- WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)
Power meter (power analyzer) · Modbus register map
Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) Modbus register map
Updated 17 November 2026
The WM14 Advanced panel analyzer and the CPT-DIN Advanced DIN-rail transducer are older Carlo Gavazzi meters with an optional RS485 Modbus RTU port. Measurements are IEEE 754 floats sent low word first. This map covers voltages, currents, powers, PF, frequency, asymmetry, demand, max/min and THD values, the model code, alarm outputs, CT/VT ratio, integration times, serial settings and the reset command.
This page lists 84 Modbus registers for the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Carlo Gavazzi’s own free documentation (linked below) and checked against it.
- Manufacturer
- Carlo Gavazzi
- Model
- WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)
- Equipment type
- Power meter (power analyzer)
- Registers
- 84 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- WM14 rev. 5+, CPT-DIN rev. 6+
- Also known as
- WM14-96 Advanced, WM14 A, CPT-DIN Advanced, CPT A, CPT-DIN A
Integration notes: Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)
Read input registers 0000h-003Fh in chunks of up to 12 registers and decode IEEE 754 floats low word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | V L1-N | FLOAT32 CDAB | V L1-N | Read |
| IR 12 | A L1 | FLOAT32 CDAB | A L1 | Read |
| IR 50 | W system | FLOAT32 CDAB | W system | Read |
| IR 56 | PF system | FLOAT32 CDAB | PF system | Read |
| IR 58 | Frequency | FLOAT32 CDAB | Frequency | Read |
| IR 211 | Carlo Gavazzi identification code | UINT16 | Model code | Read |
Enable Modbus control & writes
Needs the optional RS485 (S1) serial module; set the address (01A1h) and baud rate (01A2h) or use the front keys.
Byte order & addressing
- Floats are CDAB.
- Max 12 registers per request on RS485.
- Some printed Modicon numbers are wrong; trust the hex address.
Network setup
- 8 data bits, no parity, 1 stop bit; baud 4800-38400.
Watch out for
- Energy counters are not in this map; see the notes.
Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 300001 / 0000h | V L1-N | FLOAT32 | CDAB | V | Read | |||
| IR | 2doc 300003 / 0002h | V L2-N | FLOAT32 | CDAB | V | Read | |||
| IR | 4doc 300005 / 0004h | V L3-N | FLOAT32 | CDAB | V | Read | |||
| IR | 6doc 300007 / 0006h | V L1-L2 | FLOAT32 | CDAB | V | Read | |||
| IR | 8doc 300009 / 0008h | V L2-L3 | FLOAT32 | CDAB | V | Read | |||
| IR | 10doc 300011 / 000Ah | V L3-L1 | FLOAT32 | CDAB | V | Read | |||
| IR | 12doc 300013 / 000Ch | A L1 | FLOAT32 | CDAB | A | Read | |||
| IR | 14doc 300015 / 000Eh | A L2 | FLOAT32 | CDAB | A | Read | |||
| IR | 16doc 300017 / 0010h | A L3 | FLOAT32 | CDAB | A | Read | |||
| IR | 18doc 300019 / 0012h | A N | FLOAT32 | CDAB | A | Read | |||
| IR | 20doc 300021 / 0014h | W L1 | FLOAT32 | CDAB | W | Read | |||
| IR | 22doc 300023 / 0016h | W L2 | FLOAT32 | CDAB | W | Read | |||
| IR | 24doc 300025 / 0018h | W L3 | FLOAT32 | CDAB | W | Read | |||
| IR | 26doc 300027 / 001Ah | VA L1 | FLOAT32 | CDAB | VA | Read | |||
