Power meter (panel network parameter meter) · Modbus register map

Lumel ND20 network parameter meter Modbus register map

Updated 17 November 2026

Short answer

The ND20 is a 96x96 panel meter for 3- and 1-phase networks with an RS-485 Modbus RTU port. Each measured value is offered as a float in several register areas; this map uses the 7000 area (two 16-bit registers per value, high word first) plus the 4000 area of 16-bit settings, 32-bit energy counters and the status word.

This page lists 74 Modbus registers for the Lumel ND20 network parameter meter — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lumel’s own free documentation (linked below) and checked against it.

Manufacturer
Lumel
Model
ND20 network parameter meter
Equipment type
Power meter (panel network parameter meter)
Registers
74 (9 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
ND20, ND20-xxxx
Source document
Meter of network parameters ND20 type - User's manual · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lumel ND20 network parameter meter

Integration in brief

Read holding registers (FC03 or FC04) from 7000: 3 x 7 per-phase floats then 3-phase totals and frequency, high word first. Energy totals are the float pairs at 7096-7110 or the 32-bit counters at 4038-4045 (divide by 10).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 7000Voltage L1FLOAT32 ABCDVoltage L1Read
HR 7002Current L1FLOAT32 ABCDCurrent L1Read
HR 70463-phase active powerFLOAT32 ABCD3-phase active powerRead
HR 7052Mean power factorFLOAT32 ABCDMean power factorRead
HR 7056FrequencyFLOAT32 ABCDFrequencyRead
HR 4038Imported active energyUINT32 ABCDImported active energyRead
HR 4050Status registerBITMAP16Status / error bitsRead

Enable Modbus control & writes

The manual describes no separate Modbus enable; address, transmission mode and baud are set from the front menu or registers 4030-4032, then write 1 to 4033 to apply.

Byte order & addressing

Network setup

Watch out for

Lumel ND20 network parameter meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

