Power meter (DIN-rail network meter) · Modbus register map
Lumel NR30 DIN-rail power network meter Modbus register map
Updated 17 November 2026
The NR30 is a DIN-rail 3-phase power network meter with RS-485 Modbus RTU and, in Ethernet versions, Modbus TCP. Its fixed measurement list is offered as floats in several areas; this map uses the 8000 area (two registers per value, high word first), plus comms settings, the status word and 32-bit energy counters.
This page lists 65 Modbus registers for the Lumel NR30 DIN-rail power network meter — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lumel’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lumel
- Model
- NR30 DIN-rail power network meter
- Equipment type
- Power meter (DIN-rail network meter)
- Registers
- 65 (3 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- NR30
Integration notes: Lumel NR30 DIN-rail power network meter
Read holding registers from 8000: per-phase values, then 3-phase totals at 8054-8066, frequency at 8072 and energies from 8090. Floats are high word first in the 8000 area.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8000 | Voltage of L1 phase | FLOAT32 ABCD | L1 voltage | Read |
| HR 8002 | Current of L1 phase | FLOAT32 ABCD | L1 current | Read |
| HR 8058 | 3-phase active power (P1+P2+P3) | FLOAT32 ABCD | 3-phase active power | Read |
| HR 8064 | 3-phase power factor (P/S) | FLOAT32 ABCD | 3-phase power factor | Read |
| HR 8072 | Frequency | FLOAT32 ABCD | Frequency | Read |
| HR 4426 | Active import energy (counter) | UINT32 ABCD | Active import energy counter | Read |
| HR 4415 | Status register 1 | BITMAP16 | Status 1 | Read |
Enable Modbus control & writes
Modbus RTU is always on; set address and baud from the menu or registers 4100-4102, then write 1 to 4104.
Byte order & addressing
- The 6000 area is low word first and the 8000 area high word first.
- Powers are in W, var and VA.
Network setup
- Factory settings: address 1, 9600 baud, RTU 8N2.
- Modbus TCP: unit address in 4146 (default 1), port in 4147 (default 502), idle close time 4145 (60 s), up to 4 connections (4144).
Watch out for
- 7000-7118 returns whatever was programmed in 4200-4259, not a fixed list.
Lumel NR30 DIN-rail power network meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 4100 | Modbus address | UINT16 | Read/write | |||||
| HR | 4102 | Baud rate | UINT16 | Read/write | 0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400; 4 = 57600; 5 = 115200 | ||||
| HR | 4104 | Apply transmission settings | Write 1 to make new address/mode/baud take effect. | UINT16 | Read/write | ||||
| HR | 4403 | Program version | UINT16 | × 0.01 | Read | ||||
| HR | 4415 | Status register 1 | BITMAP16 | Read | bit 1 = RTC battery used up; bit 2 = Ethernet and internal memory present; bit 5 = Supervisory relay register error; bit 6 = MQTT register error; bit 7 = Phase sequence error; bit 8 = Energy value error; bit 9 = Programmable readout group register error; bit 10 = Display page register error; bit 11 = Configuration register error; bit 14 = No input calibration; bit 15 = FRAM memory corruption | ||||
| HR | 4426doc 4426-4427 | Active import energy (counter) | High register x 65536 + low register, in 0.01 units. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| HR | 4428doc 4428-4429 | Active export energy (counter) | High register x 65536 + low register, in 0.01 units. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| HR | 4430doc 4430-4431 | Reactive inductive energy (counter) | High register x 65536 + low register, in 0.01 units. | UINT32 | ABCD | × 0.01 | kvarh | Read | |