| IR | 28doc 300029 / 001Ch | VA L2 | FLOAT32 | CDAB | VA | Read | |||
| IR | 30doc 300031 / 001Eh | VA L3 | FLOAT32 | CDAB | VA | Read | |||
| IR | 32doc 300033 / 0020h | var L1 | FLOAT32 | CDAB | var | Read | |||
| IR | 34doc 300035 / 0022h | var L2 | FLOAT32 | CDAB | var | Read | |||
| IR | 36doc 300037 / 0024h | var L3 | FLOAT32 | CDAB | var | Read | |||
| IR | 38doc 300039 / 0026h | Phase sequence | -1 = all three phases present in correct order; +1 = wrong connection. | FLOAT32 | CDAB | Read | |||
| IR | 40doc 300041 / 0028h | PF L1 | Negative = lead (C), positive = lag (L). | FLOAT32 | CDAB | Read | |||
| IR | 42doc 300043 / 002Ah | PF L2 | FLOAT32 | CDAB | Read | ||||
| IR | 44doc 300045 / 002Ch | PF L3 | FLOAT32 | CDAB | Read | ||||
| IR | 46doc 300047 / 002Eh | V L-N system | FLOAT32 | CDAB | V | Read | |||
| IR | 48doc 300049 / 0030h | V L-L system | FLOAT32 | CDAB | V | Read | |||
| IR | 50doc 300051 / 0032h | W system | FLOAT32 | CDAB | W | Read | |||
| IR | 52doc 300053 / 0034h | VA system | FLOAT32 | CDAB | VA | Read | |||
| IR | 54doc 300055 / 0036h | var system | FLOAT32 | CDAB | var | Read | |||
| IR | 56doc 300057 / 0038h | PF system | Negative = lead (C), positive = lag (L). | FLOAT32 | CDAB | Read | |||
| IR | 58doc 300059 / 003Ah | Frequency | FLOAT32 | CDAB | Hz | Read | |||
| IR | 60doc 300061 / 003Ch | Asymmetry L-N | FLOAT32 | CDAB | % | Read | |||
| IR | 62doc 300063 / 003Eh | Asymmetry L-L | FLOAT32 | CDAB | % | Read | |||
| IR | 64doc 300065 / 0040h | A L1 dmd | FLOAT32 | CDAB | A | Read | |||
| IR | 66doc 300067 / 0042h | A L2 dmd | FLOAT32 | CDAB | A | Read | |||
| IR | 68doc 300069 / 0044h | A L3 dmd | FLOAT32 | CDAB | A | Read | |||
| IR | 70doc 300071 / 0046h | W L1 dmd | FLOAT32 | CDAB | W | Read | |||
| IR | 72doc 300073 / 0048h | W L2 dmd | FLOAT32 | CDAB | W | Read | |||
| IR | 74doc 300075 / 004Ah | W L3 dmd | FLOAT32 | CDAB | W | Read | |||
| IR | 76doc 300077 / 004Ch | VA L1 dmd | FLOAT32 | CDAB | VA | Read | |||
| IR | 78doc 300079 / 004Eh | VA L2 dmd | FLOAT32 | CDAB | VA | Read | |||
| IR | 80doc 300081 / 0050h | VA L3 dmd | FLOAT32 | CDAB | VA | Read | |||
| IR | 82doc 300083 / 0052h | W dmd | FLOAT32 | CDAB | W | Read | |||
| IR | 84doc 300085 / 0054h | VA dmd | FLOAT32 | CDAB | VA | Read | |||
| IR | 96doc 300097 / 0060h | A MAX | FLOAT32 | CDAB | A | Read | |||
| IR | 98doc 300099 / 0062h | A MAX dmd | FLOAT32 | CDAB | A | Read | |||
| IR | 100doc 300101 / 0064h | A L1 MAX | FLOAT32 | CDAB | A | Read | |||
| IR | 102doc 300103 / 0066h | A L2 MAX | FLOAT32 | CDAB | A | Read | |||
| IR | 104doc 300105 / 0068h | A L3 MAX | FLOAT32 | CDAB | A | Read | |||
| IR | 106doc 300107 / 006Ah | W L1 MAX | FLOAT32 | CDAB | W | Read | |||
| IR | 108doc 300109 / 006Ch | W L2 MAX | FLOAT32 | CDAB | W | Read | |||
| IR | 110doc 300111 / 006Eh | W L3 MAX | FLOAT32 | CDAB | W | Read | |||
| IR | 112doc 300113 / 0070h | W MAX dmd | FLOAT32 | CDAB | W | Read | |||
| IR | 114doc 300115 / 0072h | VA MAX dmd | FLOAT32 | CDAB | VA | Read | |||
| IR | 116doc 300117 / 0074h | PF L1 min | FLOAT32 | CDAB | Read | ||||
