Power meter (panel network parameter meter) · Modbus register map
Lumel ND20 network parameter meter Modbus register map
Updated 17 November 2026
The ND20 is a 96x96 panel meter for 3- and 1-phase networks with an RS-485 Modbus RTU port. Each measured value is offered as a float in several register areas; this map uses the 7000 area (two 16-bit registers per value, high word first) plus the 4000 area of 16-bit settings, 32-bit energy counters and the status word.
This page lists 74 Modbus registers for the Lumel ND20 network parameter meter — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lumel’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lumel
- Model
- ND20 network parameter meter
- Equipment type
- Power meter (panel network parameter meter)
- Registers
- 74 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- ND20, ND20-xxxx
Integration notes: Lumel ND20 network parameter meter
Read holding registers (FC03 or FC04) from 7000: 3 x 7 per-phase floats then 3-phase totals and frequency, high word first. Energy totals are the float pairs at 7096-7110 or the 32-bit counters at 4038-4045 (divide by 10).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 7000 | Voltage L1 | FLOAT32 ABCD | Voltage L1 | Read |
| HR 7002 | Current L1 | FLOAT32 ABCD | Current L1 | Read |
| HR 7046 | 3-phase active power | FLOAT32 ABCD | 3-phase active power | Read |
| HR 7052 | Mean power factor | FLOAT32 ABCD | Mean power factor | Read |
| HR 7056 | Frequency | FLOAT32 ABCD | Frequency | Read |
| HR 4038 | Imported active energy | UINT32 ABCD | Imported active energy | Read |
| HR 4050 | Status register | BITMAP16 | Status / error bits | Read |
Enable Modbus control & writes
The manual describes no separate Modbus enable; address, transmission mode and baud are set from the front menu or registers 4030-4032, then write 1 to 4033 to apply.
Byte order & addressing
- The 6000 area is low word first, the 7000 area high word first: pick one and stick to it.
- Read at most 41 32-bit or 82 16-bit registers per request.
- Powers are in W, var and VA, not kW.
Network setup
- Factory settings: address 1, 9600 baud, 8N2.
- Maximum response time is 600 ms.
Watch out for
- The 7096-7110 energies come as an overflow count (100 MWh) plus a counter that rolls at 99999.9 kWh.
Lumel ND20 network parameter meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 4000 | Password | Protection password, 0-60000. | UINT16 | Read/write | ||||
| HR | 4003 | CT ratio | Current transformer ratio, 1-10000. | UINT16 | Read/write | ||||
| HR | 4004 | VT ratio | Voltage transformer ratio stored x10. | UINT16 | × 0.1 | Read/write | |||
| HR | 4005 | Demand power synchronisation | UINT16 | Read/write | 0 = 15 min sliding window; 1 = 15 min, clock-synchronised; 2 = 30 min, clock-synchronised; 3 = 60 min, clock-synchronised | ||||
| HR | 4011 | Energy reset | UINT16 | Read/write | 0 = No change; 1 = Erase active energy; 2 = Erase reactive energy; 3 = Erase harmonic energy; 4 = Erase all energy | ||||
| HR | 4030 | Modbus address | 1-247. | UINT16 | Read/write | ||||
| HR | 4031 | Transmission mode | UINT16 | Read/write | 0 = 8N2; 1 = 8E1; 2 = 8O1; 3 = 8N1 | ||||
| HR | 4032 | Baud rate | UINT16 | Read/write | 0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400 | ||||
| HR | 4033 | Apply transmission settings | Write 1 to make new address/mode/baud take effect. | UINT16 | Read/write | ||||
| HR | 4038doc 4038-4039 | Imported active energy | High word first; raw is in 0.1 kWh (kvarh) steps. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 4040doc 4040-4041 | Exported active energy | High word first; raw is in 0.1 kWh (kvarh) steps. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 4042doc 4042-4043 | Reactive inductive energy | High word first; raw is in 0.1 kWh (kvarh) steps. | UINT32 | ABCD | × 0.1 | kvarh | Read | |
| HR | 4044doc 4044-4045 | Reactive capacitive energy | High word first; raw is in 0.1 kWh (kvarh) steps. | UINT32 | ABCD | × 0.1 | kvarh | Read | |
