Easy Modbus
  1. Home
  2. Modbus register maps
  3. Lumel
  4. NR30 DIN-rail power network meter

Power meter (DIN-rail network meter) · Modbus register map

Lumel NR30 DIN-rail power network meter Modbus register map

Updated 17 November 2026

Short answer

The NR30 is a DIN-rail 3-phase power network meter with RS-485 Modbus RTU and, in Ethernet versions, Modbus TCP. Its fixed measurement list is offered as floats in several areas; this map uses the 8000 area (two registers per value, high word first), plus comms settings, the status word and 32-bit energy counters.

This page lists 65 Modbus registers for the Lumel NR30 DIN-rail power network meter — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lumel’s own free documentation (linked below) and checked against it.

Manufacturer
Lumel
Model
NR30 DIN-rail power network meter
Equipment type
Power meter (DIN-rail network meter)
Registers
65 (3 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
1
Default serial
9600 baud, 8N2
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
NR30
Source document
NR30 Rail mounted power network meter - User's manual · NR30-09E_R1
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lumel NR30 DIN-rail power network meter

Integration in brief

Read holding registers from 8000: per-phase values, then 3-phase totals at 8054-8066, frequency at 8072 and energies from 8090. Floats are high word first in the 8000 area.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 8000Voltage of L1 phaseFLOAT32 ABCDL1 voltageRead
HR 8002Current of L1 phaseFLOAT32 ABCDL1 currentRead
HR 80583-phase active power (P1+P2+P3)FLOAT32 ABCD3-phase active powerRead
HR 80643-phase power factor (P/S)FLOAT32 ABCD3-phase power factorRead
HR 8072FrequencyFLOAT32 ABCDFrequencyRead
HR 4426Active import energy (counter)UINT32 ABCDActive import energy counterRead
HR 4415Status register 1BITMAP16Status 1Read

Enable Modbus control & writes

Modbus RTU is always on; set address and baud from the menu or registers 4100-4102, then write 1 to 4104.

Byte order & addressing

Network setup

Watch out for

Lumel NR30 DIN-rail power network meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

