Energy meter (DIN-rail, three-phase, MID) · Modbus register map
Lumel NMID31 / NMID32 three-phase energy meter Modbus register map
Updated 17 November 2026
DIN-rail MID energy meters for 1- and 3-phase networks with an RS-485 Modbus RTU port. Values are IEEE-754 floats in two registers, high word first by default, readable as input registers (3X) and mirrored in the 4X area. This map covers table 1.1: per-phase and system values, demands, energies, THD and hour counters.
This page lists 80 Modbus registers for the Lumel NMID31 / NMID32 three-phase energy meter — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lumel’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lumel
- Model
- NMID31 / NMID32 three-phase energy meter
- Equipment type
- Energy meter (DIN-rail, three-phase, MID)
- Registers
- 80 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- NMID31, NMID32
- Source document
- NMID32 / NMID31 Digital energy meter - Interface manual
Integration notes: Lumel NMID31 / NMID32 three-phase energy meter
Read input registers with function 04 from 0x00: per-phase volts, amps and powers, then system values at 0x2A-0x46 and import/export energy at 0x48-0x50. Each value is a float in two registers.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Voltage L1 (Voltage L12 for 3P3W) | FLOAT32 ABCD | Voltage L1 | Read |
| IR 6 | Current L1 | FLOAT32 ABCD | Current L1 | Read |
| IR 52 | Watt Sum | FLOAT32 ABCD | Total active power | Read |
| IR 70 | Freq | FLOAT32 ABCD | Frequency | Read |
| IR 72 | Wh import | FLOAT32 ABCD | Active energy import | Read |
| IR 74 | Wh export | FLOAT32 ABCD | Active energy export | Read |
Enable Modbus control & writes
Modbus is always on; set address and the RS-485 setup code (baud/parity/stop bits, table 4) from the front-panel menu.
Byte order & addressing
- Never start a read in the middle of a float (exception 02).
- At most 20 parameters (40 registers) per request.
- Word order is switchable; a meter set to reversed order returns CDAB.
Network setup
- RS-485 setup code (table 4) combines baud 4800-57600 with parity and stop bits in one value.
Watch out for
- Tables 1.2 and 1.3 (per-phase and tariff energies) are not in this map; their Modicon numbers and hex addresses do not always agree, so check both before using them.
Lumel NMID31 / NMID32 three-phase energy meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 (0x0000) | Voltage L1 (Voltage L12 for 3P3W) | FLOAT32 | ABCD | V | Read | |||
| IR | 2doc 30003 (0x0002) | Voltage L2 (Voltage L23 for 3P3W) | FLOAT32 | ABCD | V | Read | |||
| IR | 4doc 30005 (0x0004) | Voltage L3 (Voltage L31 for 3P3W) | FLOAT32 | ABCD | V | Read | |||
| IR | 6doc 30007 (0x0006) | Current L1 | FLOAT32 | ABCD | A | Read | |||
| IR | 8doc 30009 (0x0008) | Current L2 | FLOAT32 | ABCD | A | Read | |||
| IR | 10doc 30011 (0x000A) | Current L3 | FLOAT32 | ABCD | A | Read | |||
| IR | 12doc 30013 (0x000C) | Watt L1 | FLOAT32 | ABCD | W | Read | |||
| IR | 14doc 30015 (0x000E) | Watt L2 | FLOAT32 | ABCD | W | Read | |||
| IR | 16doc 30017 (0x0010) | Watt L3 | FLOAT32 | ABCD | W | Read | |||
| IR | 18doc 30019 (0x0012) | VA L1 | FLOAT32 | ABCD | VA | Read | |||
| IR | 20doc 30021 (0x0014) | VA L2 | FLOAT32 | ABCD | VA | Read | |||
| IR | 22doc 30023 (0x0016) | VA L3 | FLOAT32 | ABCD | VA | Read | |||
| IR | 24doc 30025 (0x0018) | VAR L1 | FLOAT32 | ABCD | VAr | Read | |||
| IR | 26doc 30027 (0x001A) | VAR L2 | FLOAT32 | ABCD | VAr | Read | |||