| HR | 4046doc 4046-4047 | Imported harmonic active energy | High word first; raw is in 0.1 kWh (kvarh) steps. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 4048doc 4048-4049 | Exported harmonic active energy | High word first; raw is in 0.1 kWh (kvarh) steps. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 4050 | Status register | BITMAP16 | Read | bit 0 = Relay output on; bit 1 = RTC battery exhausted; bit 2 = Phase A voltage too low; bit 3 = Phase B voltage too low; bit 4 = Phase C voltage too low; bit 5 = Voltage too low to measure frequency; bit 6 = Frequency outside THD calculation window; bit 7 = Demand averaging interval not yet elapsed; bit 8 = Voltage range bit 0 (bits 9-8: 00 = 57.7 V, 01 = 230 V); bit 9 = Voltage range bit 1; bit 10 = Current range (0 = 1 A, 1 = 5 A); bit 11 = Phase sequence error; bit 12 = Energy value error; bit 13 = Parameter value error; bit 14 = Missing or faulty calibration; bit 15 = Non-volatile memory damaged | ||||
| HR | 4051doc 4051-4052 | Serial number | High word first. | UINT32 | ABCD | Read | |||
| HR | 4053 | Program version | Firmware version x100. | UINT16 | × 0.01 | Read | |||
| HR | 7000doc 6000/7000 | Voltage L1 | FLOAT32 | ABCD | V | Read | |||
| HR | 7002doc 6002/7002 | Current L1 | FLOAT32 | ABCD | A | Read | |||
| HR | 7004doc 6004/7004 | Active power L1 | FLOAT32 | ABCD | W | Read | |||
| HR | 7006doc 6006/7006 | Reactive power L1 | FLOAT32 | ABCD | var | Read | |||
| HR | 7008doc 6008/7008 | Apparent power L1 | FLOAT32 | ABCD | VA | Read | |||
| HR | 7010doc 6010/7010 | Power factor L1 | FLOAT32 | ABCD | Read | ||||
| HR | 7012doc 6012/7012 | Tg phi L1 | FLOAT32 | ABCD | Read | ||||
| HR | 7014doc 6014/7014 | Voltage L2 | FLOAT32 | ABCD | V | Read | |||
| HR | 7016doc 6016/7016 | Current L2 | FLOAT32 | ABCD | A | Read | |||
| HR | 7018doc 6018/7018 | Active power L2 | FLOAT32 | ABCD | W | Read | |||
| HR | 7020doc 6020/7020 | Reactive power L2 | FLOAT32 | ABCD | var | Read | |||
| HR | 7022doc 6022/7022 | Apparent power L2 | FLOAT32 | ABCD | VA | Read | |||
| HR | 7024doc 6024/7024 | Power factor L2 | FLOAT32 | ABCD | Read | ||||
| HR | 7026doc 6026/7026 | Tg phi L2 | FLOAT32 | ABCD | Read | ||||
| HR | 7028doc 6028/7028 | Voltage L3 | FLOAT32 | ABCD | V | Read | |||
| HR | 7030doc 6030/7030 | Current L3 | FLOAT32 | ABCD | A | Read | |||
| HR | 7032doc 6032/7032 | Active power L3 | FLOAT32 | ABCD | W | Read | |||
| HR | 7034doc 6034/7034 | Reactive power L3 | FLOAT32 | ABCD | var | Read | |||
| HR | 7036doc 6036/7036 | Apparent power L3 | FLOAT32 | ABCD | VA | Read | |||
| HR | 7038doc 6038/7038 | Power factor L3 | FLOAT32 | ABCD | Read | ||||
| HR | 7040doc 6040/7040 | Tg phi L3 | FLOAT32 | ABCD | Read | ||||
| HR | 7042doc 6042/7042 | Mean 3-phase voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 7044doc 6044/7044 | Mean 3-phase current | FLOAT32 | ABCD | A | Read | |||
| HR | 7046doc 6046/7046 | 3-phase active power | Sum P1+P2+P3. | FLOAT32 | ABCD | W | Read | ||
| HR | 7048doc 6048/7048 | 3-phase reactive power | Sum Q1+Q2+Q3. | FLOAT32 | ABCD | var | Read | ||
| HR | 7050doc 6050/7050 | 3-phase apparent power | Sum S1+S2+S3. | FLOAT32 | ABCD | VA | Read | ||
| HR | 7052doc 6052/7052 | Mean power factor | FLOAT32 | ABCD | Read | ||||
| HR | 7056doc 6056/7056 | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 7058doc 6058/7058 | Voltage L1-L2 | FLOAT32 | ABCD | V | Read | |||
| HR | 7060doc 6060/7060 | Voltage L2-L3 | FLOAT32 | ABCD | V | Read | |||
| HR | 7062doc 6062/7062 | Voltage L3-L1 | FLOAT32 | ABCD | V | Read | |||
| HR | 7064doc 6064/7064 | Mean phase-to-phase voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 7066doc 6066/7066 | 3-phase demand active power | Averaged over the 15/30/60 minute window set in register 4005. | FLOAT32 | ABCD | W | Read | ||
| HR | 7068doc 6068/7068 | Harmonic / THD U1 | Selected harmonic or THD, per register 4006. | FLOAT32 | ABCD | V/% | Read | ||
