Power meter (power quality meter) · Modbus register map

GE Multilin Multilin PQMII power quality meter Modbus register map

Updated 17 November 2026

Short answer

The Multilin PQMII is a panel-mount power quality meter, now documented by GE Vernova. It speaks Modbus RTU on its RS-485 ports, with all data in one hexadecimal memory map. This map covers currents, voltages, power, power factor, energy, demand, frequency, THD and the command registers.

This page lists 59 Modbus registers for the GE Multilin Multilin PQMII power quality meter — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from GE Multilin’s own free documentation (linked below) and checked against it.

Manufacturer
GE Multilin
Model
Multilin PQMII power quality meter
Equipment type
Power meter (power quality meter)
Registers
59 (2 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Firmware
Software revision 2.2x
Also known as
PQM II, GE Multilin PQMII, PQM2
Source document
PQMII Power Quality Meter Communications Guide · GEK-113532 (manual P/N 1601-9090-A1)
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: GE Multilin Multilin PQMII power quality meter

Integration in brief

Read 0240h-0245h for currents, 0280h-0290h for voltages (32-bit), 02F0h-030Bh for power and PF, 03D0h-03D9h for energy and 0440h for frequency. Use the command registers to clear energy or min/max values.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 576Phase A currentUINT16Phase A currentRead
IR 648Voltage VabUINT32 ABCDVoltage VabRead
IR 7523-phase real powerINT32 ABCD3-phase real powerRead
IR 7583-phase power factorINT163-phase power factorRead
IR 1088FrequencyUINT16FrequencyRead
IR 9763-phase positive real energyUINT32 ABCDImported real energyRead

Enable Modbus control & writes

Set the slave address, baud rate and parity in the PQMII setpoints for the COM port in use; Modbus RTU is the native protocol.

Byte order & addressing

Network setup

Watch out for

GE Multilin Multilin PQMII power quality meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