| IR | 28doc 30029 (0x001C) | VAR L3 | FLOAT32 | ABCD | VAr | Read | |||
| IR | 30doc 30031 (0x001E) | Power Factor L1 | FLOAT32 | ABCD | Read | ||||
| IR | 32doc 30033 (0x0020) | Power Factor L2 | FLOAT32 | ABCD | Read | ||||
| IR | 34doc 30035 (0x0022) | Power Factor L3 | FLOAT32 | ABCD | Read | ||||
| IR | 36doc 30037 (0x0024) | Phase Angle L1 | FLOAT32 | ABCD | ° | Read | |||
| IR | 38doc 30039 (0x0026) | Phase Angle L2 | FLOAT32 | ABCD | ° | Read | |||
| IR | 40doc 30041 (0x0028) | Phase Angle L3 | FLOAT32 | ABCD | ° | Read | |||
| IR | 42doc 30043 (0x002A) | Voltage Avg | FLOAT32 | ABCD | V | Read | |||
| IR | 44doc 30045 (0x002C) | Voltage Sum | FLOAT32 | ABCD | V | Read | |||
| IR | 46doc 30047 (0x002E) | Current Avg | FLOAT32 | ABCD | A | Read | |||
| IR | 48doc 30049 (0x0030) | Current Sum | FLOAT32 | ABCD | A | Read | |||
| IR | 52doc 30053 (0x0034) | Watt Sum | FLOAT32 | ABCD | W | Read | |||
| IR | 54doc 30055 (0x0036) | VA Avg | FLOAT32 | ABCD | VA | Read | |||
| IR | 56doc 30057 (0x0038) | VA Sum | FLOAT32 | ABCD | VA | Read | |||
| IR | 58doc 30059 (0x003A) | VAR Avg | FLOAT32 | ABCD | VAr | Read | |||
| IR | 60doc 30061 (0x003C) | VAr Sum | FLOAT32 | ABCD | VAr | Read | |||
| IR | 62doc 30063 (0x003E) | PF Avg | FLOAT32 | ABCD | Read | ||||
| IR | 64doc 30065 (0x0040) | PF Sum | FLOAT32 | ABCD | Read | ||||
| IR | 66doc 30067 (0x0042) | Phase Angle Avg | FLOAT32 | ABCD | ° | Read | |||
| IR | 68doc 30069 (0x0044) | Phase Angle Sum | FLOAT32 | ABCD | ° | Read | |||
| IR | 70doc 30071 (0x0046) | Freq | FLOAT32 | ABCD | Hz | Read | |||
| IR | 72doc 30073 (0x0048) | Wh import | FLOAT32 | ABCD | kWh | Read | |||
| IR | 74doc 30075 (0x004A) | Wh export | FLOAT32 | ABCD | kWh | Read | |||
| IR | 76doc 30077 (0x004C) | VArh import | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 80doc 30081 (0x0050) | VAh | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 84doc 30085 (0x0054) | W imp demand | FLOAT32 | ABCD | W | Read | |||
| IR | 86doc 30087 (0x0056) | Max W imp demand | FLOAT32 | ABCD | W | Read | |||
| IR | 88doc 30089 (0x0058) | W exp demand | FLOAT32 | ABCD | W | Read | |||
| IR | 90doc 30091 (0x005A) | Max W exp demand | FLOAT32 | ABCD | W | Read | |||
| IR | 92doc 30093 (0x005C) | VAr Imp. demand | FLOAT32 | ABCD | VAr | Read | |||
| IR | 96doc 30097 (0x0060) | VAr Exp. demand | FLOAT32 | ABCD | VAr | Read | |||
| IR | 98doc 30099 (0x0062) | Max VAr Exp. demand | FLOAT32 | ABCD | VAr | Read | |||
| IR | 100doc 30101 (0x0064) | VA demand | FLOAT32 | ABCD | VA | Read | |||
| IR | 102doc 30103 (0x0066) | max VA demand | FLOAT32 | ABCD | VA | Read | |||
| IR | 104doc 30105 (0x0068) | current demand | FLOAT32 | ABCD | A | Read | |||
| IR | 106doc 30107 (0x006A) | Max current demand | FLOAT32 | ABCD | A | Read | |||
| IR | 110doc 30111 (0x006E) | Wh Import | FLOAT32 | ABCD | kWh | Read | |||
| IR | 114doc 30115 (0x0072) | Wh export | FLOAT32 | ABCD | kWh | Read | |||
| IR | 118doc 30119 (0x0076) | VArh Import | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 122doc 30123 (0x007A) | VARh Export | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 126doc 30127 (0x007E) | VAh | FLOAT32 | ABCD | kVAh | Read | |||
| IR | 132doc 30133 (0x0084) | System Voltage Max | FLOAT32 | ABCD | V | Read | |||
| IR | 134doc 30135 (0x0086) | System Voltage Min | FLOAT32 | ABCD | V | Read | |||
| IR | 138doc 30139 (0x008A) | Impulse Rate | FLOAT32 | ABCD | Read | ||||
| IR | 140doc 30141 (0x008C) | System Current Max | FLOAT32 | ABCD | A | Read | |||