| IR | 118doc 300119 / 0076h | PF L2 min | FLOAT32 | CDAB | Read | ||||
| IR | 120doc 300121 / 0078h | PF L3 min | FLOAT32 | CDAB | Read | ||||
| IR | 122doc 300123 / 007Ah | A L1 min | WM14 Advanced only. | FLOAT32 | CDAB | A | Read | ||
| IR | 124doc 300125 / 007Ch | A L2 min | WM14 Advanced only. | FLOAT32 | CDAB | A | Read | ||
| IR | 126doc 300127 / 007Eh | A L3 min | WM14 Advanced only. | FLOAT32 | CDAB | A | Read | ||
| IR | 128doc 300129 / 0080h | V L1 min | WM14 Advanced only. | FLOAT32 | CDAB | V | Read | ||
| IR | 130doc 300131 / 0082h | V L2 min | WM14 Advanced only. | FLOAT32 | CDAB | V | Read | ||
| IR | 132doc 300133 / 0084h | V L3 min | WM14 Advanced only. | FLOAT32 | CDAB | V | Read | ||
| IR | 134doc 300135 / 0086h | V L1 MAX | WM14 Advanced only. | FLOAT32 | CDAB | V | Read | ||
| IR | 136doc 300137 / 0088h | V L2 MAX | WM14 Advanced only. | FLOAT32 | CDAB | V | Read | ||
| IR | 138doc 300139 / 008Ah | V L3 MAX | WM14 Advanced only. | FLOAT32 | CDAB | V | Read | ||
| IR | 140doc 300141 / 008Ch | THD V1 | WM14 Advanced only; THD must be enabled (01A8h). | FLOAT32 | CDAB | % | Read | ||
| IR | 142doc 300143 / 008Eh | THD V2 | WM14 Advanced only; THD must be enabled (01A8h). | FLOAT32 | CDAB | % | Read | ||
| IR | 144doc 300145 / 0090h | THD V3 | WM14 Advanced only; THD must be enabled (01A8h). | FLOAT32 | CDAB | % | Read | ||
| IR | 146doc 300147 / 0092h | THD I1 | WM14 Advanced only; THD must be enabled (01A8h). | FLOAT32 | CDAB | % | Read | ||
| IR | 148doc 300149 / 0094h | THD I2 | WM14 Advanced only; THD must be enabled (01A8h). | FLOAT32 | CDAB | % | Read | ||
| IR | 150doc 300151 / 0096h | THD I3 | WM14 Advanced only; THD must be enabled (01A8h). | FLOAT32 | CDAB | % | Read | ||
| IR | 211doc 300212 / 00D3h | Carlo Gavazzi identification code | UINT16 | Read | 33 = CPT A AV5 3-phase; 34 = CPT A AV6 3-phase; 35 = CPT A AV5 1-phase; 36 = CPT A AV6 1-phase; 39 = WM14 A AV5 3-phase; 40 = WM14 A AV6 3-phase | ||||
| IR | 222doc 300223 / 00DEh | Firmware revision | Low byte = progressive revision number. | UINT16 | Read | ||||
| IR | 259doc 300260 / 0103h | Output 1 alarm | UINT16 | Read | 0 = Not in alarm; 1 = In alarm | ||||
| IR | 260doc 300261 / 0104h | Output 2 alarm | UINT16 | Read | 0 = Not in alarm; 1 = In alarm | ||||
| HR | 409doc 300410 / 0199h | Password | 0-999; out-of-range values are treated as 0. | UINT16 | Read/write | ||||
| HR | 410doc 300411 / 019Ah | Current transformer ratio | 1-60000. | UINT16 | Read/write | ||||
| HR | 411doc 300412 / 019Bh | Voltage transformer ratio | 1-60000, divided by 10 internally. | UINT16 | × 0.1 | Read/write | |||
| HR | 414doc 300415 / 019Eh | Power integration time | 1-30 min. | UINT16 | min | Read/write | |||
| HR | 415doc 300416 / 019Fh | Current integration time | 1-30 min. | UINT16 | min | Read/write | |||
| HR | 417doc 300418 / 01A1h | Modbus address | 1-255. | UINT16 | Read/write | ||||
| HR | 418doc 300419 / 01A2h | Baud rate | UINT16 | Read/write | 0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400 | ||||
