Power meter (panel network parameter meter) · Modbus register map

Lumel ND20LITE network parameter meter Modbus register map

Updated 17 November 2026

Short answer

The ND20LITE is a 96x96 panel meter for 3- and 1-phase networks with an RS-485 Modbus RTU port. Measured values are floats offered in several register areas; this map uses the 7000 area (two registers per value, high word first) for per-phase and total values, THD and energies, plus the 4000 area for comms settings, 32-bit energy counters and the status word.

This page lists 69 Modbus registers for the Lumel ND20LITE network parameter meter — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lumel’s own free documentation (linked below) and checked against it.

Manufacturer
Lumel
Model
ND20LITE network parameter meter
Equipment type
Power meter (panel network parameter meter)
Registers
69 (4 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
ND20LITE
Source document
ND20LITE Meter of network parameters - User's manual
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lumel ND20LITE network parameter meter

Integration in brief

Read holding registers (function 03 or 04) from 7000 for per-phase values, 7042-7064 for 3-phase totals and frequency, and 7100-7118 or 4038-4047 for energy. Floats are high word first in the 7000 area.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 7000Voltage of phase L1FLOAT32 ABCDVoltage L1Read
HR 7002Current in phase L1FLOAT32 ABCDCurrent L1Read
HR 70463-phase active power (P1+P2+P3)FLOAT32 ABCD3-phase active powerRead
HR 7052Mean power factor (PF)FLOAT32 ABCDMean power factorRead
HR 7056FrequencyFLOAT32 ABCDFrequencyRead
HR 4038Imported active energy (counter)UINT32 ABCDImported active energy counterRead
HR 4050Status registerBITMAP16Status bitsRead

Enable Modbus control & writes

Modbus RTU is always on; set address, mode and baud from the menu or registers 4030-4032, then write 1 to 4033.

Byte order & addressing

Network setup

Watch out for

Lumel ND20LITE network parameter meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

