Power meter (power analyzer) · Modbus register map

Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) Modbus register map

Updated 17 November 2026

Short answer

The WM14 Advanced panel analyzer and the CPT-DIN Advanced DIN-rail transducer are older Carlo Gavazzi meters with an optional RS485 Modbus RTU port. Measurements are IEEE 754 floats sent low word first. This map covers voltages, currents, powers, PF, frequency, asymmetry, demand, max/min and THD values, the model code, alarm outputs, CT/VT ratio, integration times, serial settings and the reset command.

This page lists 84 Modbus registers for the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Carlo Gavazzi’s own free documentation (linked below) and checked against it.

Manufacturer
Carlo Gavazzi
Model
WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)
Equipment type
Power meter (power analyzer)
Registers
84 (9 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Firmware
WM14 rev. 5+, CPT-DIN rev. 6+
Also known as
WM14-96 Advanced, WM14 A, CPT-DIN Advanced, CPT A, CPT-DIN A
Source document
WM14 Advanced / CPT-DIN Advanced Communication Protocol · Version 2 Revision 2 · rev. 2008-01-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)

Integration in brief

Read input registers 0000h-003Fh in chunks of up to 12 registers and decode IEEE 754 floats low word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0V L1-NFLOAT32 CDABV L1-NRead
IR 12A L1FLOAT32 CDABA L1Read
IR 50W systemFLOAT32 CDABW systemRead
IR 56PF systemFLOAT32 CDABPF systemRead
IR 58FrequencyFLOAT32 CDABFrequencyRead
IR 211Carlo Gavazzi identification codeUINT16Model codeRead

Enable Modbus control & writes

Needs the optional RS485 (S1) serial module; set the address (01A1h) and baud rate (01A2h) or use the front keys.

