Energy meter (DIN-rail, three-phase, MID) · Modbus register map

Lumel NMID31 / NMID32 three-phase energy meter Modbus register map

Updated 17 November 2026

Short answer

DIN-rail MID energy meters for 1- and 3-phase networks with an RS-485 Modbus RTU port. Values are IEEE-754 floats in two registers, high word first by default, readable as input registers (3X) and mirrored in the 4X area. This map covers table 1.1: per-phase and system values, demands, energies, THD and hour counters.

This page lists 80 Modbus registers for the Lumel NMID31 / NMID32 three-phase energy meter — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lumel’s own free documentation (linked below) and checked against it.

Manufacturer
Lumel
Model
NMID31 / NMID32 three-phase energy meter
Equipment type
Energy meter (DIN-rail, three-phase, MID)
Registers
80 (0 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
NMID31, NMID32
Source document
NMID32 / NMID31 Digital energy meter - Interface manual
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lumel NMID31 / NMID32 three-phase energy meter

Integration in brief

Read input registers with function 04 from 0x00: per-phase volts, amps and powers, then system values at 0x2A-0x46 and import/export energy at 0x48-0x50. Each value is a float in two registers.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Voltage L1 (Voltage L12 for 3P3W)FLOAT32 ABCDVoltage L1Read
IR 6Current L1FLOAT32 ABCDCurrent L1Read
IR 52Watt SumFLOAT32 ABCDTotal active powerRead
IR 70FreqFLOAT32 ABCDFrequencyRead
IR 72Wh importFLOAT32 ABCDActive energy importRead
IR 74Wh exportFLOAT32 ABCDActive energy exportRead

Enable Modbus control & writes

Modbus is always on; set address and the RS-485 setup code (baud/parity/stop bits, table 4) from the front-panel menu.

Byte order & addressing

Network setup

Watch out for

Lumel NMID31 / NMID32 three-phase energy meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

