Power meter (power quality meter) · Modbus register map
GE Multilin Multilin PQMII power quality meter Modbus register map
Updated 17 November 2026
The Multilin PQMII is a panel-mount power quality meter, now documented by GE Vernova. It speaks Modbus RTU on its RS-485 ports, with all data in one hexadecimal memory map. This map covers currents, voltages, power, power factor, energy, demand, frequency, THD and the command registers.
This page lists 59 Modbus registers for the GE Multilin Multilin PQMII power quality meter — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from GE Multilin’s own free documentation (linked below) and checked against it.
- Manufacturer
- GE Multilin
- Model
- Multilin PQMII power quality meter
- Equipment type
- Power meter (power quality meter)
- Registers
- 59 (2 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Software revision 2.2x
- Also known as
- PQM II, GE Multilin PQMII, PQM2
Integration notes: GE Multilin Multilin PQMII power quality meter
Read 0240h-0245h for currents, 0280h-0290h for voltages (32-bit), 02F0h-030Bh for power and PF, 03D0h-03D9h for energy and 0440h for frequency. Use the command registers to clear energy or min/max values.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 576 | Phase A current | UINT16 | Phase A current | Read |
| IR 648 | Voltage Vab | UINT32 ABCD | Voltage Vab | Read |
| IR 752 | 3-phase real power | INT32 ABCD | 3-phase real power | Read |
| IR 758 | 3-phase power factor | INT16 | 3-phase power factor | Read |
| IR 1088 | Frequency | UINT16 | Frequency | Read |
| IR 976 | 3-phase positive real energy | UINT32 ABCD | Imported real energy | Read |
Enable Modbus control & writes
Set the slave address, baud rate and parity in the PQMII setpoints for the COM port in use; Modbus RTU is the native protocol.
Byte order & addressing
- Hex addresses are wire addresses.
- 32-bit values are high register first; signed values (F4) are two's complement across both registers.
Network setup
- Address 0 is broadcast (setpoint stores and commands only); give each meter its own address.
Watch out for
- Voltages are whole volts in 32-bit registers; power is in 0.01 kW units, not watts.
GE Multilin Multilin PQMII power quality meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 0000 | Product device code | Reads 73 for a PQMII. | UINT16 | Read | ||||
| IR | 540doc 021C | General status | Status flags (format F109 in the manual). | UINT16 | Read | ||||
| IR | 576doc 0240 | Phase A current | UINT16 | A | Read | ||||
| IR | 577doc 0241 | Phase B current | UINT16 | A | Read | ||||
| IR | 578doc 0242 | Phase C current | UINT16 | A | Read | ||||
| IR | 579doc 0243 | Average current | UINT16 | A | Read | ||||
| IR | 580doc 0244 | Neutral current | UINT16 | A | Read | ||||
| IR | 581doc 0245 | Current unbalance | UINT16 | × 0.1 | % | Read | |||
| IR | 640doc 0280-0281 | Voltage Van | High register first. | UINT32 | ABCD | V | Read | ||
| IR | 642doc 0282-0283 | Voltage Vbn | High register first. | UINT32 | ABCD | V | Read | ||
| IR | 644doc 0284-0285 | Voltage Vcn | High register first. | UINT32 | ABCD | V | Read | ||
| IR | 646doc 0286-0287 | Average phase voltage | High register first. | UINT32 | ABCD | V | Read | ||
| IR | 648doc 0288-0289 | Voltage Vab | High register first. | UINT32 | ABCD | V | Read | ||
| IR | 650doc 028A-028B | Voltage Vbc | High register first. | UINT32 | ABCD | V | Read | ||
| IR | 652doc 028C-028D | Voltage Vca | High register first. | UINT32 | ABCD | V | Read | ||
| IR | 654doc 028E-028F | Average line voltage | High register first. | UINT32 | ABCD | V | Read | ||
| IR | 656doc 0290 | Voltage unbalance | UINT16 | × 0.1 | % | Read | |||
| IR | 752doc 02F0-02F1 | 3-phase real power | Signed, high register first. | INT32 | ABCD | × 0.01 | kW | Read | |
| IR | 754doc 02F2-02F3 | 3-phase reactive power | Signed, high register first. | INT32 | ABCD | × 0.01 | kvar | Read | |
