- ND20LITE network parameter meter
Power meter (panel network parameter meter) · Modbus register map
Lumel ND20LITE network parameter meter Modbus register map
Updated 17 November 2026
The ND20LITE is a 96x96 panel meter for 3- and 1-phase networks with an RS-485 Modbus RTU port. Measured values are floats offered in several register areas; this map uses the 7000 area (two registers per value, high word first) for per-phase and total values, THD and energies, plus the 4000 area for comms settings, 32-bit energy counters and the status word.
This page lists 69 Modbus registers for the Lumel ND20LITE network parameter meter — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lumel’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lumel
- Model
- ND20LITE network parameter meter
- Equipment type
- Power meter (panel network parameter meter)
- Registers
- 69 (4 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- ND20LITE
- Source document
- ND20LITE Meter of network parameters - User's manual
Integration notes: Lumel ND20LITE network parameter meter
Read holding registers (function 03 or 04) from 7000 for per-phase values, 7042-7064 for 3-phase totals and frequency, and 7100-7118 or 4038-4047 for energy. Floats are high word first in the 7000 area.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 7000 | Voltage of phase L1 | FLOAT32 ABCD | Voltage L1 | Read |
| HR 7002 | Current in phase L1 | FLOAT32 ABCD | Current L1 | Read |
| HR 7046 | 3-phase active power (P1+P2+P3) | FLOAT32 ABCD | 3-phase active power | Read |
| HR 7052 | Mean power factor (PF) | FLOAT32 ABCD | Mean power factor | Read |
| HR 7056 | Frequency | FLOAT32 ABCD | Frequency | Read |
| HR 4038 | Imported active energy (counter) | UINT32 ABCD | Imported active energy counter | Read |
| HR 4050 | Status register | BITMAP16 | Status bits | Read |
Enable Modbus control & writes
Modbus RTU is always on; set address, mode and baud from the menu or registers 4030-4032, then write 1 to 4033.
Byte order & addressing
- The 6000 area is low word first and the 7000 area high word first.
- At most 41 32-bit or 82 16-bit registers per request.
- Powers are in W, var and VA.
Network setup
- Factory settings: address 1, 9600 baud, RTU 8N2.
- Maximum response time is 600 ms.
Watch out for
- ND20, ND20CT and ND20LITE use different register maps.
Lumel ND20LITE network parameter meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 4030 | Modbus address | UINT16 | Read/write | |||||
| HR | 4031 | Transmission mode | UINT16 | Read/write | 0 = 8N2; 1 = 8E1; 2 = 8O1; 3 = 8N1 | ||||
| HR | 4032 | Baud rate | UINT16 | Read/write | 0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400 | ||||
| HR | 4033 | Apply transmission settings | Write 1 to make new address/mode/baud take effect. | UINT16 | Read/write | ||||
| HR | 4038doc 4038-4039 | Imported active energy (counter) | High register x 65536 + low register, in 0.1 units. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 4040doc 4040-4041 | Exported active energy (counter) | High register x 65536 + low register, in 0.1 units. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 4042doc 4042-4043 | Reactive inductive energy (counter) | High register x 65536 + low register, in 0.1 units. | UINT32 | ABCD | × 0.1 | kvarh | Read | |
| HR | 4044doc 4044-4045 | Reactive capacitive energy (counter) | High register x 65536 + low register, in 0.1 units. | UINT32 | ABCD | × 0.1 | kvarh | Read | |
| HR | 4046doc 4046-4047 | Apparent energy (counter) | High register x 65536 + low register, in 0.1 units. | UINT32 | ABCD | × 0.1 | kVAh | Read | |
| HR | 4050 | Status register | BITMAP16 | Read | bit 0 = Relay output on; bit 2 = Voltage L1 too low; bit 3 = Voltage L2 too low; bit 4 = Voltage L3 too low; bit 5 = Voltage too low for frequency measurement; bit 6 = Frequency outside THD calculation range; bit 7 = Averaging interval not yet elapsed; bit 10 = Current range 5 A (0 = 1 A); bit 11 = Phase sequence error; bit 12 = Energy value error; bit 13 = Parameter value error; bit 14 = No or bad calibration; bit 15 = Non-volatile memory damaged | ||||