| IR | 142doc 30143 (0x008E) | System Current Min | FLOAT32 | ABCD | A | Read | |||
| IR | 144doc 30145 (0x0090) | Wh Import Resetable | Resettable energy counter. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 146doc 30147 (0x0092) | Wh export Resetable | Resettable energy counter. | FLOAT32 | ABCD | kWh | Read | ||
| IR | 148doc 30149 (0x0094) | VARh import Resetable | Resettable energy counter. | FLOAT32 | ABCD | kVArh | Read | ||
| IR | 150doc 30151 (0x0096) | VARh export Resetable | Resettable energy counter. | FLOAT32 | ABCD | kVArh | Read | ||
| IR | 154doc 30155 (0x009A) | VArh Total Resetable | Resettable energy counter. | FLOAT32 | ABCD | kVArh | Read | ||
| IR | 200doc 30201 (0x00C8) | V12 | FLOAT32 | ABCD | V | Read | |||
| IR | 202doc 30203 (0x00CA) | V23 | FLOAT32 | ABCD | V | Read | |||
| IR | 204doc 30205 (0x00CC) | V31 | FLOAT32 | ABCD | V | Read | |||
| IR | 206doc 30207 (0x00CE) | VTHD-R | R/Y/B = phases L1/L2/L3. | FLOAT32 | ABCD | % | Read | ||
| IR | 208doc 30209 (0x00D0) | VTHD-Y | R/Y/B = phases L1/L2/L3. | FLOAT32 | ABCD | % | Read | ||
| IR | 210doc 30211 (0x00D2) | VTHD-B | R/Y/B = phases L1/L2/L3. | FLOAT32 | ABCD | % | Read | ||
| IR | 212doc 30213 (0x00D4) | I THD-R | R/Y/B = phases L1/L2/L3. | FLOAT32 | ABCD | % | Read | ||
| IR | 214doc 30215 (0x00D6) | I THD-Y | R/Y/B = phases L1/L2/L3. | FLOAT32 | ABCD | % | Read | ||
| IR | 216doc 30217 (0x00D8) | I THD-B | R/Y/B = phases L1/L2/L3. | FLOAT32 | ABCD | % | Read | ||
| IR | 218doc 30219 (0x00DA) | System V-THD | FLOAT32 | ABCD | % | Read | |||
| IR | 220doc 30221 (0x00DC) | System I-THD | FLOAT32 | ABCD | % | Read | |||
| IR | 224doc 30225 (0x00E0) | Neutral Current (3P4W only) | FLOAT32 | ABCD | A | Read | |||
| IR | 226doc 30227 (0x00E2) | Run hour | FLOAT32 | ABCD | h | Read | |||
| IR | 228doc 30229 (0x00E4) | On Hour | FLOAT32 | ABCD | h | Read | |||
| IR | 230doc 30231 (0x00E6) | No. of interrupts | FLOAT32 | ABCD | Read |
Notes on this map
- Floats are IEEE-754, most significant byte first in normal mode; the example frames return 43 5B 41 06 (219.254 V) and 44 FA 00 00 (2000 W), so high word first.
- The word order can be reversed by writing 2141.0 to the word-order setup register (Table 3 lists it at 46053, the description text at 46055); this map assumes the normal order.
- The same values sit in the 4X area at the same offsets; only the 3X copy is listed.
- Left out: 0x32 'Watt Avg' (no unit printed), 0x4E 'VArh export' (unit printed kVAh), 0x5E 'max kVAr Imp. demand' (name says kVAr, unit column says VAr) row 77 'Wh Total Resetable' (hex address misprinted '.98'); the per-phase and tariff energy tables 1.2/1.3 because their Modicon numbers and hex addresses disagree in places; the 32-bit integer energy tables and the 4X setup table.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lumel NMID31 / NMID32 three-phase energy meter
What Modbus registers does the Lumel NMID31 / NMID32 three-phase energy meter have?
This map lists 80 registers: 80 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lumel NMID31 / NMID32 three-phase energy meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Table 1.1 prints Modicon numbers (30001) next to the hex start address (00 00). The hex column is the wire address, so 30001 is register 0.
What byte order does the Lumel NMID31 / NMID32 three-phase energy meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lumel NMID31 / NMID32 three-phase energy meter?
