- NMID08 / NMID09 / NMID10 single-phase energy meter
Energy meter (DIN-rail, single-phase, MID) · Modbus register map
Lumel NMID08 / NMID09 / NMID10 single-phase energy meter Modbus register map
Updated 17 November 2026
Single-phase MID energy meters with an RS-485 Modbus RTU port. Every value is an IEEE-754 float in two registers, high word first, readable as input registers (3X) and mirrored as holding registers (4X). This map covers the 3X measurement table: instantaneous values, demands, total, tariff and partial energies with their overflow counters.
This page lists 88 Modbus registers for the Lumel NMID08 / NMID09 / NMID10 single-phase energy meter — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lumel’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lumel
- Model
- NMID08 / NMID09 / NMID10 single-phase energy meter
- Equipment type
- Energy meter (DIN-rail, single-phase, MID)
- Registers
- 88 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- NMID08, NMID09, NMID10
Integration notes: Lumel NMID08 / NMID09 / NMID10 single-phase energy meter
Poll input registers 0x00-0x1F with function 04 for voltage, current, powers and power factor, then 0x6C and 0x70 for import/export energy. Each value is a float in two registers, high word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Voltage | FLOAT32 ABCD | Voltage | Read |
| IR 6 | Current | FLOAT32 ABCD | Current | Read |
| IR 12 | Active Power | FLOAT32 ABCD | Active power | Read |
| IR 30 | Power Factor | FLOAT32 ABCD | Power factor | Read |
| IR 70 | Frequency | FLOAT32 ABCD | Frequency | Read |
| IR 108 | Active Import Energy | FLOAT32 ABCD | Active import energy | Read |
| IR 112 | Active Export Energy | FLOAT32 ABCD | Active export energy | Read |
Enable Modbus control & writes
Modbus is always on in the Modbus versions; set address, baud rate and parity/stop bits in the front-panel setup menu.
Byte order & addressing
- Read two registers per value and never start a read in the middle of a float (exception 02).
- Keep one request to 40 parameters (80 registers) or fewer.
Network setup
- Factory settings: address 1, 9600 baud, no parity, 1 stop bit (nonE1).
- Parity choices are nonE1, nonE2, EVEn and odd.
- Broadcast address 0 is not supported.
Watch out for
- Energy needs the overflow counter for very large totals.
Lumel NMID08 / NMID09 / NMID10 single-phase energy meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 (0x0000) | Voltage | FLOAT32 | ABCD | V | Read | |||
| IR | 6doc 30007 (0x0006) | Current | FLOAT32 | ABCD | A | Read | |||
| IR | 12doc 30013 (0x000C) | Active Power | FLOAT32 | ABCD | W | Read | |||
| IR | 18doc 30019 (0x0012) | Apparent Power | FLOAT32 | ABCD | VA | Read | |||
| IR | 24doc 30025 (0x0018) | Reactive Power | FLOAT32 | ABCD | VAr | Read | |||
| IR | 30doc 30031 (0x001E) | Power Factor | FLOAT32 | ABCD | Read | ||||
| IR | 70doc 30071 (0x0046) | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| IR | 72doc 30073 (0x0048) | W Import Demand | FLOAT32 | ABCD | W | Read | |||
| IR | 74doc 30075 (0x004A) | W Import Max Demand | FLOAT32 | ABCD | W | Read | |||
| IR | 76doc 30077 (0x004C) | W Export Demand | FLOAT32 | ABCD | W | Read | |||
| IR | 78doc 30079 (0x004E) | W Exp. Max Demand | FLOAT32 | ABCD | W | Read | |||
| IR | 80doc 30081 (0x0050) | var Imp. / Ind Demand | FLOAT32 | ABCD | VAr | Read | |||
| IR | 82doc 30083 (0x0052) | var Imp. / Ind Max Demand | FLOAT32 | ABCD | VAr | Read | |||
| IR | 86doc 30087 (0x0056) | var Exp. / Cap Max Demand | FLOAT32 | ABCD | VAr | Read | |||
| IR | 88doc 30089 (0x0058) | va Imp. Demand | FLOAT32 | ABCD | VA | Read | |||
| IR | 90doc 30091 (0x005A) | va Imp. Max Demand | FLOAT32 | ABCD | VA | Read | |||
| IR | 92doc 30093 (0x005C) | va Exp. Demand | FLOAT32 | ABCD | VA | Read | |||
| IR | 94doc 30095 (0x005E) | va Exp. Max Demand | FLOAT32 | ABCD | VA | Read | |||
| IR | 96doc 30097 (0x0060) | Current Imp. Demand | FLOAT32 | ABCD | A | Read | |||
| IR | 98doc 30099 (0x0062) | Current Imp Max. Demand | FLOAT32 | ABCD | A | Read | |||
| IR | 106doc 30107 (0x006A) | Active Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 108doc 30109 (0x006C) | Active Import Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 110doc 30111 (0x006E) | Active Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 112doc 30113 (0x0070) | Active Export Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 114doc 30115 (0x0072) | Reactive Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 116doc 30117 (0x0074) | Reactive Import Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 118doc 30119 (0x0076) | Reactive Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 120doc 30121 (0x0078) | Reactive Export Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 122doc 30123 (0x007A) | Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 124doc 30125 (0x007C) | Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 130doc 30131 (0x0082) | Total Active Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 132doc 30133 (0x0084) | Total Active Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 134doc 30135 (0x0086) | Total Reactive Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 136doc 30137 (0x0088) | Total Reactive Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 138doc 30139 (0x008A) | Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 140doc 30141 (0x008C) | Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 142doc 30143 (0x008E) | T1 Active Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 144doc 30145 (0x0090) | T1 Active Import Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 146doc 30147 (0x0092) | T1 