| HR | 4053 | Program version | UINT16 | × 0.01 | Read | ||||
| HR | 7000doc 6000/7000 | Voltage of phase L1 | FLOAT32 | ABCD | V | Read | |||
| HR | 7002doc 6002/7002 | Current in phase L1 | FLOAT32 | ABCD | A | Read | |||
| HR | 7004doc 6004/7004 | Active power of phase L1 | FLOAT32 | ABCD | W | Read | |||
| HR | 7006doc 6006/7006 | Reactive power of phase L1 | FLOAT32 | ABCD | var | Read | |||
| HR | 7008doc 6008/7008 | Apparent power of phase L1 | FLOAT32 | ABCD | VA | Read | |||
| HR | 7010doc 6010/7010 | Power factor (PF) of phase L1 | FLOAT32 | ABCD | Read | ||||
| HR | 7012doc 6012/7012 | Tg phi factor L1 | FLOAT32 | ABCD | Read | ||||
| HR | 7014doc 6014/7014 | Voltage of phase L2 | FLOAT32 | ABCD | V | Read | |||
| HR | 7016doc 6016/7016 | Current in phase L2 | FLOAT32 | ABCD | A | Read | |||
| HR | 7018doc 6018/7018 | Active power of phase L2 | FLOAT32 | ABCD | W | Read | |||
| HR | 7020doc 6020/7020 | Reactive power of phase L2 | FLOAT32 | ABCD | var | Read | |||
| HR | 7022doc 6022/7022 | Apparent power of phase L2 | FLOAT32 | ABCD | VA | Read | |||
| HR | 7024doc 6024/7024 | Power factor (PF) of phase L2 | FLOAT32 | ABCD | Read | ||||
| HR | 7026doc 6026/7026 | Tg phi factor L2 | FLOAT32 | ABCD | Read | ||||
| HR | 7028doc 6028/7028 | Voltage of phase L3 | FLOAT32 | ABCD | V | Read | |||
| HR | 7030doc 6030/7030 | Current in phase L3 | FLOAT32 | ABCD | A | Read | |||
| HR | 7032doc 6032/7032 | Active power of phase L3 | FLOAT32 | ABCD | W | Read | |||
| HR | 7034doc 6034/7034 | Reactive power of phase L3 | FLOAT32 | ABCD | var | Read | |||
| HR | 7036doc 6036/7036 | Apparent power of phase L3 | FLOAT32 | ABCD | VA | Read | |||
| HR | 7038doc 6038/7038 | Power factor (PF) of phase L3 | FLOAT32 | ABCD | Read | ||||
| HR | 7040doc 6040/7040 | Tg phi factor L3 | FLOAT32 | ABCD | Read | ||||
| HR | 7042doc 6042/7042 | Mean 3-phase voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 7044doc 6044/7044 | Mean 3-phase current | FLOAT32 | ABCD | A | Read | |||
| HR | 7046doc 6046/7046 | 3-phase active power (P1+P2+P3) | FLOAT32 | ABCD | W | Read | |||
| HR | 7048doc 6048/7048 | 3-phase reactive power (Q1+Q2+Q3) | FLOAT32 | ABCD | var | Read | |||
| HR | 7050doc 6050/7050 | 3-phase apparent power (S1+S2+S3) | FLOAT32 | ABCD | VA | Read | |||
| HR | 7052doc 6052/7052 | Mean power factor (PF) | FLOAT32 | ABCD | Read | ||||
| HR | 7056doc 6056/7056 | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 7058doc 6058/7058 | Phase-to-phase voltage L1-2 | FLOAT32 | ABCD | V | Read | |||
| HR | 7060doc 6060/7060 | Phase-to-phase voltage L2-3 | FLOAT32 | ABCD | V | Read | |||
| HR | 7062doc 6062/7062 | Phase-to-phase voltage L3-1 | FLOAT32 | ABCD | V | Read | |||
| HR | 7064doc 6064/7064 | Mean phase-to-phase voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 7066doc 6066/7066 | 3-phase 15/30/60-minute active power (P1+P2+P3) | FLOAT32 | ABCD | W | Read | |||
| HR | 7068doc 6068/7068 | THD U1 | FLOAT32 | ABCD | % | Read | |||
| HR | 7070doc 6070/7070 | THD U2 | FLOAT32 | ABCD | % | Read | |||
| HR | 7072doc 6072/7072 | THD U3 | FLOAT32 | ABCD | % | Read | |||
| HR | 7074doc 6074/7074 | THD U mean | FLOAT32 | ABCD | % | Read | |||
| HR | 7076doc 6076/7076 | THD I1 | FLOAT32 | ABCD | % | Read | |||
| HR | 7078doc 6078/7078 | THD I2 | FLOAT32 | ABCD | % | Read | |||
| HR | 7080doc 6080/7080 | THD I3 | FLOAT32 | ABCD | % | Read | |||
| HR | 7082doc 6082/7082 | Cosinus of angle between U1 and I1 | FLOAT32 | ABCD | Read | ||||
| HR | 7084doc 6084/7084 | Cosinus of angle between U2 and I2 | FLOAT32 | ABCD | Read | ||||
| HR | 7088doc 6088/7088 | Cosinus of angle between U3 and I3 | FLOAT32 | ABCD | Read | ||||