| HR | 4432doc 4432-4433 | Reactive capacitive energy (counter) | High register x 65536 + low register, in 0.01 units. | UINT32 | ABCD | × 0.01 | kvarh | Read | |
| HR | 4434doc 4434-4435 | Apparent energy (counter) | High register x 65536 + low register, in 0.01 units. | UINT32 | ABCD | × 0.01 | kVAh | Read | |
| HR | 8000doc 6000/8000 | Voltage of L1 phase | FLOAT32 | ABCD | V | Read | |||
| HR | 8002doc 6002/8002 | Current of L1 phase | FLOAT32 | ABCD | A | Read | |||
| HR | 8004doc 6004/8004 | Active power of L1 phase | FLOAT32 | ABCD | W | Read | |||
| HR | 8006doc 6006/8006 | Reactive power of L1 phase | FLOAT32 | ABCD | var | Read | |||
| HR | 8008doc 6008/8008 | Apparent power of L1 phase | FLOAT32 | ABCD | VA | Read | |||
| HR | 8010doc 6010/8010 | L1 power factor (P1/S1) | FLOAT32 | ABCD | Read | ||||
| HR | 8012doc 6012/8012 | L1 tg phi (Q1/P1) | FLOAT32 | ABCD | Read | ||||
| HR | 8014doc 6014/8014 | THD U1 | FLOAT32 | ABCD | % | Read | |||
| HR | 8016doc 6016/8016 | THD I1 | FLOAT32 | ABCD | % | Read | |||
| HR | 8018doc 6018/8018 | Voltage of L2 phase | FLOAT32 | ABCD | V | Read | |||
| HR | 8020doc 6020/8020 | Current of L2 phase | FLOAT32 | ABCD | A | Read | |||
| HR | 8022doc 6022/8022 | Active power of L2 phase | FLOAT32 | ABCD | W | Read | |||
| HR | 8024doc 6024/8024 | Reactive power of L2 phase | FLOAT32 | ABCD | var | Read | |||
| HR | 8026doc 6026/8026 | Apparent power of L2 phase | FLOAT32 | ABCD | VA | Read | |||
| HR | 8028doc 6028/8028 | L2 power factor (P2/S2) | FLOAT32 | ABCD | Read | ||||
| HR | 8030doc 6030/8030 | L2 tg phi (Q2/P2) | FLOAT32 | ABCD | Read | ||||
| HR | 8032doc 6032/8032 | THD U2 | FLOAT32 | ABCD | % | Read | |||
| HR | 8034doc 6034/8034 | THD I2 | FLOAT32 | ABCD | % | Read | |||
| HR | 8036doc 6036/8036 | Voltage of L3 phase | FLOAT32 | ABCD | V | Read | |||
| HR | 8038doc 6038/8038 | Current of L3 phase | FLOAT32 | ABCD | A | Read | |||
| HR | 8040doc 6040/8040 | Active power of L3 phase | FLOAT32 | ABCD | W | Read | |||
| HR | 8042doc 6042/8042 | Reactive power of L3 phase | FLOAT32 | ABCD | var | Read | |||
| HR | 8044doc 6044/8044 | Apparent power of L3 phase | FLOAT32 | ABCD | VA | Read | |||
| HR | 8046doc 6046/8046 | L3 power factor (P3/S3) | FLOAT32 | ABCD | Read | ||||
| HR | 8048doc 6048/8048 | L3 tg phi (Q3/P3) | FLOAT32 | ABCD | Read | ||||
| HR | 8050doc 6050/8050 | THD U3 | FLOAT32 | ABCD | % | Read | |||
| HR | 8052doc 6052/8052 | THD I3 | FLOAT32 | ABCD | % | Read | |||
| HR | 8054doc 6054/8054 | Average 3-phase voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8056doc 6056/8056 | Average 3-phase current | FLOAT32 | ABCD | A | Read | |||
| HR | 8058doc 6058/8058 | 3-phase active power (P1+P2+P3) | FLOAT32 | ABCD | W | Read | |||
| HR | 8060doc 6060/8060 | 3-phase reactive power (Q1+Q2+Q3) | FLOAT32 | ABCD | var | Read | |||
| HR | 8062doc 6062/8062 | 3-phase apparent power (S1+S2+S3) | FLOAT32 | ABCD | VA | Read | |||
| HR | 8064doc 6064/8064 | 3-phase power factor (P/S) | FLOAT32 | ABCD | Read | ||||
| HR | 8066doc 6066/8066 | Mean 3-phase tg phi (Q/P) | FLOAT32 | ABCD | Read | ||||
| HR | 8068doc 6068/8068 | Mean 3-phase THD U | FLOAT32 | ABCD | % | Read | |||
| HR | 8070doc 6070/8070 | Mean 3-phase THD I | FLOAT32 | ABCD | % | Read | |||
| HR | 8072doc 6072/8072 | Frequency | Unit printed as 'f' in the table. | FLOAT32 | ABCD | Hz | Read | ||
| HR | 8074doc 6074/8074 | Phase-to-phase voltage L1-2 | FLOAT32 | ABCD | V | Read | |||