65 of 65 shown
Lumel NR30 DIN-rail power network meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR4100Modbus addressUINT16Read/write
HR4102Baud rateUINT16Read/write0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400; 4 = 57600; 5 = 115200
HR4104Apply transmission settingsWrite 1 to make new address/mode/baud take effect.UINT16Read/write
HR4403Program versionUINT16× 0.01Read
HR4415Status register 1BITMAP16Readbit 1 = RTC battery used up; bit 2 = Ethernet and internal memory present; bit 5 = Supervisory relay register error; bit 6 = MQTT register error; bit 7 = Phase sequence error; bit 8 = Energy value error; bit 9 = Programmable readout group register error; bit 10 = Display page register error; bit 11 = Configuration register error; bit 14 = No input calibration; bit 15 = FRAM memory corruption
HR4426doc 4426-4427Active import energy (counter)High register x 65536 + low register, in 0.01 units.UINT32ABCD× 0.01kWhRead
HR4428doc 4428-4429Active export energy (counter)High register x 65536 + low register, in 0.01 units.UINT32ABCD× 0.01kWhRead
HR4430doc 4430-4431Reactive inductive energy (counter)High register x 65536 + low register, in 0.01 units.UINT32ABCD× 0.01kvarhRead
HR4432doc 4432-4433Reactive capacitive energy (counter)High register x 65536 + low register, in 0.01 units.UINT32ABCD× 0.01kvarhRead
HR4434doc 4434-4435Apparent energy (counter)High register x 65536 + low register, in 0.01 units.UINT32ABCD× 0.01kVAhRead
HR8000doc 6000/8000Voltage of L1 phaseFLOAT32ABCDVRead
HR8002doc 6002/8002Current of L1 phaseFLOAT32ABCDARead
HR8004doc 6004/8004Active power of L1 phaseFLOAT32ABCDWRead
HR8006doc 6006/8006Reactive power of L1 phaseFLOAT32ABCDvarRead
HR8008doc 6008/8008Apparent power of L1 phaseFLOAT32ABCDVARead
HR8010doc 6010/8010L1 power factor (P1/S1)FLOAT32ABCDRead
HR8012doc 6012/8012L1 tg phi (Q1/P1)FLOAT32ABCDRead
HR8014doc 6014/8014THD U1FLOAT32ABCD%Read
HR8016doc 6016/8016THD I1FLOAT32ABCD%Read
HR8018doc 6018/8018Voltage of L2 phaseFLOAT32ABCDVRead
HR8020doc 6020/8020Current of L2 phaseFLOAT32ABCDARead
HR8022doc 6022/8022Active power of L2 phaseFLOAT32ABCDWRead
HR8024doc 6024/8024Reactive power of L2 phaseFLOAT32ABCDvarRead
HR8026doc 6026/8026Apparent power of L2 phaseFLOAT32ABCDVARead
HR8028doc 6028/8028L2 power factor (P2/S2)FLOAT32ABCDRead
HR8030doc 6030/8030L2 tg phi (Q2/P2)FLOAT32ABCDRead
HR8032doc 6032/8032THD U2FLOAT32ABCD%Read
HR8034doc 6034/8034THD I2FLOAT32ABCD%Read
HR8036doc 6036/8036Voltage of L3 phaseFLOAT32ABCDVRead
HR8038doc 6038/8038Current of L3 phaseFLOAT32ABCDARead
HR8040doc 6040/8040Active power of L3 phaseFLOAT32ABCDWRead
HR8042doc 6042/8042Reactive power of L3 phaseFLOAT32ABCDvarRead
HR8044doc 6044/8044Apparent power of L3 phaseFLOAT32ABCDVARead
HR8046doc 6046/8046L3 power factor (P3/S3)FLOAT32ABCDRead
HR8048doc 6048/8048L3 tg phi (Q3/P3)FLOAT32ABCDRead
HR8050doc 6050/8050THD U3FLOAT32ABCD%Read
HR8052doc 6052/8052THD I3FLOAT32ABCD%Read
HR8054doc 6054/8054Average 3-phase voltageFLOAT32ABCDVRead
HR8056doc 6056/8056Average 3-phase currentFLOAT32ABCDARead
HR8058doc 6058/80583-phase active power (P1+P2+P3)FLOAT32ABCDWRead
HR8060doc 6060/80603-phase reactive power (Q1+Q2+Q3)FLOAT32ABCDvarRead
HR8062doc 6062/80623-phase apparent power (S1+S2+S3)FLOAT32ABCDVARead
HR8064doc 6064/80643-phase power factor (P/S)FLOAT32ABCDRead
HR8066doc 6066/8066Mean 3-phase tg phi (Q/P)FLOAT32ABCDRead
HR8068doc 6068/8068Mean 3-phase THD UFLOAT32ABCD%Read
HR8070doc 6070/8070Mean 3-phase THD IFLOAT32ABCD%Read
HR8072doc 6072/8072FrequencyUnit printed as 'f' in the table.FLOAT32ABCDHzRead
HR8074doc 6074/8074Phase-to-phase voltage L1-2FLOAT32ABCDVRead
HR8076doc 6076/8076Phase-to-phase voltage L2-3FLOAT32ABCDVRead
HR8078doc 6078/8078Phase-to-phase voltage L3-1FLOAT32ABCDVRead
HR8080doc 6080/8080Average phase-to-phase voltagePrinted as 'Average phase-to-phase voltage L1-2'.FLOAT32ABCDVRead
HR8082doc 6082/8082Averaged active power (P demand)FLOAT32ABCDWRead
HR8084doc 6084/8084Averaged apparent power (S demand)FLOAT32ABCDVARead
HR8086doc 6086/8086Averaged current (I demand)FLOAT32ABCDARead
HR8088doc 6088/8088Current in neutral wire (calculated from vectors)FLOAT32ABCDARead
HR8090doc 6090/8090Active import energy overflowsCounts roll-overs of the next register.FLOAT32ABCD100 MWhRead
HR8092doc 6092/8092Active import energyCounter up to 99999.99; add the overflow register for the full total.FLOAT32ABCDkWhRead
HR8094doc 6094/8094Active export energy overflowsCounts roll-overs of the next register.FLOAT32ABCD100 MWhRead
HR8096doc 6096/8096Active export energyCounter up to 99999.99; add the overflow register for the full total.FLOAT32ABCDkWhRead
HR8098doc 6098/8098Reactive inductive energy overflowsCounts roll-overs of the next register.FLOAT32ABCD100 MvarhRead
HR8100doc 6100/8100Reactive inductive energyCounter up to 99999.99; add the overflow register for the full total.FLOAT32ABCDkvarhRead
HR8102doc 6102/8102Reactive capacitive energy overflowsCounts roll-overs of the next register.FLOAT32ABCD100 MvarhRead
HR8104doc 6104/8104Reactive capacitive energyCounter up to 99999.99; add the overflow register for the full total.FLOAT32ABCDkvarhRead
HR8106doc 6106/8106Apparent energy overflowsCounts roll-overs of the next register.FLOAT32ABCD100 MVAhRead
HR8108doc 6108/8108Apparent energyCounter up to 99999.99; add the overflow register for the full total.FLOAT32ABCDkVAhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lumel NR30 DIN-rail power network meter

What Modbus registers does the Lumel NR30 DIN-rail power network meter have?

This map lists 65 registers: 65 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lumel NR30 DIN-rail power network meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are used as printed: the example frames read 7000 as 0x1B58 and 6000 as 0x1770. Float registers show the table's 6xxx/8xxx pair in 'documented'; this map uses the 8xxx address.

What byte order does the Lumel NR30 DIN-rail power network meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Lumel NR30 DIN-rail power network meter?

Start with HR 8000 Voltage of L1 phase (L1 voltage); HR 8002 Current of L1 phase (L1 current); HR 8058 3-phase active power (P1+P2+P3) (3-phase active power); HR 8064 3-phase power factor (P/S) (3-phase power factor); HR 8072 Frequency (Frequency); HR 4426 Active import energy (counter) (Active import energy counter); HR 4415 Status register 1 (Status 1).

How do I enable Modbus control of the Lumel NR30 DIN-rail power network meter?

Modbus RTU is always on; set address and baud from the menu or registers 4100-4102, then write 1 to 4104.

Where is the official Lumel NR30 DIN-rail power network meter Modbus documentation?

The source is NR30 Rail mounted power network meter - User's manual (NR30-09E_R1), published free by Lumel at https://www.lumel.com.pl/resources/Pliki%20do%20pobrania/NR30/NR30_service_manual.pdf.

More Lumel Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: NR30 Rail mounted power network meter - User's manual · NR30-09E_R1. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.