| HR | 7090doc 6090/7090 | 3-phase mean cosinus | FLOAT32 | ABCD | Read | ||||
| HR | 7092doc 6092/7092 | Angle between U1 and I1 | FLOAT32 | ABCD | ° | Read | |||
| HR | 7094doc 6094/7094 | Angle between U2 and I2 | FLOAT32 | ABCD | ° | Read | |||
| HR | 7096doc 6096/7096 | Angle between U3 and I3 | FLOAT32 | ABCD | ° | Read | |||
| HR | 7098doc 6098/7098 | Neutral current (calculated from vectors) | FLOAT32 | ABCD | A | Read | |||
| HR | 7100doc 6100/7100 | Imported active energy overflows | Counts 100 MWh (100 Mvarh/MVAh) roll-overs of the next register. | FLOAT32 | ABCD | 100 MWh | Read | ||
| HR | 7102doc 6102/7102 | Imported active energy | Counter up to 99999.9; add 100000 x the overflow register. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 7104doc 6104/7104 | Exported active energy overflows | Counts 100 MWh (100 Mvarh/MVAh) roll-overs of the next register. | FLOAT32 | ABCD | 100 MWh | Read | ||
| HR | 7106doc 6106/7106 | Exported active energy | Counter up to 99999.9; add 100000 x the overflow register. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 7108doc 6108/7108 | Reactive inductive energy overflows | Counts 100 MWh (100 Mvarh/MVAh) roll-overs of the next register. | FLOAT32 | ABCD | 100 Mvarh | Read | ||
| HR | 7110doc 6110/7110 | Reactive inductive energy | Counter up to 99999.9; add 100000 x the overflow register. | FLOAT32 | ABCD | kvarh | Read | ||
| HR | 7112doc 6112/7112 | Reactive capacitive energy overflows | Counts 100 MWh (100 Mvarh/MVAh) roll-overs of the next register. | FLOAT32 | ABCD | 100 Mvarh | Read | ||
| HR | 7114doc 6114/7114 | Reactive capacitive energy | Counter up to 99999.9; add 100000 x the overflow register. | FLOAT32 | ABCD | kvarh | Read | ||
| HR | 7116doc 6116/7116 | Apparent energy overflows | Counts 100 MWh (100 Mvarh/MVAh) roll-overs of the next register. | FLOAT32 | ABCD | 100 MVAh | Read | ||
| HR | 7118doc 6118/7118 | Apparent energy | Counter up to 99999.9; add 100000 x the overflow register. | FLOAT32 | ABCD | kVAh | Read |
Notes on this map
- Byte order: the area table gives 7000-7319 as bytes 3-2-1-0 and 6000-6319 as 1-0-3-2; example 2 returns 41 20 00 00 (10.0) from 7000 and example 3 returns 00 00 41 20 from 6000, so the 7000 area is high word first (ABCD).
- Energy counters 4038-4047 follow the manual's formula (high x 65536 + low) / 10.
- Left out: the min/max area from 7140, 7054 (labelled a phase L1 value inside the 3-phase block), 4057 (its value list prints 3Ph/4W twice), 7120-7138 (reserved, time and 'utilized ordered power' printed with unit V), 7086/7543 which the table skips, the alarm and display setup registers, and 4061 status 2.
- Table 10 shows which values exist in 3Ph/4W, 3Ph/3W and 1Ph/2W modes; per-phase values are not valid in 3-wire mode.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lumel ND20LITE network parameter meter
What Modbus registers does the Lumel ND20LITE network parameter meter have?
This map lists 69 registers: 69 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lumel ND20LITE network parameter meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are used as printed: the example frames read 4000 as 0x0FA0, 7000 as 0x1B58 and 6000 as 0x1770. The 'documented' field of float registers shows the table's 6xxx/7xxx pair; this map uses the 7xxx address.
What byte order does the Lumel ND20LITE network parameter meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lumel ND20LITE network parameter meter?
Start with HR 7000 Voltage of phase L1 (Voltage L1); HR 7002 Current in phase L1 (Current L1); HR 7046 3-phase active power (P1+P2+P3) (3-phase active power); HR 7052 Mean power factor (PF) (Mean power factor); HR 7056 Frequency (Frequency); HR 4038 Imported active energy (counter) (Imported active energy counter); HR 4050 Status register (Status bits).
