Volume tariff 2 stored ST2 | FLOAT32 | CDAB | Read | ||||
| IR | 500doc 30501 | Auxiliary A1 unit (float block) | UINT16 | Read | 0 = No unit; 18 = Wh; 19 = kWh; 20 = BTU; 80 = m3; 83 = US gallon; 126 = MJ; 146 = MWh; 226 = GJ | ||||
| IR | 502doc 30503 - 30504 | Auxiliary A1 | Pulse input A1 counter; unit per 30501. | FLOAT32 | CDAB | Read | |||
| IR | 504doc 30505 - 30506 | Auxiliary A1 stored ST1 | FLOAT32 | CDAB | Read | ||||
| IR | 506doc 30507 - 30508 | Auxiliary A1 stored ST2 | FLOAT32 | CDAB | Read | ||||
| IR | 510doc 30511 | Auxiliary A2 unit (float block) | UINT16 | Read | 0 = No unit; 18 = Wh; 19 = kWh; 20 = BTU; 80 = m3; 83 = US gallon; 126 = MJ; 146 = MWh; 226 = GJ | ||||
| IR | 512doc 30513 - 30514 | Auxiliary A2 | Pulse input A2 counter; unit per 30511. | FLOAT32 | CDAB | Read | |||
| IR | 514doc 30515 - 30516 | Auxiliary A2 stored ST1 | FLOAT32 | CDAB | Read | ||||
| IR | 516doc 30517 - 30518 | Auxiliary A2 stored ST2 | FLOAT32 | CDAB | Read | ||||
| IR | 700doc 30701 | Power unit (float block) | UINT16 | Read | 47 = W; 48 = kW | ||||
| IR | 702doc 30703 - 30704 | Power | Unit per 30701. | FLOAT32 | CDAB | Read | |||
| IR | 710doc 30711 | Flow unit (float block) | UINT16 | Read | 135 = m3/h | ||||
| IR | 712doc 30713 - 30714 | Flow | FLOAT32 | CDAB | m3/h | Read | |||
| IR | 720doc 30721 | Temperature unit (float block) | UINT16 | Read | 62 = °C | ||||
| IR | 722doc 30723 - 30724 | High temperature | Hot-side temperature. | FLOAT32 | CDAB | °C | Read | ||
| IR | 724doc 30725 - 30726 | Low temperature | Cold-side temperature. | FLOAT32 | CDAB | °C | Read | ||
| IR | 730doc 30731 | Delta temperature unit (float block) | UINT16 | Read | 63 = K | ||||
| IR | 732doc 30733 - 30734 | Delta temperature | FLOAT32 | CDAB | K | Read | |||
| HR | 10doc 40011 | Actual date: year | UINT16 | Read/write | |||||
| HR | 11doc 40012 | Actual date: month | UINT16 | Read/write | |||||
| HR | 12doc 40013 | Actual date: day | UINT16 | Read/write | |||||
| HR | 13doc 40014 | Actual time: hour | UINT16 | Read/write | |||||
| HR | 14doc 40015 | Actual time: minute | UINT16 | Read/write | |||||
| HR | 15doc 40016 | Actual time: second | UINT16 | Read/write | |||||
| HR | 16doc 40017 | Password 'Communication' | Must be written (1234) in the same telegram as new comm settings. | UINT16 | Read/write | ||||
| HR | 17doc 40018 | Modbus address | 1-247. | UINT16 | Read/write | ||||
| HR | 18doc 40019 | Parity | UINT16 | Read/write | 0 = None; 1 = Odd; 2 = Even | ||||
| HR | 19doc 40020 | Flow control (transmission mode) | Source lists 'MB_RTU=0, MB_RTU=1'; see notes. | UINT16 | Read/write | ||||
| HR | 20doc 40021 | Stop bits | 1 or 2. | UINT16 | Read/write | ||||
| HR | 22doc 40023 - 40024 | Custom ID | OEM serial number. | UINT32 | CDAB | Read/write | |||
| HR | 24doc 40025 | Password 'Set Day' | UINT16 | Read/write | |||||
| HR | 25doc 40026 | Set-Day 1: month | UINT16 | Read/write | |||||
| HR | 26doc 40027 | Set-Day 1: day | UINT16 | Read/write | |||||
| HR | 27doc 40028 | Set-Day 2: month | UINT16 | Read/write | |||||
| HR | 28doc 40029 | Set-Day 2: day | UINT16 | Read/write |
Notes on this map
- This is an unaltered Sontex manual hosted by the Swiss distributor NeoVac; Sontex keeps its own copy behind a login-only extranet and does not host it publicly.