74 of 74 shown
Lumel ND20 network parameter meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR4000PasswordProtection password, 0-60000.UINT16Read/write
HR4003CT ratioCurrent transformer ratio, 1-10000.UINT16Read/write
HR4004VT ratioVoltage transformer ratio stored x10.UINT16× 0.1Read/write
HR4005Demand power synchronisationUINT16Read/write0 = 15 min sliding window; 1 = 15 min, clock-synchronised; 2 = 30 min, clock-synchronised; 3 = 60 min, clock-synchronised
HR4011Energy resetUINT16Read/write0 = No change; 1 = Erase active energy; 2 = Erase reactive energy; 3 = Erase harmonic energy; 4 = Erase all energy
HR4030Modbus address1-247.UINT16Read/write
HR4031Transmission modeUINT16Read/write0 = 8N2; 1 = 8E1; 2 = 8O1; 3 = 8N1
HR4032Baud rateUINT16Read/write0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400
HR4033Apply transmission settingsWrite 1 to make new address/mode/baud take effect.UINT16Read/write
HR4038doc 4038-4039Imported active energyHigh word first; raw is in 0.1 kWh (kvarh) steps.UINT32ABCD× 0.1kWhRead
HR4040doc 4040-4041Exported active energyHigh word first; raw is in 0.1 kWh (kvarh) steps.UINT32ABCD× 0.1kWhRead
HR4042doc 4042-4043Reactive inductive energyHigh word first; raw is in 0.1 kWh (kvarh) steps.UINT32ABCD× 0.1kvarhRead
HR4044doc 4044-4045Reactive capacitive energyHigh word first; raw is in 0.1 kWh (kvarh) steps.UINT32ABCD× 0.1kvarhRead
HR4046doc 4046-4047Imported harmonic active energyHigh word first; raw is in 0.1 kWh (kvarh) steps.UINT32ABCD× 0.1kWhRead
HR4048doc 4048-4049Exported harmonic active energyHigh word first; raw is in 0.1 kWh (kvarh) steps.UINT32ABCD× 0.1kWhRead
HR4050Status registerBITMAP16Readbit 0 = Relay output on; bit 1 = RTC battery exhausted; bit 2 = Phase A voltage too low; bit 3 = Phase B voltage too low; bit 4 = Phase C voltage too low; bit 5 = Voltage too low to measure frequency; bit 6 = Frequency outside THD calculation window; bit 7 = Demand averaging interval not yet elapsed; bit 8 = Voltage range bit 0 (bits 9-8: 00 = 57.7 V, 01 = 230 V); bit 9 = Voltage range bit 1; bit 10 = Current range (0 = 1 A, 1 = 5 A); bit 11 = Phase sequence error; bit 12 = Energy value error; bit 13 = Parameter value error; bit 14 = Missing or faulty calibration; bit 15 = Non-volatile memory damaged
HR4051doc 4051-4052Serial numberHigh word first.UINT32ABCDRead
HR4053Program versionFirmware version x100.UINT16× 0.01Read
HR7000doc 6000/7000Voltage L1FLOAT32ABCDVRead
HR7002doc 6002/7002Current L1FLOAT32ABCDARead
HR7004doc 6004/7004Active power L1FLOAT32ABCDWRead
HR7006doc 6006/7006Reactive power L1FLOAT32ABCDvarRead
HR7008doc 6008/7008Apparent power L1FLOAT32ABCDVARead
HR7010doc 6010/7010Power factor L1FLOAT32ABCDRead
HR7012doc 6012/7012Tg phi L1FLOAT32ABCDRead
HR7014doc 6014/7014Voltage L2FLOAT32ABCDVRead
HR7016doc 6016/7016Current L2FLOAT32ABCDARead
HR7018doc 6018/7018Active power L2FLOAT32ABCDWRead
HR7020doc 6020/7020Reactive power L2FLOAT32ABCDvarRead
HR7022doc 6022/7022Apparent power L2FLOAT32ABCDVARead
HR7024doc 6024/7024Power factor L2FLOAT32ABCDRead
HR7026doc 6026/7026Tg phi L2FLOAT32ABCDRead
HR7028doc 6028/7028Voltage L3FLOAT32ABCDVRead
HR7030doc 6030/7030Current L3FLOAT32ABCDARead
HR7032doc 6032/7032Active power L3FLOAT32ABCDWRead
HR7034doc 6034/7034Reactive power L3FLOAT32ABCDvarRead
HR7036doc 6036/7036Apparent power L3FLOAT32ABCDVARead
HR7038doc 6038/7038Power factor L3FLOAT32ABCDRead
HR7040doc 6040/7040Tg phi L3FLOAT32ABCDRead
HR7042doc 6042/7042Mean 3-phase voltageFLOAT32ABCDVRead
HR7044doc 6044/7044Mean 3-phase currentFLOAT32ABCDARead
HR7046doc 6046/70463-phase active powerSum P1+P2+P3.FLOAT32ABCDWRead
HR7048doc 6048/70483-phase reactive powerSum Q1+Q2+Q3.FLOAT32ABCDvarRead
HR7050doc 6050/70503-phase apparent powerSum S1+S2+S3.FLOAT32ABCDVARead
HR7052doc 6052/7052Mean power factorFLOAT32ABCDRead
HR7056doc 6056/7056FrequencyFLOAT32ABCDHzRead
HR7058doc 6058/7058Voltage L1-L2FLOAT32ABCDVRead
HR7060doc 6060/7060Voltage L2-L3FLOAT32ABCDVRead
HR7062doc 6062/7062Voltage L3-L1FLOAT32ABCDVRead
HR7064doc 6064/7064Mean phase-to-phase voltageFLOAT32ABCDVRead
HR7066doc 6066/70663-phase demand active powerAveraged over the 15/30/60 minute window set in register 4005.FLOAT32ABCDWRead
HR7068doc 6068/7068Harmonic / THD U1Selected harmonic or THD, per register 4006.FLOAT32ABCDV/%Read
HR7070doc 6070/7070Harmonic / THD U2FLOAT32ABCDV/%Read
HR7072doc 6072/7072Harmonic / THD U3FLOAT32ABCDV/%Read
HR7074doc 6074/7074Harmonic / THD I1FLOAT32ABCDA/%Read
HR7076doc 6076/7076Harmonic / THD I2FLOAT32ABCDA/%Read
HR7078doc 6078/7078Harmonic / THD I3FLOAT32ABCDA/%Read
HR7080doc 6080/7080Cos phi U1-I1FLOAT32ABCDRead
HR7082doc 6082/7082Cos phi U2-I2FLOAT32ABCDRead
HR7084doc 6084/7084Cos phi U3-I3FLOAT32ABCDRead
HR7086doc 6086/70863-phase mean cos phiFLOAT32ABCDRead
HR7088doc 6088/7088Angle U1-I1FLOAT32ABCD°Read
HR7090doc 6090/7090Angle U2-I2FLOAT32ABCD°Read
HR7092doc 6092/7092Angle U3-I3FLOAT32ABCD°Read
HR7094doc 6094/7094Neutral currentCalculated from the phase vectors.FLOAT32ABCDARead
HR7096doc 6096/7096Imported active energy, overflowsCount of rollovers of 7098.FLOAT32ABCD100 MWhRead
HR7098doc 6098/7098Imported active energyCounts up to 99999.9 kWh.FLOAT32ABCDkWhRead
HR7100doc 6100/7100Exported active energy, overflowsCount of rollovers of 7102.FLOAT32ABCD100 MWhRead
HR7102doc 6102/7102Exported active energyCounts up to 99999.9 kWh.FLOAT32ABCDkWhRead
HR7104doc 6104/7104Reactive inductive energy, overflowsCount of rollovers of 7106.FLOAT32ABCD100 MvarhRead
HR7106doc 6106/7106Reactive inductive energyCounts up to 99999.9 kvarh.FLOAT32ABCDkvarhRead
HR7108doc 6108/7108Reactive capacitive energy, overflowsCount of rollovers of 7110.FLOAT32ABCD100 MvarhRead
HR7110doc 6110/7110Reactive capacitive energyCounts up to 99999.9 kvarh.FLOAT32ABCDkvarhRead
HR7126doc 6126/7126Analog output valueFLOAT32ABCDmARead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lumel ND20 network parameter meter