How do I enable Modbus control of the Lumel ND20LITE network parameter meter?
Modbus RTU is always on; set address, mode and baud from the menu or registers 4030-4032, then write 1 to 4033.
Where is the official Lumel ND20LITE network parameter meter Modbus documentation?
The source is ND20LITE Meter of network parameters - User's manual, published free by Lumel at https://www.lumel.com.pl/resources/Pliki%20do%20pobrania/ND20LITE/ND20LITE_user_manual.pdf.
More Lumel Modbus register maps
- Power meter (panel network parameter meter)
Lumel ND20 network parameter meter
Lumel ND20 panel meter per the ND20 user's manual; registers 4056-4061 need firmware 1.09 or later and are not listed here.
Also known as: ND20, ND20-xxxx - Power meter (panel network parameter meter)
Lumel ND31LITE network parameter meter
Lumel ND31LITE panel meter with RS-485 Modbus RTU, per user manual ND31LITE-09.
Also known as: ND31LITE - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID08 / NMID09 / NMID10 single-phase energy meter
Modbus RTU versions of the NMID08 (1/5 A CT), NMID09 (100 mA CT) and NMID10 (100 A direct) meters; the LITE and MBUS versions have no Modbus port.
Also known as: NMID08, NMID09, NMID10 - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID11 / NMID12 / NMID13 single-phase energy meter
Modbus RTU versions of the NMID11, NMID12 and NMID13 meters (NMID11/NMID13 are the CT-connected models); the LITE and MBUS versions have no Modbus port.
Also known as: NMID11, NMID12, NMID13 - Energy meter (DIN-rail, three-phase, MID)
Lumel NMID31 / NMID32 three-phase energy meter
Lumel NMID31 and NMID32 DIN-rail single/three-phase energy meters with RS-485 Modbus RTU, per their interface manual.
Also known as: NMID31, NMID32 - Energy meter (DIN-rail, single-phase)
Lumel NR10PLUS single-phase energy meter
Lumel NR10PLUS single-phase DIN-rail meter with RS-485 Modbus RTU, per its user manual.
Also known as: NR10PLUS - Power meter (DIN-rail network meter)
Lumel NR30 DIN-rail power network meter
Lumel NR30 rail-mounted 3-phase meter (RS-485 Modbus RTU; Ethernet versions also offer Modbus TCP), per manual NR30-09E_R1.
Also known as: NR30
Other power & energy meters register maps
- Energy meter
Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC)
Measurlogic DTS AC and DC sub-meters and transducers with Modbus RTU or Modbus TCP, per DTS Modbus Map version 2.7U (Oct 2012). Registers depend on model and wiring.
Also known as: DTS 101, DTS 105, DTS 305, DTS 310, DTS SMX, DTS SKT, DTS DC - Energy meter
Panasonic KW7M Eco-POWER METER
Panasonic KW7M (AKW7111 / AKW7111B) with Modbus RTU selected, user manual ARCT1F434E-6.
Also known as: AKW7111, AKW7111B - Sensor (counter / rate panel meter)
Red Lion PAXI counter / rate panel meter (Modbus)
PAXI counter/rate meters with a Modbus serial card, per register table LP0897A (revised 7/10/12).
Also known as: PAXI, PAX I, Red Lion PAXI counter - Energy meter
Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters
Rishabh RISH ED11XX (direct), EC11XX (CT) and ER11XX (RJ12 CT) single-phase DIN-rail meters in their Modbus (x1) versions, per operating manual DMAN-00IM-1071 Rev. M.
Also known as: RISH ED11X1, RISH EC11X1, RISH ER11X1, ED1111, EC1111, ER1111, RISH ED11XX, RISH EC11XX, RISH ER11XX - Energy meter (DC)
Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter
Rishabh RISH EM DC 6001 / 6002 multi-channel DC energy meters with RS-485 Modbus, per interface definition 2-60-006-00-00627 Rev. 0 (10/2015).
Also known as: RISH EM DC 6001, RISH EM DC 6002, EM DC 6001, EM DC 6002 - Power meter (multi-circuit energy meter)
Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)
RISH Multiload Monitor (12 current channels, 4 voltage channels) per interface definition DMAN-00IM-0795 Rev A (08/2020).
Also known as: RISH ML 1400, RISH ML 1410, RISH MLM, Multiload Monitor
All power & energy meters Modbus register maps →
Source: ND20LITE Meter of network parameters - User's manual. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.