| IR | 756doc 02F4-02F5 | 3-phase apparent power | UINT32 | ABCD | × 0.01 | kVA | Read | ||
| IR | 758doc 02F6 | 3-phase power factor | INT16 | × 0.01 | Read | ||||
| IR | 759doc 02F7-02F8 | Phase A real power | INT32 | ABCD | × 0.01 | kW | Read | ||
| IR | 761doc 02F9-02FA | Phase A reactive power | INT32 | ABCD | × 0.01 | kvar | Read | ||
| IR | 763doc 02FB-02FC | Phase A apparent power | UINT32 | ABCD | × 0.01 | kVA | Read | ||
| IR | 765doc 02FD | Phase A power factor | INT16 | × 0.01 | Read | ||||
| IR | 766doc 02FE-02FF | Phase B real power | INT32 | ABCD | × 0.01 | kW | Read | ||
| IR | 768doc 0300-0301 | Phase B reactive power | INT32 | ABCD | × 0.01 | kvar | Read | ||
| IR | 770doc 0302-0303 | Phase B apparent power | UINT32 | ABCD | × 0.01 | kVA | Read | ||
| IR | 772doc 0304 | Phase B power factor | INT16 | × 0.01 | Read | ||||
| IR | 773doc 0305-0306 | Phase C real power | INT32 | ABCD | × 0.01 | kW | Read | ||
| IR | 775doc 0307-0308 | Phase C reactive power | INT32 | ABCD | × 0.01 | kvar | Read | ||
| IR | 777doc 0309-030A | Phase C apparent power | UINT32 | ABCD | × 0.01 | kVA | Read | ||
| IR | 779doc 030B | Phase C power factor | INT16 | × 0.01 | Read | ||||
| IR | 976doc 03D0-03D1 | 3-phase positive real energy | Imported real energy. | UINT32 | ABCD | kWh | Read | ||
| IR | 978doc 03D2-03D3 | 3-phase negative real energy | Exported real energy. | UINT32 | ABCD | kWh | Read | ||
| IR | 980doc 03D4-03D5 | 3-phase positive reactive energy | UINT32 | ABCD | kvarh | Read | |||
| IR | 982doc 03D6-03D7 | 3-phase negative reactive energy | UINT32 | ABCD | kvarh | Read | |||
| IR | 984doc 03D8-03D9 | 3-phase apparent energy | UINT32 | ABCD | kVAh | Read | |||
| IR | 986doc 03DA-03DB | Energy used in last 24 h | UINT32 | ABCD | kWh | Read | |||
| IR | 1024doc 0400 | Phase A current demand | UINT16 | A | Read | ||||
| IR | 1025doc 0401 | Phase B current demand | UINT16 | A | Read | ||||
| IR | 1026doc 0402 | Phase C current demand | UINT16 | A | Read | ||||
| IR | 1027doc 0403 | Neutral current demand | UINT16 | A | Read | ||||
| IR | 1028doc 0404-0405 | 3-phase real power demand | INT32 | ABCD | × 0.01 | kW | Read | ||
| IR | 1030doc 0406-0407 | 3-phase reactive power demand | INT32 | ABCD | × 0.01 | kvar | Read | ||
| IR | 1032doc 0408-0409 | 3-phase apparent power demand | UINT32 | ABCD | × 0.01 | kVA | Read | ||
| IR | 1088doc 0440 | Frequency | UINT16 | × 0.01 | Hz | Read | |||
| IR | 1089doc 0441 | Frequency minimum | UINT16 | × 0.01 | Hz | Read | |||
| IR | 1090doc 0442 | Frequency maximum | UINT16 | × 0.01 | Hz | Read | |||
| IR | 1144doc 0478 | Phase A current THD | UINT16 | × 0.1 | % | Read | |||
| IR | 1146doc 047A | Phase C current THD | UINT16 | × 0.1 | % | Read | |||
| IR | 1147doc 047B | Neutral current THD | UINT16 | × 0.1 | % | Read | |||
| IR | 1148doc 047C | Voltage Van THD | UINT16 | × 0.1 | % | Read | |||
| IR | 1149doc 047D | Voltage Vbn THD | UINT16 | × 0.1 | % | Read | |||
| IR | 1150doc 047E | Voltage Vcn THD | UINT16 | × 0.1 | % | Read | |||
| IR | 1151doc 047F | Voltage Vab THD | UINT16 | × 0.1 | % | Read | |||
| IR | 1152doc 0480 | Voltage Vbc THD | UINT16 | × 0.1 | % | Read | |||
| HR | 128doc 0080 | Command function code | Write 5 before the operation code (printed range 5). | UINT16 | Read/write | ||||
| HR | 129doc 0081 | Command operation code | Command to run (format F7). | UINT16 | Read/write | 1 = Reset; 2 = Alarm relay on; 3 = Alarm relay off; 10 = Set clock time; 11 = Set clock date; 14 = Clear energy values; 15 = Clear max demand values; 16 = Clear min/max current; 17 = Clear min/max voltage; 18 = Clear min/max power; 19 = Clear max THD; 20 = Clear switch input pulse count; 31 = Clear event record; 34 = Clear all demand; 35 = Clear min/max frequency |
Notes on this map
- Word order: the manual says long integers occupy two registers, high-order register first, and its worked example (02F0 = 004Fh, 02F1 = 35D1h -> 51911.21 kW) confirms ABCD.