Byte order & addressing

Network setup

Watch out for

Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

84 of 84 shown
Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 300001 / 0000hV L1-NFLOAT32CDABVRead
IR2doc 300003 / 0002hV L2-NFLOAT32CDABVRead
IR4doc 300005 / 0004hV L3-NFLOAT32CDABVRead
IR6doc 300007 / 0006hV L1-L2FLOAT32CDABVRead
IR8doc 300009 / 0008hV L2-L3FLOAT32CDABVRead
IR10doc 300011 / 000AhV L3-L1FLOAT32CDABVRead
IR12doc 300013 / 000ChA L1FLOAT32CDABARead
IR14doc 300015 / 000EhA L2FLOAT32CDABARead
IR16doc 300017 / 0010hA L3FLOAT32CDABARead
IR18doc 300019 / 0012hA NFLOAT32CDABARead
IR20doc 300021 / 0014hW L1FLOAT32CDABWRead
IR22doc 300023 / 0016hW L2FLOAT32CDABWRead
IR24doc 300025 / 0018hW L3FLOAT32CDABWRead
IR26doc 300027 / 001AhVA L1FLOAT32CDABVARead
IR28doc 300029 / 001ChVA L2FLOAT32CDABVARead
IR30doc 300031 / 001EhVA L3FLOAT32CDABVARead
IR32doc 300033 / 0020hvar L1FLOAT32CDABvarRead
IR34doc 300035 / 0022hvar L2FLOAT32CDABvarRead
IR36doc 300037 / 0024hvar L3FLOAT32CDABvarRead
IR38doc 300039 / 0026hPhase sequence-1 = all three phases present in correct order; +1 = wrong connection.FLOAT32CDABRead
IR40doc 300041 / 0028hPF L1Negative = lead (C), positive = lag (L).FLOAT32CDABRead
IR42doc 300043 / 002AhPF L2FLOAT32CDABRead
IR44doc 300045 / 002ChPF L3FLOAT32CDABRead
IR46doc 300047 / 002EhV L-N systemFLOAT32CDABVRead
IR48doc 300049 / 0030hV L-L systemFLOAT32CDABVRead
IR50doc 300051 / 0032hW systemFLOAT32CDABWRead
IR52doc 300053 / 0034hVA systemFLOAT32CDABVARead
IR54doc 300055 / 0036hvar systemFLOAT32CDABvarRead
IR56doc 300057 / 0038hPF systemNegative = lead (C), positive = lag (L).FLOAT32CDABRead
IR58doc 300059 / 003AhFrequencyFLOAT32CDABHzRead
IR60doc 300061 / 003ChAsymmetry L-NFLOAT32CDAB%Read
IR62doc 300063 / 003EhAsymmetry L-LFLOAT32CDAB%Read
IR64doc 300065 / 0040hA L1 dmdFLOAT32CDABARead
IR66doc 300067 / 0042hA L2 dmdFLOAT32CDABARead
IR68doc 300069 / 0044hA L3 dmdFLOAT32CDABARead
IR70doc 300071 / 0046hW L1 dmdFLOAT32CDABWRead
IR72doc 300073 / 0048hW L2 dmdFLOAT32CDABWRead
IR74doc 300075 / 004AhW L3 dmdFLOAT32CDABWRead
IR76doc 300077 / 004ChVA L1 dmdFLOAT32CDABVARead
IR78doc 300079 / 004EhVA L2 dmdFLOAT32CDABVARead
IR80doc 300081 / 0050hVA L3 dmdFLOAT32CDABVARead
IR82doc 300083 / 0052hW dmdFLOAT32CDABWRead
IR84doc 300085 / 0054hVA dmdFLOAT32CDABVARead
IR96doc 300097 / 0060hA MAXFLOAT32CDABARead
IR98doc 300099 / 0062hA MAX dmdFLOAT32CDABARead
IR100doc 300101 / 0064hA L1 MAXFLOAT32CDABARead
IR102doc 300103 / 0066hA L2 MAXFLOAT32CDABARead
IR104doc 300105 / 0068hA L3 MAXFLOAT32CDABARead
IR106doc 300107 / 006AhW L1 MAXFLOAT32CDABWRead
IR108doc 300109 / 006ChW L2 MAXFLOAT32CDABWRead
IR110doc 300111 / 006EhW L3 MAXFLOAT32CDABWRead
IR112doc 300113 / 0070hW MAX dmdFLOAT32CDABWRead
IR114doc 300115 / 0072hVA MAX dmdFLOAT32CDABVARead
IR116doc 300117 / 0074hPF L1 minFLOAT32CDABRead
IR118doc 300119 / 0076hPF L2 minFLOAT32CDABRead
IR120doc 300121 / 0078hPF L3 minFLOAT32CDABRead
IR122doc 300123 / 007AhA L1 minWM14 Advanced only.FLOAT32CDABARead
IR124doc 300125 / 007ChA L2 minWM14 Advanced only.FLOAT32CDABARead
IR126doc 300127 / 007EhA L3 minWM14 Advanced only.FLOAT32CDABARead
IR128doc 300129 / 0080hV L1 minWM14 Advanced only.FLOAT32CDABVRead
IR130doc 300131 / 0082hV L2 minWM14 Advanced only.FLOAT32CDABVRead
IR132doc 300133 / 0084hV L3 minWM14 Advanced only.FLOAT32CDABVRead
IR134doc 300135 / 0086hV L1 MAXWM14 Advanced only.FLOAT32CDABVRead
IR136doc 300137 / 0088hV L2 MAXWM14 Advanced only.FLOAT32CDABVRead
IR138doc 300139 / 008AhV L3 MAXWM14 Advanced only.FLOAT32CDABVRead
IR140doc 300141 / 008ChTHD V1WM14 Advanced only; THD must be enabled (01A8h).FLOAT32CDAB%Read
IR142doc 300143 / 008EhTHD V2WM14 Advanced only; THD must be enabled (01A8h).FLOAT32CDAB%Read
IR144doc 300145 / 0090hTHD V3WM14 Advanced only; THD must be enabled (01A8h).FLOAT32CDAB%Read
IR146doc 300147 / 0092hTHD I1WM14 Advanced only; THD must be enabled (01A8h).FLOAT32CDAB%Read
IR148doc 300149 / 0094hTHD I2WM14 Advanced only; THD must be enabled (01A8h).FLOAT32CDAB%Read
IR150doc 300151 / 0096hTHD I3WM14 Advanced only; THD must be enabled (01A8h).FLOAT32CDAB%Read
IR211doc 300212 / 00D3hCarlo Gavazzi identification codeUINT16Read33 = CPT A AV5 3-phase; 34 = CPT A AV6 3-phase; 35 = CPT A AV5 1-phase; 36 = CPT A AV6 1-phase; 39 = WM14 A AV5 3-phase; 40 = WM14 A AV6 3-phase
IR222doc 300223 / 00DEhFirmware revisionLow byte = progressive revision number.UINT16Read
IR259doc 300260 / 0103hOutput 1 alarmUINT16Read0 = Not in alarm; 1 = In alarm
IR260doc 300261 / 0104hOutput 2 alarmUINT16Read0 = Not in alarm; 1 = In alarm
HR409doc 300410 / 0199hPassword0-999; out-of-range values are treated as 0.UINT16Read/write
HR410doc 300411 / 019AhCurrent transformer ratio1-60000.UINT16Read/write
HR411doc 300412 / 019BhVoltage transformer ratio1-60000, divided by 10 internally.UINT16× 0.1Read/write
HR414doc 300415 / 019EhPower integration time1-30 min.UINT16minRead/write
HR415doc 300416 / 019FhCurrent integration time1-30 min.UINT16minRead/write
HR417doc 300418 / 01A1hModbus address1-255.UINT16Read/write
HR418doc 300419 / 01A2hBaud rateUINT16Read/write0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400
HR424doc 300417 / 01A8hTHD calculationUINT16Read/write0 = Disabled; 1 = Enabled
HR8430doc 608431 / 20EEhReset commandUINT16Write0 = Reset all variables (instantaneous, min, MAX, dmd, counters); 256 = Reset all demand values; 512 = Reset energy counters and hour counter; 768 = Reset total energy counters; 1024 = Reset partial energy counters; 1280 = Reset hour counters; 1536 = Reset MAX and min values

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)

What Modbus registers does the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) have?

This map lists 84 registers: 75 input registers, 9 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Rows give a 6-digit Modicon number (3xxxxx) and the hex physical address; the hex address goes in the frame, so 300001 / 0000h is wire address 0. A few printed Modicon numbers do not match their hex address (0058h is printed 300099, 01A8h is printed 300417); the hex value is used.

What byte order does the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)?

Start with IR 0 V L1-N (V L1-N); IR 12 A L1 (A L1); IR 50 W system (W system); IR 56 PF system (PF system); IR 58 Frequency (Frequency); IR 211 Carlo Gavazzi identification code (Model code).

How do I enable Modbus control of the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)?

Needs the optional RS485 (S1) serial module; set the address (01A1h) and baud rate (01A2h) or use the front keys.

Where is the official Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) Modbus documentation?

The source is WM14 Advanced / CPT-DIN Advanced Communication Protocol (Version 2 Revision 2), revision 2008-01-09, published free by Carlo Gavazzi at https://www.gavazziautomation.com/fileadmin/images/PIM/OTHERSTUFF/COMPRO/WM14%20A%20and%20CPT%20A%20CP%20v2r2%20ENG%200108.pdf.

More Carlo Gavazzi Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: WM14 Advanced / CPT-DIN Advanced Communication Protocol · Version 2 Revision 2 · rev. 2008-01-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.