| HR | 7070doc 6070/7070 | Harmonic / THD U2 | FLOAT32 | ABCD | V/% | Read | |||
| HR | 7072doc 6072/7072 | Harmonic / THD U3 | FLOAT32 | ABCD | V/% | Read | |||
| HR | 7074doc 6074/7074 | Harmonic / THD I1 | FLOAT32 | ABCD | A/% | Read | |||
| HR | 7076doc 6076/7076 | Harmonic / THD I2 | FLOAT32 | ABCD | A/% | Read | |||
| HR | 7078doc 6078/7078 | Harmonic / THD I3 | FLOAT32 | ABCD | A/% | Read | |||
| HR | 7080doc 6080/7080 | Cos phi U1-I1 | FLOAT32 | ABCD | Read | ||||
| HR | 7082doc 6082/7082 | Cos phi U2-I2 | FLOAT32 | ABCD | Read | ||||
| HR | 7084doc 6084/7084 | Cos phi U3-I3 | FLOAT32 | ABCD | Read | ||||
| HR | 7086doc 6086/7086 | 3-phase mean cos phi | FLOAT32 | ABCD | Read | ||||
| HR | 7088doc 6088/7088 | Angle U1-I1 | FLOAT32 | ABCD | ° | Read | |||
| HR | 7090doc 6090/7090 | Angle U2-I2 | FLOAT32 | ABCD | ° | Read | |||
| HR | 7092doc 6092/7092 | Angle U3-I3 | FLOAT32 | ABCD | ° | Read | |||
| HR | 7094doc 6094/7094 | Neutral current | Calculated from the phase vectors. | FLOAT32 | ABCD | A | Read | ||
| HR | 7096doc 6096/7096 | Imported active energy, overflows | Count of rollovers of 7098. | FLOAT32 | ABCD | 100 MWh | Read | ||
| HR | 7098doc 6098/7098 | Imported active energy | Counts up to 99999.9 kWh. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 7100doc 6100/7100 | Exported active energy, overflows | Count of rollovers of 7102. | FLOAT32 | ABCD | 100 MWh | Read | ||
| HR | 7102doc 6102/7102 | Exported active energy | Counts up to 99999.9 kWh. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 7104doc 6104/7104 | Reactive inductive energy, overflows | Count of rollovers of 7106. | FLOAT32 | ABCD | 100 Mvarh | Read | ||
| HR | 7106doc 6106/7106 | Reactive inductive energy | Counts up to 99999.9 kvarh. | FLOAT32 | ABCD | kvarh | Read | ||
| HR | 7108doc 6108/7108 | Reactive capacitive energy, overflows | Count of rollovers of 7110. | FLOAT32 | ABCD | 100 Mvarh | Read | ||
| HR | 7110doc 6110/7110 | Reactive capacitive energy | Counts up to 99999.9 kvarh. | FLOAT32 | ABCD | kvarh | Read | ||
| HR | 7126doc 6126/7126 | Analog output value | FLOAT32 | ABCD | mA | Read |
Notes on this map
- Source is Conrad's copy of the unaltered Lumel manual; Lumel's own site did not turn up a public copy of the full manual in two searches, though its quick-start guides point to lumel.com.pl.
- Float areas: 7000-7319 is two 16-bit registers per value with bytes 3-2-1-0 (ABCD), confirmed by the example frame that returns 41 20 00 00 = 10.0. The 6000 area holds the same values with bytes 1-0-3-2 (CDAB) and 7500 the same values as single 32-bit registers; only the 7000 area is listed here.
- Energy in the 4000 area is (high register x 65536 + low register) / 10 in kWh or kvarh, per the manual's formulas.
- Left out: 7054 (labelled 'Mean Tg factor of phase L1', which does not fit a 3-phase mean), the min/max area from 7128 on, harmonic energy overflow pairs 7112-7118, time registers 7120-7124, the averaged power archive 1000-1077, alarm and analog output setup 4001-4002 and 4012-4029, display configuration 4054-4056, and 4057 (its value list prints 3Ph/4W twice).
- Which quantities are valid depends on the connection (3Ph/4W, 3Ph/3W, 1Ph/2W); Table 12 marks phase values that are not available in 3-wire mode.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lumel ND20 network parameter meter
What Modbus registers does the Lumel ND20 network parameter meter have?
This map lists 74 registers: 74 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lumel ND20 network parameter meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are used as printed: the manual's example frames read 4000 as 0x0FA0, 7000 as 0x1B58 and 7500 as 0x1D4C. For the float area the 'documented' field shows the table's '6xxx/7xxx' pair; this map uses the 7xxx address.
What byte order does the Lumel ND20 network parameter meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lumel ND20 network parameter meter?