| HR | 8076doc 6076/8076 | Phase-to-phase voltage L2-3 | FLOAT32 | ABCD | V | Read | |||
| HR | 8078doc 6078/8078 | Phase-to-phase voltage L3-1 | FLOAT32 | ABCD | V | Read | |||
| HR | 8080doc 6080/8080 | Average phase-to-phase voltage | Printed as 'Average phase-to-phase voltage L1-2'. | FLOAT32 | ABCD | V | Read | ||
| HR | 8082doc 6082/8082 | Averaged active power (P demand) | FLOAT32 | ABCD | W | Read | |||
| HR | 8084doc 6084/8084 | Averaged apparent power (S demand) | FLOAT32 | ABCD | VA | Read | |||
| HR | 8086doc 6086/8086 | Averaged current (I demand) | FLOAT32 | ABCD | A | Read | |||
| HR | 8088doc 6088/8088 | Current in neutral wire (calculated from vectors) | FLOAT32 | ABCD | A | Read | |||
| HR | 8090doc 6090/8090 | Active import energy overflows | Counts roll-overs of the next register. | FLOAT32 | ABCD | 100 MWh | Read | ||
| HR | 8092doc 6092/8092 | Active import energy | Counter up to 99999.99; add the overflow register for the full total. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 8094doc 6094/8094 | Active export energy overflows | Counts roll-overs of the next register. | FLOAT32 | ABCD | 100 MWh | Read | ||
| HR | 8096doc 6096/8096 | Active export energy | Counter up to 99999.99; add the overflow register for the full total. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 8098doc 6098/8098 | Reactive inductive energy overflows | Counts roll-overs of the next register. | FLOAT32 | ABCD | 100 Mvarh | Read | ||
| HR | 8100doc 6100/8100 | Reactive inductive energy | Counter up to 99999.99; add the overflow register for the full total. | FLOAT32 | ABCD | kvarh | Read | ||
| HR | 8102doc 6102/8102 | Reactive capacitive energy overflows | Counts roll-overs of the next register. | FLOAT32 | ABCD | 100 Mvarh | Read | ||
| HR | 8104doc 6104/8104 | Reactive capacitive energy | Counter up to 99999.99; add the overflow register for the full total. | FLOAT32 | ABCD | kvarh | Read | ||
| HR | 8106doc 6106/8106 | Apparent energy overflows | Counts roll-overs of the next register. | FLOAT32 | ABCD | 100 MVAh | Read | ||
| HR | 8108doc 6108/8108 | Apparent energy | Counter up to 99999.99; add the overflow register for the full total. | FLOAT32 | ABCD | kVAh | Read |
Notes on this map
- Byte order: the area table gives 8000-8970 as bytes 3-2-1-0 and 6000-6970 as 1-0-3-2; example 2 returns 41 20 00 00 (10.0) for a 3-2-1-0 area and example 3 returns 00 00 41 20 for the 6000 area, so the 8000 area is high word first (ABCD).
- The 7000/7200/7400 areas are a user-programmable group (set in 4200-4259) and are not listed.
- Energy counters 4426-4435 follow the manual's formula (high x 65536 + low) / 100.
- Left out: 4101 transmission mode (its row could not be read cleanly), time/date and status floats 8110-8128, the min/max area from 8136, and the alarm, MQTT and display setup registers.
- Frequency (8072) is printed with unit 'f'; it is listed in Hz.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lumel NR30 DIN-rail power network meter
What Modbus registers does the Lumel NR30 DIN-rail power network meter have?
This map lists 65 registers: 65 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lumel NR30 DIN-rail power network meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are used as printed: the example frames read 7000 as 0x1B58 and 6000 as 0x1770. Float registers show the table's 6xxx/8xxx pair in 'documented'; this map uses the 8xxx address.
What byte order does the Lumel NR30 DIN-rail power network meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lumel NR30 DIN-rail power network meter?