80 of 80 shown
Lumel NMID31 / NMID32 three-phase energy meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001 (0x0000)Voltage L1 (Voltage L12 for 3P3W)FLOAT32ABCDVRead
IR2doc 30003 (0x0002)Voltage L2 (Voltage L23 for 3P3W)FLOAT32ABCDVRead
IR4doc 30005 (0x0004)Voltage L3 (Voltage L31 for 3P3W)FLOAT32ABCDVRead
IR6doc 30007 (0x0006)Current L1FLOAT32ABCDARead
IR8doc 30009 (0x0008)Current L2FLOAT32ABCDARead
IR10doc 30011 (0x000A)Current L3FLOAT32ABCDARead
IR12doc 30013 (0x000C)Watt L1FLOAT32ABCDWRead
IR14doc 30015 (0x000E)Watt L2FLOAT32ABCDWRead
IR16doc 30017 (0x0010)Watt L3FLOAT32ABCDWRead
IR18doc 30019 (0x0012)VA L1FLOAT32ABCDVARead
IR20doc 30021 (0x0014)VA L2FLOAT32ABCDVARead
IR22doc 30023 (0x0016)VA L3FLOAT32ABCDVARead
IR24doc 30025 (0x0018)VAR L1FLOAT32ABCDVArRead
IR26doc 30027 (0x001A)VAR L2FLOAT32ABCDVArRead
IR28doc 30029 (0x001C)VAR L3FLOAT32ABCDVArRead
IR30doc 30031 (0x001E)Power Factor L1FLOAT32ABCDRead
IR32doc 30033 (0x0020)Power Factor L2FLOAT32ABCDRead
IR34doc 30035 (0x0022)Power Factor L3FLOAT32ABCDRead
IR36doc 30037 (0x0024)Phase Angle L1FLOAT32ABCD°Read
IR38doc 30039 (0x0026)Phase Angle L2FLOAT32ABCD°Read
IR40doc 30041 (0x0028)Phase Angle L3FLOAT32ABCD°Read
IR42doc 30043 (0x002A)Voltage AvgFLOAT32ABCDVRead
IR44doc 30045 (0x002C)Voltage SumFLOAT32ABCDVRead
IR46doc 30047 (0x002E)Current AvgFLOAT32ABCDARead
IR48doc 30049 (0x0030)Current SumFLOAT32ABCDARead
IR52doc 30053 (0x0034)Watt SumFLOAT32ABCDWRead
IR54doc 30055 (0x0036)VA AvgFLOAT32ABCDVARead
IR56doc 30057 (0x0038)VA SumFLOAT32ABCDVARead
IR58doc 30059 (0x003A)VAR AvgFLOAT32ABCDVArRead
IR60doc 30061 (0x003C)VAr SumFLOAT32ABCDVArRead
IR62doc 30063 (0x003E)PF AvgFLOAT32ABCDRead
IR64doc 30065 (0x0040)PF SumFLOAT32ABCDRead
IR66doc 30067 (0x0042)Phase Angle AvgFLOAT32ABCD°Read
IR68doc 30069 (0x0044)Phase Angle SumFLOAT32ABCD°Read
IR70doc 30071 (0x0046)FreqFLOAT32ABCDHzRead
IR72doc 30073 (0x0048)Wh importFLOAT32ABCDkWhRead
IR74doc 30075 (0x004A)Wh exportFLOAT32ABCDkWhRead
IR76doc 30077 (0x004C)VArh importFLOAT32ABCDkVArhRead
IR80doc 30081 (0x0050)VAhFLOAT32ABCDkVAhRead
IR84doc 30085 (0x0054)W imp demandFLOAT32ABCDWRead
IR86doc 30087 (0x0056)Max W imp demandFLOAT32ABCDWRead
IR88doc 30089 (0x0058)W exp demandFLOAT32ABCDWRead
IR90doc 30091 (0x005A)Max W exp demandFLOAT32ABCDWRead
IR92doc 30093 (0x005C)VAr Imp. demandFLOAT32ABCDVArRead
IR96doc 30097 (0x0060)VAr Exp. demandFLOAT32ABCDVArRead
IR98doc 30099 (0x0062)Max VAr Exp. demandFLOAT32ABCDVArRead
IR100doc 30101 (0x0064)VA demandFLOAT32ABCDVARead
IR102doc 30103 (0x0066)max VA demandFLOAT32ABCDVARead
IR104doc 30105 (0x0068)current demandFLOAT32ABCDARead
IR106doc 30107 (0x006A)Max current demandFLOAT32ABCDARead
IR110doc 30111 (0x006E)Wh ImportFLOAT32ABCDkWhRead
IR114doc 30115 (0x0072)Wh exportFLOAT32ABCDkWhRead
IR118doc 30119 (0x0076)VArh ImportFLOAT32ABCDkVArhRead
IR122doc 30123 (0x007A)VARh ExportFLOAT32ABCDkVArhRead
IR126doc 30127 (0x007E)VAhFLOAT32ABCDkVAhRead
IR132doc 30133 (0x0084)System Voltage MaxFLOAT32ABCDVRead
IR134doc 30135 (0x0086)System Voltage MinFLOAT32ABCDVRead
IR138doc 30139 (0x008A)Impulse RateFLOAT32ABCDRead
IR140doc 30141 (0x008C)System Current MaxFLOAT32ABCDARead
IR142doc 30143 (0x008E)System Current MinFLOAT32ABCDARead
IR144doc 30145 (0x0090)Wh Import ResetableResettable energy counter.FLOAT32ABCDkWhRead
IR146doc 30147 (0x0092)Wh export ResetableResettable energy counter.FLOAT32ABCDkWhRead
IR148doc 30149 (0x0094)VARh import ResetableResettable energy counter.FLOAT32ABCDkVArhRead
IR150doc 30151 (0x0096)VARh export ResetableResettable energy counter.FLOAT32ABCDkVArhRead
IR154doc 30155 (0x009A)VArh Total ResetableResettable energy counter.FLOAT32ABCDkVArhRead
IR200doc 30201 (0x00C8)V12FLOAT32ABCDVRead
IR202doc 30203 (0x00CA)V23FLOAT32ABCDVRead
IR204doc 30205 (0x00CC)V31FLOAT32ABCDVRead
IR206doc 30207 (0x00CE)VTHD-RR/Y/B = phases L1/L2/L3.FLOAT32ABCD%Read
IR208doc 30209 (0x00D0)VTHD-YR/Y/B = phases L1/L2/L3.FLOAT32ABCD%Read
IR210doc 30211 (0x00D2)VTHD-BR/Y/B = phases L1/L2/L3.FLOAT32ABCD%Read
IR212doc 30213 (0x00D4)I THD-RR/Y/B = phases L1/L2/L3.FLOAT32ABCD%Read
IR214doc 30215 (0x00D6)I THD-YR/Y/B = phases L1/L2/L3.FLOAT32ABCD%Read
IR216doc 30217 (0x00D8)I THD-BR/Y/B = phases L1/L2/L3.FLOAT32ABCD%Read
IR218doc 30219 (0x00DA)System V-THDFLOAT32ABCD%Read
IR220doc 30221 (0x00DC)System I-THDFLOAT32ABCD%Read
IR224doc 30225 (0x00E0)Neutral Current (3P4W only)FLOAT32ABCDARead
IR226doc 30227 (0x00E2)Run hourFLOAT32ABCDhRead
IR228doc 30229 (0x00E4)On HourFLOAT32ABCDhRead
IR230doc 30231 (0x00E6)No. of interruptsFLOAT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lumel NMID31 / NMID32 three-phase energy meter

What Modbus registers does the Lumel NMID31 / NMID32 three-phase energy meter have?

This map lists 80 registers: 80 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lumel NMID31 / NMID32 three-phase energy meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Table 1.1 prints Modicon numbers (30001) next to the hex start address (00 00). The hex column is the wire address, so 30001 is register 0.

What byte order does the Lumel NMID31 / NMID32 three-phase energy meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Lumel NMID31 / NMID32 three-phase energy meter?

Start with IR 0 Voltage L1 (Voltage L12 for 3P3W) (Voltage L1); IR 6 Current L1 (Current L1); IR 52 Watt Sum (Total active power); IR 70 Freq (Frequency); IR 72 Wh import (Active energy import); IR 74 Wh export (Active energy export).

How do I enable Modbus control of the Lumel NMID31 / NMID32 three-phase energy meter?

Modbus is always on; set address and the RS-485 setup code (baud/parity/stop bits, table 4) from the front-panel menu.

Where is the official Lumel NMID31 / NMID32 three-phase energy meter Modbus documentation?

The source is NMID32 / NMID31 Digital energy meter - Interface manual, published free by Lumel at https://www.lumel.com.pl/resources/Pliki%20do%20pobrania/liczniki%20energii/NMID31_NMID32_interface_manual.pdf.

More Lumel Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: NMID32 / NMID31 Digital energy meter - Interface manual. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.