Active Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 148doc 30149 (0x0094) | T1 Active Export Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 150doc 30151 (0x0096) | T1 Reactive Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 152doc 30153 (0x0098) | T1 Reactive Import Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 154doc 30155 (0x009A) | T1 Reactive Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 156doc 30157 (0x009C) | T1 Reactive Export Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 158doc 30159 (0x009E) | T1 Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 160doc 30161 (0x00A0) | T1 Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 166doc 30167 (0x00A6) | T1 Total Active Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 168doc 30169 (0x00A8) | T1 Total Active Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 170doc 30171 (0x00AA) | T1 Total Reactive Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 172doc 30173 (0x00AC) | T1 Total Reactive Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 174doc 30175 (0x00AE) | T1 Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 176doc 30177 (0x00B0) | T1 Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 178doc 30179 (0x00B2) | T2 Active Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 180doc 30181 (0x00B4) | T2 Active Import Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 182doc 30183 (0x00B6) | T2 Active Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 184doc 30185 (0x00B8) | T2 Active Export Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 186doc 30187 (0x00BA) | T2 Reactive Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 188doc 30189 (0x00BC) | T2 Reactive Import Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 190doc 30191 (0x00BE) | T2 Reactive Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 192doc 30193 (0x00C0) | T2 Reactive Export Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 194doc 30195 (0x00C2) | T2 Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 196doc 30197 (0x00C4) | T2 Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 202doc 30203 (0x00CA) | T2 Total Active Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 204doc 30205 (0x00CC) | T2 Total Active Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 206doc 30207 (0x00CE) | T2 Total Reactive Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 208doc 30209 (0x00D0) | T2 Total Reactive Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 210doc 30211 (0x00D2) | T2 Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 212doc 30213 (0x00D4) | T2 Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 214doc 30215 (0x00D6) | Partial Active Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 216doc 30217 (0x00D8) | Partial Active Import Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 218doc 30219 (0x00DA) | Partial Active Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 220doc 30221 (0x00DC) | Partial Active Export Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 222doc 30223 (0x00DE) | Partial Reactive Import Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 224doc 30225 (0x00E0) | Partial Reactive Import Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 226doc 30227 (0x00E2) | partial Reactive Export Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 228doc 30229 (0x00E4) | Partial Reactive Export Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 230doc 30231 (0x00E6) | Partial Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 232doc 30233 (0x00E8) | Partial Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 238doc 30239 (0x00EE) | Partial Total Active Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 240doc 30241 (0x00F0) | Partial Total Active Energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 242doc 30243 (0x00F2) | Partial Total Reactive Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 244doc 30245 (0x00F4) | Partial Total Reactive Energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 246doc 30247 (0x00F6) | Partial Total Apparent Energy Overflow Count | Times the matching energy register rolled past 99999.999. | FLOAT32 | ABCD | Read | |||
| IR | 248doc 30249 (0x00F8) | Partial Total Apparent Energy | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 254doc 30255 (0x00FE) | No of Interrupts | FLOAT32 | ABCD | Read | ||||
| IR | 256doc 30257 (0x0100) | Impulse Rate | FLOAT32 | ABCD | Read | ||||
| IR | 260doc 30261 (0x0104) | Tariff Status | FLOAT32 | ABCD | Read | ||||
| IR | 262doc 30263 (0x0106) | Current Direction | 0 = current flows the right way, 1 = reversed. | FLOAT32 | ABCD | Read |
Notes on this map
- Format is stated as 4 bytes per parameter, IEEE-754 float, most significant byte first; the example frames return 43 66 00 00 for 230 V and 40 A0 00 00 for 5 A, which settles high word first.
- The same values sit in the 4X (holding register) area at the same addresses; this map lists the 3X copy only.
- Left out: hex 0x54, which the table labels 'var Exp./Cap Max Demand' exactly like 0x56; the long-energy table 5 (0x200 on), because its data format is not spelled out; the 4X setup table 6 and the user-assignable area from 0x400.
- Energy registers count up to 99999.999 and the matching overflow register counts the roll-overs.
- Table 4 uses the label 'Total Apparent Energy' twice (0x7A/0x7C and 0x8A/0x8C), and likewise for the T1, T2 and partial groups; both copies are listed as printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lumel NMID08 / NMID09 / NMID10 single-phase energy meter
What Modbus registers does the Lumel NMID08 / NMID09 / NMID10 single-phase energy meter have?