Start with HR 7000 Voltage L1 (Voltage L1); HR 7002 Current L1 (Current L1); HR 7046 3-phase active power (3-phase active power); HR 7052 Mean power factor (Mean power factor); HR 7056 Frequency (Frequency); HR 4038 Imported active energy (Imported active energy); HR 4050 Status register (Status / error bits).
How do I enable Modbus control of the Lumel ND20 network parameter meter?
The manual describes no separate Modbus enable; address, transmission mode and baud are set from the front menu or registers 4030-4032, then write 1 to 4033 to apply.
Where is the official Lumel ND20 network parameter meter Modbus documentation?
The source is Meter of network parameters ND20 type - User's manual. Lumel doesn't publish it on its own website, so this map was re-typed from a free copy at https://asset.conrad.com/media10/add/160267/c1/-/en/001384097ML02/upute-za-rukovanje-1384097-lumel-nd20-221100m1.pdf. It may be an older revision, so check it against the live unit.
More Lumel Modbus register maps
- Power meter (panel network parameter meter)
Lumel ND20LITE network parameter meter
Lumel ND20LITE 96x96 panel meter with RS-485 Modbus RTU (not the ND20 or ND20CT, which have their own maps).
Also known as: ND20LITE - Power meter (panel network parameter meter)
Lumel ND31LITE network parameter meter
Lumel ND31LITE panel meter with RS-485 Modbus RTU, per user manual ND31LITE-09.
Also known as: ND31LITE - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID08 / NMID09 / NMID10 single-phase energy meter
Modbus RTU versions of the NMID08 (1/5 A CT), NMID09 (100 mA CT) and NMID10 (100 A direct) meters; the LITE and MBUS versions have no Modbus port.
Also known as: NMID08, NMID09, NMID10 - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID11 / NMID12 / NMID13 single-phase energy meter
Modbus RTU versions of the NMID11, NMID12 and NMID13 meters (NMID11/NMID13 are the CT-connected models); the LITE and MBUS versions have no Modbus port.
Also known as: NMID11, NMID12, NMID13 - Energy meter (DIN-rail, three-phase, MID)
Lumel NMID31 / NMID32 three-phase energy meter
Lumel NMID31 and NMID32 DIN-rail single/three-phase energy meters with RS-485 Modbus RTU, per their interface manual.
Also known as: NMID31, NMID32 - Energy meter (DIN-rail, single-phase)
Lumel NR10PLUS single-phase energy meter
Lumel NR10PLUS single-phase DIN-rail meter with RS-485 Modbus RTU, per its user manual.
Also known as: NR10PLUS - Power meter (DIN-rail network meter)
Lumel NR30 DIN-rail power network meter
Lumel NR30 rail-mounted 3-phase meter (RS-485 Modbus RTU; Ethernet versions also offer Modbus TCP), per manual NR30-09E_R1.
Also known as: NR30
Other power & energy meters register maps
- Power meter (multi-circuit power monitor)
Omron KM-N3-FLK on-panel power monitor
Omron KM-N3-FLK power monitor (catalog N214-E1-04).
Also known as: KM-N3-FLK, KM-N3 - Sensor (counter / rate panel meter)
Red Lion PAX2D counter / rate panel meter (Modbus)
PAX2D dual counter / rate meter, per register table LP0930A (4/11/13).
Also known as: PAX2D, PAX2 D, Red Lion PAX2D counter - Energy meter
Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters
Rishabh RISH EC43xx and ER43xx DIN-rail digital energy meters with RS-485 Modbus, per interface definition DMAN-00IM-09xx Rev. F (11/25).
Also known as: EC4311, EC4321, ER4311, ER4321, RISH EC43X1, EC43XX, ER43XX - Energy meter (DC)
Rishabh Instruments RISH EM DC 6000 programmable DC energy meter
Rishabh RISH EM DC 6000 single-channel programmable DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0862 Rev. 0 (12/2020).
Also known as: RISH EM DC 6000, EMDC 6000, EM DC6000 - Power meter
Rishabh Instruments RISH Master 3440i / 3440iDL (class 0.2S) touch-screen meter
Rishabh RISH Master 3440i and 3440iDL touch-screen class 0.2S meters with RS-485 Modbus, per interface definition DMAN-00IM-0712 Rev. F (10/2026).
Also known as: RISH Master 3440i, RISH Master 3440iDL, RM3440i, RM3440iDL - Power meter (revenue / power quality)
SATEC EM235 / PM335 PRO advanced power meter
SATEC EM235 and PM335 PRO advanced power meters, per Modbus reference guide BG0613 Rev. A8 (Sept 2025).
Also known as: EM235, PM335 PRO, PM335PRO, SATEC EM235, SATEC PM335
All power & energy meters Modbus register maps →
Source: Meter of network parameters ND20 type - User's manual · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.