- Data formats: F1 unsigned 16-bit, F2 signed 16-bit, F3 unsigned 32-bit, F4 signed 32-bit. Scales are copied from the Units and Scale column (0.01 x kW, 0.1 x %, 0.01 x Hz).
- Up to 125 registers can be read in one request; up to 60 written.
- Phase B current THD (0479h) is left out because its units/scale cell is blank in the table. Min/max time stamps, tariff energies/costs, per-harmonic data and setpoints are left out.
- The user-definable area (index 0180h-01F7h, data 0100h-0177h) can gather scattered registers into one block.
- Communication defaults are not listed: the RS-485 setpoint rows (e.g. baud rate at 1018h) give codes whose meaning is not readable in this copy of the table.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the GE Multilin Multilin PQMII power quality meter
What Modbus registers does the GE Multilin Multilin PQMII power quality meter have?
This map lists 59 registers: 57 input registers, 2 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the GE Multilin Multilin PQMII power quality meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The memory map prints addresses in hex, and the manual's examples send that hex value on the wire (e.g. a read of 3 registers starting at 006B). Actual values are input registers, setpoints and commands holding registers; function 03 and 04 both read either area.
What byte order does the GE Multilin Multilin PQMII power quality meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the GE Multilin Multilin PQMII power quality meter?
Start with IR 576 Phase A current (Phase A current); IR 648 Voltage Vab (Voltage Vab); IR 752 3-phase real power (3-phase real power); IR 758 3-phase power factor (3-phase power factor); IR 1088 Frequency (Frequency); IR 976 3-phase positive real energy (Imported real energy).
How do I enable Modbus control of the GE Multilin Multilin PQMII power quality meter?
Set the slave address, baud rate and parity in the PQMII setpoints for the COM port in use; Modbus RTU is the native protocol.
Where is the official GE Multilin Multilin PQMII power quality meter Modbus documentation?
The source is PQMII Power Quality Meter Communications Guide (GEK-113532 (manual P/N 1601-9090-A1)), published free by GE Multilin at https://www.gevernova.com/grid-solutions/sites/default/files/resources/products/manuals/pqmii/gek-113532-GEV.pdf.
Other power & energy meters register maps
- Power meter (DIN-rail)
IME Nemo D4-Le multifunction meter (MFD44)
IME Nemo D4-Le DIN-rail meter MFD44 with RS-485, per protocol PR129 (software 2.05).
Also known as: MFD44, Nemo D4-Le - Energy meter
inepro Metering PRO3 three-phase energy meter (2026 PRO line)
PRO3-Mod (art. 1301) and PRO3-Mod-Ba (art. 1302, with RTC tariffs) from the 2026 PRO3 user manual version 1.3; the PRO3-S has no Modbus.
Also known as: PRO3-Mod, PRO3-Mod-Ba, PRO3 1U AC 100A Mod T MID, PRO3 1U AC 100A Mod T Ba MID, 1301, 1302 - Power meter (power quality analyser)
Janitza UMG 511 power quality analyser (Modbus RTU)
UMG 511 per Modbus address list 1.037.021.9.g (05/2021).
Also known as: UMG511, UMG 511, Janitza UMG511 - Power meter (power analyser)
Janitza UMG 96RM power analyser (basic device, RS-485 Modbus RTU)
UMG 96RM basic device from firmware release 1.14, per address list 1.040.034.t; the same list covers the shared registers of the -P, -CBM and -PN extensions. Other UMG 96RM variants (e.g. the Ethernet -E / -EL) are not covered by this list.
Also known as: UMG96RM, UMG 96 RM, UMG 96RM-P, UMG 96RM-CBM, UMG 96RM-PN, Janitza UMG96RM - Sensor (ultrasonic flowmeter)
KROHNE UFC 400 ultrasonic flow converter (Modbus RTU)
UFC 400 signal converter with Modbus, electronic revision ER 2.2.0_, Modbus version 2.1.0_, supplementary instructions 4002744801 R01 (05/2013).
Also known as: UFC400, KROHNE UFC 400, UFC 400 Modbus - Power meter (panel network parameter meter)
Lumel ND20LITE network parameter meter
Lumel ND20LITE 96x96 panel meter with RS-485 Modbus RTU (not the ND20 or ND20CT, which have their own maps).
Also known as: ND20LITE
All power & energy meters Modbus register maps →
Source: PQMII Power Quality Meter Communications Guide · GEK-113532 (manual P/N 1601-9090-A1). Register numbers, types, scaling and units are reproduced as published; descriptions are our own.