Start with IR 0 Voltage L1 (Voltage L12 for 3P3W) (Voltage L1); IR 6 Current L1 (Current L1); IR 52 Watt Sum (Total active power); IR 70 Freq (Frequency); IR 72 Wh import (Active energy import); IR 74 Wh export (Active energy export).
How do I enable Modbus control of the Lumel NMID31 / NMID32 three-phase energy meter?
Modbus is always on; set address and the RS-485 setup code (baud/parity/stop bits, table 4) from the front-panel menu.
Where is the official Lumel NMID31 / NMID32 three-phase energy meter Modbus documentation?
The source is NMID32 / NMID31 Digital energy meter - Interface manual, published free by Lumel at https://www.lumel.com.pl/resources/Pliki%20do%20pobrania/liczniki%20energii/NMID31_NMID32_interface_manual.pdf.
More Lumel Modbus register maps
- Power meter (panel network parameter meter)
Lumel ND20 network parameter meter
Lumel ND20 panel meter per the ND20 user's manual; registers 4056-4061 need firmware 1.09 or later and are not listed here.
Also known as: ND20, ND20-xxxx - Power meter (panel network parameter meter)
Lumel ND20LITE network parameter meter
Lumel ND20LITE 96x96 panel meter with RS-485 Modbus RTU (not the ND20 or ND20CT, which have their own maps).
Also known as: ND20LITE - Power meter (panel network parameter meter)
Lumel ND31LITE network parameter meter
Lumel ND31LITE panel meter with RS-485 Modbus RTU, per user manual ND31LITE-09.
Also known as: ND31LITE - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID08 / NMID09 / NMID10 single-phase energy meter
Modbus RTU versions of the NMID08 (1/5 A CT), NMID09 (100 mA CT) and NMID10 (100 A direct) meters; the LITE and MBUS versions have no Modbus port.
Also known as: NMID08, NMID09, NMID10 - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID11 / NMID12 / NMID13 single-phase energy meter
Modbus RTU versions of the NMID11, NMID12 and NMID13 meters (NMID11/NMID13 are the CT-connected models); the LITE and MBUS versions have no Modbus port.
Also known as: NMID11, NMID12, NMID13 - Energy meter (DIN-rail, single-phase)
Lumel NR10PLUS single-phase energy meter
Lumel NR10PLUS single-phase DIN-rail meter with RS-485 Modbus RTU, per its user manual.
Also known as: NR10PLUS - Power meter (DIN-rail network meter)
Lumel NR30 DIN-rail power network meter
Lumel NR30 rail-mounted 3-phase meter (RS-485 Modbus RTU; Ethernet versions also offer Modbus TCP), per manual NR30-09E_R1.
Also known as: NR30
Other power & energy meters register maps
- Power meter (modular multi-circuit energy meter)
Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU)
Each SM352 slave meter in a multicube system with the RTU485 Modbus module, per comms manual Rev Beta 1.02 (March 2011).
Also known as: MultiCube, ND multicube, SM352, RTU485 - Sensor / multi-parameter controller
ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)
diaLog DACa controllers with the Modbus RTU interface option, per software manual BA DM 212 12/15.
Also known as: DACa, diaLog DACa, DULCOMETER DACa - Power meter
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
Rishabh RISH Delta VAF NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0118 Rev. F.
Also known as: RISH Delta VAF NX, Delta VAF NX, RISH Delta VAF - Energy meter
Rishabh Instruments RISH EM 3490 SS single-phase energy meter
Rishabh RISH EM 3490 SS single-phase energy meters with the optional RS-485 Modbus output, per the 1-phase manual Rev D.
Also known as: RISH EM 3490 SS 1P, EM3490SS 1P, EM 3490 SS single-phase - Power meter
Rishabh Instruments RISH LM1360+ RJ12 smart energy meter
Rishabh RISH LM1360 PLUS RJ12 smart energy meters (RJ12 CT inputs) with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. A (01/2026).
Also known as: RISH LM 1360+, LM1360 PLUS RJ12, LM1360+ - Power meter (multi-circuit branch feeder monitor)
SATEC BFM136/036 branch feeder monitor
SATEC BFM136 and BFM036 multi-circuit meters per Modbus reference guide BG0395 Rev. A8 (July 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM136, BFM036, BFM 136, SATEC BFM136
All power & energy meters Modbus register maps →
Source: NMID32 / NMID31 Digital energy meter - Interface manual. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.