| HR | 424doc 300417 / 01A8h | THD calculation | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 8430doc 608431 / 20EEh | Reset command | UINT16 | Write | 0 = Reset all variables (instantaneous, min, MAX, dmd, counters); 256 = Reset all demand values; 512 = Reset energy counters and hour counter; 768 = Reset total energy counters; 1024 = Reset partial energy counters; 1280 = Reset hour counters; 1536 = Reset MAX and min values |
Notes on this map
- Float word order: the protocol lists the frame bytes as bits 15-8, 7-0, 31-24, 23-16 of the IEEE 754 value, i.e. low word first (CDAB).
- Left out: the UINT32 energy counters and hour counter (0056h-005Fh). The word-order sentence covers only UINT16 and UINT64 integers, so the order of these 32-bit integers is not stated.
- Left out: filter settings, system type (its value list is garbled in the source), output control and digital output/alarm blocks, analogue output setup and virtual alarm words.
- Up to 12 registers per read on the RS485 port (28 on the CPT-DIN RS232 port).
- Reads use function 03 or 04; writes use function 06.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)
What Modbus registers does the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) have?
This map lists 84 registers: 75 input registers, 9 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Rows give a 6-digit Modicon number (3xxxxx) and the hex physical address; the hex address goes in the frame, so 300001 / 0000h is wire address 0. A few printed Modicon numbers do not match their hex address (0058h is printed 300099, 01A8h is printed 300417); the hex value is used.
What byte order does the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)?
Start with IR 0 V L1-N (V L1-N); IR 12 A L1 (A L1); IR 50 W system (W system); IR 56 PF system (PF system); IR 58 Frequency (Frequency); IR 211 Carlo Gavazzi identification code (Model code).
How do I enable Modbus control of the Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy)?
Needs the optional RS485 (S1) serial module; set the address (01A1h) and baud rate (01A2h) or use the front keys.
Where is the official Carlo Gavazzi WM14 Advanced / CPT-DIN Advanced power analyzer (legacy) Modbus documentation?
The source is WM14 Advanced / CPT-DIN Advanced Communication Protocol (Version 2 Revision 2), revision 2008-01-09, published free by Carlo Gavazzi at https://www.gavazziautomation.com/fileadmin/images/PIM/OTHERSTUFF/COMPRO/WM14%20A%20and%20CPT%20A%20CP%20v2r2%20ENG%200108.pdf.
More Carlo Gavazzi Modbus register maps
- Energy meter (DC)
Carlo Gavazzi DCM1 DC energy meter for EV chargers (Modbus RTU / TCP)
DCM1 300 A / 600 A, 1000 V DC meters (MID, Eichrecht and LNE variants) with RS485 and Ethernet, protocol version 1.11.
Also known as: DCM1A60V10L20S1PFA, DCM1A60V10L20S1PFB, DCM1A60V10L20S2DEB, DCM1A60V10L20S3DEB, DCM1A60V10L20S2DEBF, DCM1A60V10L20S3DEBF, DCM1A30V10L20S1PFA, DCM1A30V10L20S1PFB, DCM1A30V10L20S2DEB, DCM1A30V10L20S3DEB, DCM1A30V10L20S2DEBF, DCM1A30V10L20S3DEBF, DCM1A60V10L20S1ULB, DCM1A30V10L20S1ULB - Energy meter (DC)
Carlo Gavazzi DCT1 DC energy meter (Modbus RTU)
DCT1 300 A and 600 A / 1000 V DC meters, with and without signed data (S1/S2/S3), protocol version 1.1.