- Word order: the tables label 32-bit values '(h-l)' but every table footer says Sontex uses l-h ordering, and the word-swapping example (p. 10) puts the low word in the first register (30723) and the high word in the next (30724). The ModScan example also uses 'least significant register first'. All 32-bit values here are therefore CDAB.
- Units of the float values follow the unit-code register at the start of each block (e.g. 30101 energy: 18 Wh, 19 kWh, 146 MWh, 126 MJ, 226 GJ, 20 BTU).
- Left out: the 'long data point' integer copies (30201-30220, 30401-30420, 30601-30618, 30801-30834). Their value must be divided by 10 to the power of a separate Decimals register (0-3), which cannot be expressed as a fixed scale. The float copies carry the same quantities.
- Left out: monthly logs 31001-33266 (32 stored months per quantity, 2 registers each, floats from 31003 and longs from 31203), which are long arrays rather than single points.
- 40020 Flow control is printed as 'MB_RTU=0, MB_RTU=1' (presumably RTU/ASCII, but the source does not say), so no enum is given. 32-bit integers are given as UINT32 because the source does not mark them signed (it marks signed values explicitly elsewhere).
- The same document also covers the BACnet MS/TP module; that part is not used here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module
What Modbus registers does the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module have?
This map lists 79 registers: 16 discrete inputs, 46 input registers, 17 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual says register numbering starts at 1, which is physical address 0 in the telegram, and prints Modicon-style references: 40011 is holding wire address 10, 30103 is input wire address 102, 10001 is discrete input 0. Its own Modbus Poll / ModScan screenshots use the same 30713/30103 references.
What byte order does the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module?
Start with IR 100 Energy unit (float block) (Energy unit code); IR 102 Energy totalizer heating (Energy totalizer (float)); IR 302 Volume (Volume (float)); IR 702 Power (Power (float)); IR 712 Flow (Flow (float)); IR 722 High temperature (High temperature); IR 724 Low temperature (Low temperature); DI 2 Error status: flow (Flow error flag).
How do I enable Modbus control of the Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module?
The integrator detects the module automatically once it is plugged into a module slot; no setting is needed. Baud rate is set with DIP switch S2 (default 19200), bias and termination with DIP switch S1.
Where is the official Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module Modbus documentation?
The source is Modbus EIA-485 Module for Supercal 531 and Superstatic 440/449 - Instructions for Use (0531P217 V05), revision 2019-09. Sontex doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.neovac.ch/downloadcenter/document-a9b1ddfb-1182-446f-b1b9-132bdb729345.pdf. It may be an older revision, so check it against the live unit.
Other power & energy meters register maps
- Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Power meter
Accuenergy AcuRev 1310 series DIN-rail power meter
Accuenergy AcuRev 1310 series (1312/1313/1314) DIN-rail meters, Modbus map workbook revision 1.1.
Also known as: AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310 - Power meter (universal measuring / power quality device)
Camille Bauer Metrawatt SINEAX CAM universal measurement device (Modbus/TCP)
SINEAX CAM with Ethernet (Modbus/TCP) bus card; document W 157471, change 2014-018. Instantaneous values, THD/TDD, system analysis, analog inputs, I/O states.
Also known as: SINEAX CAM, CAM - Energy meter
Carlo Gavazzi EM24-IS (SFA and SFB models)
EM24-DIN AV2/AV5 IS SFA and SFB versions (identification codes 1696-1699), protocol revision 2.0.
Also known as: EM24DINAV23XISSFA, EM24DINAV53XISSFA, EM24DINAV23XISSFB, EM24DINAV53XISSFB, EM24 SFA, EM24 SFB - Power meter (power analyzer)
Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)
WM14 Advanced (revision 5 onward) and CPT-DIN Advanced (revision 6 onward) with RS485 (or RS232 on CPT-DIN), protocol version 2 revision 2 (2008-01-09).
Also known as: WM14-96 Advanced, WM14 A, CPT-DIN Advanced, CPT A, CPT-DIN A - Power meter
Circutor CVM-C5
Circutor CVM-C5 panel power analyzer, RS-485 Modbus RTU versions (ITF-485, MC-485, mV-485), manual M026B01-03.
Also known as: CVM-C5-ITF-485, CVM-C5-MC-485, CVM-C5-mV-485
All power & energy meters Modbus register maps →
Source: Modbus EIA-485 Module for Supercal 531 and Superstatic 440/449 - Instructions for Use · 0531P217 V05 · rev. 2019-09 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.