59 of 59 shown
GE Multilin Multilin PQMII power quality meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 0000Product device codeReads 73 for a PQMII.UINT16Read
IR540doc 021CGeneral statusStatus flags (format F109 in the manual).UINT16Read
IR576doc 0240Phase A currentUINT16ARead
IR577doc 0241Phase B currentUINT16ARead
IR578doc 0242Phase C currentUINT16ARead
IR579doc 0243Average currentUINT16ARead
IR580doc 0244Neutral currentUINT16ARead
IR581doc 0245Current unbalanceUINT16× 0.1%Read
IR640doc 0280-0281Voltage VanHigh register first.UINT32ABCDVRead
IR642doc 0282-0283Voltage VbnHigh register first.UINT32ABCDVRead
IR644doc 0284-0285Voltage VcnHigh register first.UINT32ABCDVRead
IR646doc 0286-0287Average phase voltageHigh register first.UINT32ABCDVRead
IR648doc 0288-0289Voltage VabHigh register first.UINT32ABCDVRead
IR650doc 028A-028BVoltage VbcHigh register first.UINT32ABCDVRead
IR652doc 028C-028DVoltage VcaHigh register first.UINT32ABCDVRead
IR654doc 028E-028FAverage line voltageHigh register first.UINT32ABCDVRead
IR656doc 0290Voltage unbalanceUINT16× 0.1%Read
IR752doc 02F0-02F13-phase real powerSigned, high register first.INT32ABCD× 0.01kWRead
IR754doc 02F2-02F33-phase reactive powerSigned, high register first.INT32ABCD× 0.01kvarRead
IR756doc 02F4-02F53-phase apparent powerUINT32ABCD× 0.01kVARead
IR758doc 02F63-phase power factorINT16× 0.01Read
IR759doc 02F7-02F8Phase A real powerINT32ABCD× 0.01kWRead
IR761doc 02F9-02FAPhase A reactive powerINT32ABCD× 0.01kvarRead
IR763doc 02FB-02FCPhase A apparent powerUINT32ABCD× 0.01kVARead
IR765doc 02FDPhase A power factorINT16× 0.01Read
IR766doc 02FE-02FFPhase B real powerINT32ABCD× 0.01kWRead
IR768doc 0300-0301Phase B reactive powerINT32ABCD× 0.01kvarRead
IR770doc 0302-0303Phase B apparent powerUINT32ABCD× 0.01kVARead
IR772doc 0304Phase B power factorINT16× 0.01Read
IR773doc 0305-0306Phase C real powerINT32ABCD× 0.01kWRead
IR775doc 0307-0308Phase C reactive powerINT32ABCD× 0.01kvarRead
IR777doc 0309-030APhase C apparent powerUINT32ABCD× 0.01kVARead
IR779doc 030BPhase C power factorINT16× 0.01Read
IR976doc 03D0-03D13-phase positive real energyImported real energy.UINT32ABCDkWhRead
IR978doc 03D2-03D33-phase negative real energyExported real energy.UINT32ABCDkWhRead
IR980doc 03D4-03D53-phase positive reactive energyUINT32ABCDkvarhRead
IR982doc 03D6-03D73-phase negative reactive energyUINT32ABCDkvarhRead
IR984doc 03D8-03D93-phase apparent energyUINT32ABCDkVAhRead
IR986doc 03DA-03DBEnergy used in last 24 hUINT32ABCDkWhRead
IR1024doc 0400Phase A current demandUINT16ARead
IR1025doc 0401Phase B current demandUINT16ARead
IR1026doc 0402Phase C current demandUINT16ARead
IR1027doc 0403Neutral current demandUINT16ARead
IR1028doc 0404-04053-phase real power demandINT32ABCD× 0.01kWRead
IR1030doc 0406-04073-phase reactive power demandINT32ABCD× 0.01kvarRead
IR1032doc 0408-04093-phase apparent power demandUINT32ABCD× 0.01kVARead
IR1088doc 0440FrequencyUINT16× 0.01HzRead
IR1089doc 0441Frequency minimumUINT16× 0.01HzRead
IR1090doc 0442Frequency maximumUINT16× 0.01HzRead
IR1144doc 0478Phase A current THDUINT16× 0.1%Read
IR1146doc 047APhase C current THDUINT16× 0.1%Read
IR1147doc 047BNeutral current THDUINT16× 0.1%Read
IR1148doc 047CVoltage Van THDUINT16× 0.1%Read
IR1149doc 047DVoltage Vbn THDUINT16× 0.1%Read
IR1150doc 047EVoltage Vcn THDUINT16× 0.1%Read
IR1151doc 047FVoltage Vab THDUINT16× 0.1%Read
IR1152doc 0480Voltage Vbc THDUINT16× 0.1%Read
HR128doc 0080Command function codeWrite 5 before the operation code (printed range 5).UINT16Read/write
HR129doc 0081Command operation codeCommand to run (format F7).UINT16Read/write1 = Reset; 2 = Alarm relay on; 3 = Alarm relay off; 10 = Set clock time; 11 = Set clock date; 14 = Clear energy values; 15 = Clear max demand values; 16 = Clear min/max current; 17 = Clear min/max voltage; 18 = Clear min/max power; 19 = Clear max THD; 20 = Clear switch input pulse count; 31 = Clear event record; 34 = Clear all demand; 35 = Clear min/max frequency

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the GE Multilin Multilin PQMII power quality meter

What Modbus registers does the GE Multilin Multilin PQMII power quality meter have?

This map lists 59 registers: 57 input registers, 2 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the GE Multilin Multilin PQMII power quality meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The memory map prints addresses in hex, and the manual's examples send that hex value on the wire (e.g. a read of 3 registers starting at 006B). Actual values are input registers, setpoints and commands holding registers; function 03 and 04 both read either area.

What byte order does the GE Multilin Multilin PQMII power quality meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the GE Multilin Multilin PQMII power quality meter?

Start with IR 576 Phase A current (Phase A current); IR 648 Voltage Vab (Voltage Vab); IR 752 3-phase real power (3-phase real power); IR 758 3-phase power factor (3-phase power factor); IR 1088 Frequency (Frequency); IR 976 3-phase positive real energy (Imported real energy).

How do I enable Modbus control of the GE Multilin Multilin PQMII power quality meter?

Set the slave address, baud rate and parity in the PQMII setpoints for the COM port in use; Modbus RTU is the native protocol.

Where is the official GE Multilin Multilin PQMII power quality meter Modbus documentation?

The source is PQMII Power Quality Meter Communications Guide (GEK-113532 (manual P/N 1601-9090-A1)), published free by GE Multilin at https://www.gevernova.com/grid-solutions/sites/default/files/resources/products/manuals/pqmii/gek-113532-GEV.pdf.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: PQMII Power Quality Meter Communications Guide · GEK-113532 (manual P/N 1601-9090-A1). Register numbers, types, scaling and units are reproduced as published; descriptions are our own.