Also known as: DCT1A60V10LS1X, DCT1A60V10LS2EC, DCT1A60V10LS3EC, DCT1A30V10LS1X, DCT1A30V10LS2EC, DCT1A30V10LS3EC - Energy meter
Carlo Gavazzi EM100 / ET100 series (EM111, EM112, ET112)
Single-phase EM111, EM112 energy meters and ET112 bidirectional meter with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 14.
Also known as: EM111, EM112, ET112, EM110, EM111-DIN, EM112-DIN, ET112-DIN, EM111DINAV81XS1X, EM112DINAV01XS1X, ET112DINAV01XS1X - Energy meter (energy analyzer)
Carlo Gavazzi EM210 (AV versions)
EM210 three-phase energy analyzers, AV input versions with the RS485 Modbus RTU option, protocol version 4 revision 3 (newest variables need firmware A.5/A.6).
Also known as: EM210, EM210-72D, EM210 AV - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN (PFA, PFB and X models)
EM24-DIN three-phase energy analyzers, PFA/PFB (MID) and X models with the RS485 Modbus RTU port (IS option), protocol version 4 revision 0.
Also known as: EM24, EM24DIN, EM24DINAV93XISPFA, EM24DINAV93XISPFB, EM24DINAV93XISX, EM24DINAV53XISX, EM24DINAV23XISX, EM24 DIN AV9, EM24 DIN AV5 - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN Ethernet (E1)
EM24-DIN energy analyzers with the E1 Ethernet (RJ45) Modbus TCP port, AV2 and AV5 inputs, X/PFA/PFB, protocol version 0 revision 1.3 (FW 1.0).
Also known as: EM24 E1, EM24_E1, EM24DINAV23XE1X, EM24DINAV23XE1PFA, EM24DINAV23XE1PFB, EM24DINAV53XE1X, EM24DINAV53XE1PFA, EM24DINAV53XE1PFB - Energy meter
Carlo Gavazzi EM24-IS (SFA and SFB models)
EM24-DIN AV2/AV5 IS SFA and SFB versions (identification codes 1696-1699), protocol revision 2.0.
Also known as: EM24DINAV23XISSFA, EM24DINAV53XISSFA, EM24DINAV23XISSFB, EM24DINAV53XISSFB, EM24 SFA, EM24 SFB - Energy meter
Carlo Gavazzi EM270 / EM280 dual three-phase energy meters with TCD current sensors
EM270 X (firmware r.b0+), EM270 W (r.C0+) and EM280 (r.E0+) on RS485 Modbus RTU, per communication protocol version 5 revision 1 (2018-01-29).
Also known as: EM270, EM280, EM270 X, EM270 W, EM27072DMV53X2SX, EM28072DMV53X2SX - Energy meter
Carlo Gavazzi EM271 dual three-phase energy meter with TCD current sensors
EM271 (firmware r.d0+, PF values from r.d2) on RS485 Modbus RTU, per communication protocol version 1 revision 2 (2018-01-29).
Also known as: EM271, EM27172DMV53X2SX, EM27172DMV63X2SX - Energy meter
Carlo Gavazzi EM300 / ET300 series (EM330, EM340, ET330, ET340)
EM330, EM331, EM340, EM341 energy meters and ET330/ET340 bidirectional meters with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 17.
Also known as: EM330, EM340, ET330, ET340, EM331, EM341, EM330-DIN, EM340-DIN, ET340-DIN, EM340DINAV23XS1X, EM340DINAV23XS1PFA, EM340DINAV23XS1PFB - Energy meter
Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)
EM511 direct-connected single-phase DIN meters with RS485 and digital input (X, PFA, PFB, SFA versions), protocol rev. 1.8.
Also known as: EM511-IS, EM511DINAV81XS1X, EM511DINAV81XS1PFA, EM511DINAV81XS1PFB, EM511DINAV81XS1SFA - Energy meter
Carlo Gavazzi EM530 / EM540 three-phase energy meters (RS485 Modbus)
EM530 (CT-connected) and EM540 (direct-connected) with the S1 RS485 port, X and MID (PFA/PFB/PFC) versions, protocol document version 1.3.