What Modbus registers does the Lumel ND20 network parameter meter have?

This map lists 74 registers: 74 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lumel ND20 network parameter meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are used as printed: the manual's example frames read 4000 as 0x0FA0, 7000 as 0x1B58 and 7500 as 0x1D4C. For the float area the 'documented' field shows the table's '6xxx/7xxx' pair; this map uses the 7xxx address.

What byte order does the Lumel ND20 network parameter meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Lumel ND20 network parameter meter?

Start with HR 7000 Voltage L1 (Voltage L1); HR 7002 Current L1 (Current L1); HR 7046 3-phase active power (3-phase active power); HR 7052 Mean power factor (Mean power factor); HR 7056 Frequency (Frequency); HR 4038 Imported active energy (Imported active energy); HR 4050 Status register (Status / error bits).

How do I enable Modbus control of the Lumel ND20 network parameter meter?

The manual describes no separate Modbus enable; address, transmission mode and baud are set from the front menu or registers 4030-4032, then write 1 to 4033 to apply.

Where is the official Lumel ND20 network parameter meter Modbus documentation?

The source is Meter of network parameters ND20 type - User's manual. Lumel doesn't publish it on its own website, so this map was re-typed from a free copy at https://asset.conrad.com/media10/add/160267/c1/-/en/001384097ML02/upute-za-rukovanje-1384097-lumel-nd20-221100m1.pdf. It may be an older revision, so check it against the live unit.

More Lumel Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Meter of network parameters ND20 type - User's manual · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.