This map lists 88 registers: 88 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lumel NMID08 / NMID09 / NMID10 single-phase energy meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The measurement table prints Modicon numbers (30001) next to the hex start address (00 00). The hex column is the wire address, so 30001 is register 0 and power factor 30031 is 0x1E.
What byte order does the Lumel NMID08 / NMID09 / NMID10 single-phase energy meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lumel NMID08 / NMID09 / NMID10 single-phase energy meter?
Start with IR 0 Voltage (Voltage); IR 6 Current (Current); IR 12 Active Power (Active power); IR 30 Power Factor (Power factor); IR 70 Frequency (Frequency); IR 108 Active Import Energy (Active import energy); IR 112 Active Export Energy (Active export energy).
How do I enable Modbus control of the Lumel NMID08 / NMID09 / NMID10 single-phase energy meter?
Modbus is always on in the Modbus versions; set address, baud rate and parity/stop bits in the front-panel setup menu.
Where is the official Lumel NMID08 / NMID09 / NMID10 single-phase energy meter Modbus documentation?
The source is NMID08, NMID09, NMID10 DIN rail mount single phase energy meter - User Manual, published free by Lumel at https://www.lumel.com.pl/resources/Pliki%20do%20pobrania/liczniki%20energii/NMID08_NMID09_NMID10_user_manual.pdf.
More Lumel Modbus register maps
- Power meter (panel network parameter meter)
Lumel ND20 network parameter meter
Lumel ND20 panel meter per the ND20 user's manual; registers 4056-4061 need firmware 1.09 or later and are not listed here.
Also known as: ND20, ND20-xxxx - Power meter (panel network parameter meter)
Lumel ND20LITE network parameter meter
Lumel ND20LITE 96x96 panel meter with RS-485 Modbus RTU (not the ND20 or ND20CT, which have their own maps).
Also known as: ND20LITE - Power meter (panel network parameter meter)
Lumel ND31LITE network parameter meter
Lumel ND31LITE panel meter with RS-485 Modbus RTU, per user manual ND31LITE-09.
Also known as: ND31LITE - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID11 / NMID12 / NMID13 single-phase energy meter
Modbus RTU versions of the NMID11, NMID12 and NMID13 meters (NMID11/NMID13 are the CT-connected models); the LITE and MBUS versions have no Modbus port.
Also known as: NMID11, NMID12, NMID13 - Energy meter (DIN-rail, three-phase, MID)
Lumel NMID31 / NMID32 three-phase energy meter
Lumel NMID31 and NMID32 DIN-rail single/three-phase energy meters with RS-485 Modbus RTU, per their interface manual.
Also known as: NMID31, NMID32 - Energy meter (DIN-rail, single-phase)
Lumel NR10PLUS single-phase energy meter
Lumel NR10PLUS single-phase DIN-rail meter with RS-485 Modbus RTU, per its user manual.
Also known as: NR10PLUS - Power meter (DIN-rail network meter)
Lumel NR30 DIN-rail power network meter
Lumel NR30 rail-mounted 3-phase meter (RS-485 Modbus RTU; Ethernet versions also offer Modbus TCP), per manual NR30-09E_R1.
Also known as: NR30
Other power & energy meters register maps
- Energy meter
Northern Design Cube 300 panel kWh meter (Modbus RTU option)
Cube300 meters fitted with the RS-485 Modbus option, per the October 2005 Modbus Communications manual.
Also known as: Cube300, ND Cube 300, Northern Design Cube300 - Energy meter (multi-circuit power monitor)
Panasonic KW9M Eco-POWER METER
Panasonic KW9M (AKW91110) with the Modbus RTU protocol selected, user manual WUME-KW9M-10.
Also known as: AKW91110 - Energy meter
Rishabh Instruments RISH Delta Energy NX multifunction energy meter
Rishabh RISH Delta Energy NX panel energy meters with RS-485 Modbus RTU, per the operating manual on the product page (standard CT version).
Also known as: RISH Delta Energy NX, Delta Energy NX, RISH Delta Energy - Energy meter
Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters
Rishabh RISH EM 1320/1330/1340 and EM 2320/2330/2340 panel energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0721 Rev. B (06/2020). Rows marked 'only 2340' apply to the dual-source EM 2340.
Also known as: RISH EM 1320, RISH EM 1330, RISH EM 1340, RISH EM 2320, RISH EM 2330, RISH EM 2340, EM2340DS - Power meter
Rishabh Instruments RISH LM 1360 load manager (LM 13xx)
Rishabh RISH LM 1360 panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0662 Rev. D (01/2024).
Also known as: RISH LM 1360, LM1360, LM 13xx, LM1360 RJ12 - Energy meter
Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU)
ALE3 unidirectional (ALE3D5FD10C3A00) and bidirectional (ALE3B5FD00C3A00) Modbus types, assembly and operating instructions 431951130.
Also known as: ALE3D5FD10C3A00, ALE3B5FD00C3A00, ALE3D5FD10, ALE3B5FD00, SBC ALE3 Modbus
All power & energy meters Modbus register maps →
Source: NMID08, NMID09, NMID10 DIN rail mount single phase energy meter - User Manual. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.