Also known as: EM530, EM540, EM530DINAV53XS1X, EM530DINAV53XS1PFA, EM530DINAV53XS1PFB, EM530DINAV53XS1PFC, EM540DINAV23XS1X, EM540DINAV23XS1PFA, EM540DINAV23XS1PFB, EM540DINAV23XS1PFC, EM500 series - Energy meter
Carlo Gavazzi EM580 three-phase AC energy meter for EV chargers (Modbus RTU)
EM580-IS MID/Eichrecht AC meters (DEB, DET, DEA variants, 256/384-bit signatures), protocol version 1.11.
Also known as: EM580-IS, EM580DINAV23XS2DEB, EM580DINAV23XS3DEB, EM580DINAV23XS2DET, EM580DINAV23XS3DET, EM580DINAV23XS2DEA, EM580DINAV23XS3DEA - Power meter (power analyzer)
Carlo Gavazzi WM15 power analyzer
WM15-96 three-phase panel power analyzers with RS485 Modbus RTU (OS / OSPF / HOS versions), protocol version 1.2.
Also known as: WM15, WM15-96, WM1596AV53XOSX, WM1596AV53XOSPFB, WM1596AV53HOSX - Power meter (power analyzer)
Carlo Gavazzi WM20 / WM30 / WM40 power analyzers
WM20, WM30 and WM40 modular power analyzers with an RS485 (or Ethernet) Modbus module, protocol internal version rev. 4.0 (2018-03-28); WM30 = firmware letter X, WM40 = Y, WM20 = Z.
Also known as: WM20, WM30, WM40, WM20-96, WM30-96, WM40-96 - Power meter (power analyzer)
Carlo Gavazzi WM50 power analyzer with TCD branch channels
WM50 base unit (firmware X0, i.e. all A and B versions) with an MC485232 or MCETH communication module, plus TCD branch channels, per communication protocol user version rev. 1.0.0 (2017-09-27).
Also known as: WM50, WM50AV5, WM50-96, WM50 AV5
Other power & energy meters register maps
- Power meter
Circutor CVM-C5
Circutor CVM-C5 panel power analyzer, RS-485 Modbus RTU versions (ITF-485, MC-485, mV-485), manual M026B01-03.
Also known as: CVM-C5-ITF-485, CVM-C5-MC-485, CVM-C5-mV-485 - Power meter (power quality analyzer)
E-Mon (Honeywell) PowerSmart+ Advanced power quality meter
Honeywell E-Mon PowerSmart+ Advanced power quality meter, per Modbus reference guide BG0545 Rev. A1 (Jul 2013).
Also known as: E-Mon PowerSmart+ Advanced, PowerSmart Plus Advanced, Honeywell PowerSmart+, BG0545 - Energy meter
Eastron SDM630-Modbus
Eastron SDM630Modbus three-phase DIN-rail meter, protocol implementation V1.8 as published by Eastron Europe.
Also known as: SDM630Modbus, SDM630 Modbus V2, SDM630-Modbus V2 - Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 300 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 300 with the Modbus RS485 communication option, parameter description GP01131D/06/EN/02.24-00.
Also known as: Prosonic Flow G 300 - Power meter (power quality meter)
GE Multilin Multilin PQMII power quality meter
Multilin PQMII per instruction manual GEK-113532 (communications guide chapter).
Also known as: PQM II, GE Multilin PQMII, PQM2 - Power meter (DIN-rail)
IME Nemo D4-Le multifunction meter (MFD44)
IME Nemo D4-Le DIN-rail meter MFD44 with RS-485, per protocol PR129 (software 2.05).
Also known as: MFD44, Nemo D4-Le
All power & energy meters Modbus register maps →
Source: WM14 Advanced / CPT-DIN Advanced Communication Protocol · Version 2 Revision 2 · rev. 2008-01-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.