69 of 69 shown
Lumel ND20LITE network parameter meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR4030Modbus addressUINT16Read/write
HR4031Transmission modeUINT16Read/write0 = 8N2; 1 = 8E1; 2 = 8O1; 3 = 8N1
HR4032Baud rateUINT16Read/write0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400
HR4033Apply transmission settingsWrite 1 to make new address/mode/baud take effect.UINT16Read/write
HR4038doc 4038-4039Imported active energy (counter)High register x 65536 + low register, in 0.1 units.UINT32ABCD× 0.1kWhRead
HR4040doc 4040-4041Exported active energy (counter)High register x 65536 + low register, in 0.1 units.UINT32ABCD× 0.1kWhRead
HR4042doc 4042-4043Reactive inductive energy (counter)High register x 65536 + low register, in 0.1 units.UINT32ABCD× 0.1kvarhRead
HR4044doc 4044-4045Reactive capacitive energy (counter)High register x 65536 + low register, in 0.1 units.UINT32ABCD× 0.1kvarhRead
HR4046doc 4046-4047Apparent energy (counter)High register x 65536 + low register, in 0.1 units.UINT32ABCD× 0.1kVAhRead
HR4050Status registerBITMAP16Readbit 0 = Relay output on; bit 2 = Voltage L1 too low; bit 3 = Voltage L2 too low; bit 4 = Voltage L3 too low; bit 5 = Voltage too low for frequency measurement; bit 6 = Frequency outside THD calculation range; bit 7 = Averaging interval not yet elapsed; bit 10 = Current range 5 A (0 = 1 A); bit 11 = Phase sequence error; bit 12 = Energy value error; bit 13 = Parameter value error; bit 14 = No or bad calibration; bit 15 = Non-volatile memory damaged
HR4053Program versionUINT16× 0.01Read
HR7000doc 6000/7000Voltage of phase L1FLOAT32ABCDVRead
HR7002doc 6002/7002Current in phase L1FLOAT32ABCDARead
HR7004doc 6004/7004Active power of phase L1FLOAT32ABCDWRead
HR7006doc 6006/7006Reactive power of phase L1FLOAT32ABCDvarRead
HR7008doc 6008/7008Apparent power of phase L1FLOAT32ABCDVARead
HR7010doc 6010/7010Power factor (PF) of phase L1FLOAT32ABCDRead
HR7012doc 6012/7012Tg phi factor L1FLOAT32ABCDRead
HR7014doc 6014/7014Voltage of phase L2FLOAT32ABCDVRead
HR7016doc 6016/7016Current in phase L2FLOAT32ABCDARead
HR7018doc 6018/7018Active power of phase L2FLOAT32ABCDWRead
HR7020doc 6020/7020Reactive power of phase L2FLOAT32ABCDvarRead
HR7022doc 6022/7022Apparent power of phase L2FLOAT32ABCDVARead
HR7024doc 6024/7024Power factor (PF) of phase L2FLOAT32ABCDRead
HR7026doc 6026/7026Tg phi factor L2FLOAT32ABCDRead
HR7028doc 6028/7028Voltage of phase L3FLOAT32ABCDVRead
HR7030doc 6030/7030Current in phase L3FLOAT32ABCDARead
HR7032doc 6032/7032Active power of phase L3FLOAT32ABCDWRead
HR7034doc 6034/7034Reactive power of phase L3FLOAT32ABCDvarRead
HR7036doc 6036/7036Apparent power of phase L3FLOAT32ABCDVARead
HR7038doc 6038/7038Power factor (PF) of phase L3FLOAT32ABCDRead
HR7040doc 6040/7040Tg phi factor L3FLOAT32ABCDRead
HR7042doc 6042/7042Mean 3-phase voltageFLOAT32ABCDVRead
HR7044doc 6044/7044Mean 3-phase currentFLOAT32ABCDARead
HR7046doc 6046/70463-phase active power (P1+P2+P3)FLOAT32ABCDWRead
HR7048doc 6048/70483-phase reactive power (Q1+Q2+Q3)FLOAT32ABCDvarRead
HR7050doc 6050/70503-phase apparent power (S1+S2+S3)FLOAT32ABCDVARead
HR7052doc 6052/7052Mean power factor (PF)FLOAT32ABCDRead
HR7056doc 6056/7056FrequencyFLOAT32ABCDHzRead
HR7058doc 6058/7058Phase-to-phase voltage L1-2FLOAT32ABCDVRead
HR7060doc 6060/7060Phase-to-phase voltage L2-3FLOAT32ABCDVRead
HR7062doc 6062/7062Phase-to-phase voltage L3-1FLOAT32ABCDVRead
HR7064doc 6064/7064Mean phase-to-phase voltageFLOAT32ABCDVRead
HR7066doc 6066/70663-phase 15/30/60-minute active power (P1+P2+P3)FLOAT32ABCDWRead
HR7068doc 6068/7068THD U1FLOAT32ABCD%Read
HR7070doc 6070/7070THD U2FLOAT32ABCD%Read
HR7072doc 6072/7072THD U3FLOAT32ABCD%Read
HR7074doc 6074/7074THD U meanFLOAT32ABCD%Read
HR7076doc 6076/7076THD I1FLOAT32ABCD%Read
HR7078doc 6078/7078THD I2FLOAT32ABCD%Read
HR7080doc 6080/7080THD I3FLOAT32ABCD%Read
HR7082doc 6082/7082Cosinus of angle between U1 and I1FLOAT32ABCDRead
HR7084doc 6084/7084Cosinus of angle between U2 and I2FLOAT32ABCDRead
HR7088doc 6088/7088Cosinus of angle between U3 and I3FLOAT32ABCDRead
HR7090doc 6090/70903-phase mean cosinusFLOAT32ABCDRead
HR7092doc 6092/7092Angle between U1 and I1FLOAT32ABCD°Read
HR7094doc 6094/7094Angle between U2 and I2FLOAT32ABCD°Read
HR7096doc 6096/7096Angle between U3 and I3FLOAT32ABCD°Read
HR7098doc 6098/7098Neutral current (calculated from vectors)FLOAT32ABCDARead
HR7100doc 6100/7100Imported active energy overflowsCounts 100 MWh (100 Mvarh/MVAh) roll-overs of the next register.FLOAT32ABCD100 MWhRead
HR7102doc 6102/7102Imported active energyCounter up to 99999.9; add 100000 x the overflow register.FLOAT32ABCDkWhRead
HR7104doc 6104/7104Exported active energy overflowsCounts 100 MWh (100 Mvarh/MVAh) roll-overs of the next register.FLOAT32ABCD100 MWhRead
HR7106doc 6106/7106Exported active energyCounter up to 99999.9; add 100000 x the overflow register.FLOAT32ABCDkWhRead
HR7108doc 6108/7108Reactive inductive energy overflowsCounts 100 MWh (100 Mvarh/MVAh) roll-overs of the next register.FLOAT32ABCD100 MvarhRead
HR7110doc 6110/7110Reactive inductive energyCounter up to 99999.9; add 100000 x the overflow register.FLOAT32ABCDkvarhRead
HR7112doc 6112/7112Reactive capacitive energy overflowsCounts 100 MWh (100 Mvarh/MVAh) roll-overs of the next register.FLOAT32ABCD100 MvarhRead
HR7114doc 6114/7114Reactive capacitive energyCounter up to 99999.9; add 100000 x the overflow register.FLOAT32ABCDkvarhRead
HR7116doc 6116/7116Apparent energy overflowsCounts 100 MWh (100 Mvarh/MVAh) roll-overs of the next register.FLOAT32ABCD100 MVAhRead
HR7118doc 6118/7118Apparent energyCounter up to 99999.9; add 100000 x the overflow register.FLOAT32ABCDkVAhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lumel ND20LITE network parameter meter

What Modbus registers does the Lumel ND20LITE network parameter meter have?

This map lists 69 registers: 69 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lumel ND20LITE network parameter meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are used as printed: the example frames read 4000 as 0x0FA0, 7000 as 0x1B58 and 6000 as 0x1770. The 'documented' field of float registers shows the table's 6xxx/7xxx pair; this map uses the 7xxx address.

What byte order does the Lumel ND20LITE network parameter meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Lumel ND20LITE network parameter meter?

Start with HR 7000 Voltage of phase L1 (Voltage L1); HR 7002 Current in phase L1 (Current L1); HR 7046 3-phase active power (P1+P2+P3) (3-phase active power); HR 7052 Mean power factor (PF) (Mean power factor); HR 7056 Frequency (Frequency); HR 4038 Imported active energy (counter) (Imported active energy counter); HR 4050 Status register (Status bits).

How do I enable Modbus control of the Lumel ND20LITE network parameter meter?

Modbus RTU is always on; set address, mode and baud from the menu or registers 4030-4032, then write 1 to 4033.

Where is the official Lumel ND20LITE network parameter meter Modbus documentation?

The source is ND20LITE Meter of network parameters - User's manual, published free by Lumel at https://www.lumel.com.pl/resources/Pliki%20do%20pobrania/ND20LITE/ND20LITE_user_manual.pdf.

More Lumel Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: ND20LITE Meter of network parameters - User's manual. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.