Start with HR 8000 Voltage of L1 phase (L1 voltage); HR 8002 Current of L1 phase (L1 current); HR 8058 3-phase active power (P1+P2+P3) (3-phase active power); HR 8064 3-phase power factor (P/S) (3-phase power factor); HR 8072 Frequency (Frequency); HR 4426 Active import energy (counter) (Active import energy counter); HR 4415 Status register 1 (Status 1).
How do I enable Modbus control of the Lumel NR30 DIN-rail power network meter?
Modbus RTU is always on; set address and baud from the menu or registers 4100-4102, then write 1 to 4104.
Where is the official Lumel NR30 DIN-rail power network meter Modbus documentation?
The source is NR30 Rail mounted power network meter - User's manual (NR30-09E_R1), published free by Lumel at https://www.lumel.com.pl/resources/Pliki%20do%20pobrania/NR30/NR30_service_manual.pdf.
More Lumel Modbus register maps
- Power meter (panel network parameter meter)
Lumel ND20 network parameter meter
Lumel ND20 panel meter per the ND20 user's manual; registers 4056-4061 need firmware 1.09 or later and are not listed here.
Also known as: ND20, ND20-xxxx - Power meter (panel network parameter meter)
Lumel ND20LITE network parameter meter
Lumel ND20LITE 96x96 panel meter with RS-485 Modbus RTU (not the ND20 or ND20CT, which have their own maps).
Also known as: ND20LITE - Power meter (panel network parameter meter)
Lumel ND31LITE network parameter meter
Lumel ND31LITE panel meter with RS-485 Modbus RTU, per user manual ND31LITE-09.
Also known as: ND31LITE - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID08 / NMID09 / NMID10 single-phase energy meter
Modbus RTU versions of the NMID08 (1/5 A CT), NMID09 (100 mA CT) and NMID10 (100 A direct) meters; the LITE and MBUS versions have no Modbus port.
Also known as: NMID08, NMID09, NMID10 - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID11 / NMID12 / NMID13 single-phase energy meter
Modbus RTU versions of the NMID11, NMID12 and NMID13 meters (NMID11/NMID13 are the CT-connected models); the LITE and MBUS versions have no Modbus port.
Also known as: NMID11, NMID12, NMID13 - Energy meter (DIN-rail, three-phase, MID)
Lumel NMID31 / NMID32 three-phase energy meter
Lumel NMID31 and NMID32 DIN-rail single/three-phase energy meters with RS-485 Modbus RTU, per their interface manual.
Also known as: NMID31, NMID32 - Energy meter (DIN-rail, single-phase)
Lumel NR10PLUS single-phase energy meter
Lumel NR10PLUS single-phase DIN-rail meter with RS-485 Modbus RTU, per its user manual.
Also known as: NR10PLUS
Other power & energy meters register maps
- Power meter (multi-circuit power monitor)
Omron KM-N3-FLK on-panel power monitor
Omron KM-N3-FLK power monitor (catalog N214-E1-04).
Also known as: KM-N3-FLK, KM-N3 - Sensor (counter / rate panel meter)
Red Lion PAX2D counter / rate panel meter (Modbus)
PAX2D dual counter / rate meter, per register table LP0930A (4/11/13).
Also known as: PAX2D, PAX2 D, Red Lion PAX2D counter - Energy meter
Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters
Rishabh RISH EC43xx and ER43xx DIN-rail digital energy meters with RS-485 Modbus, per interface definition DMAN-00IM-09xx Rev. F (11/25).
Also known as: EC4311, EC4321, ER4311, ER4321, RISH EC43X1, EC43XX, ER43XX - Energy meter (DC)
Rishabh Instruments RISH EM DC 6000 programmable DC energy meter
Rishabh RISH EM DC 6000 single-channel programmable DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0862 Rev. 0 (12/2020).
Also known as: RISH EM DC 6000, EMDC 6000, EM DC6000 - Power meter
Rishabh Instruments RISH Master 3440i / 3440iDL (class 0.2S) touch-screen meter
Rishabh RISH Master 3440i and 3440iDL touch-screen class 0.2S meters with RS-485 Modbus, per interface definition DMAN-00IM-0712 Rev. F (10/2026).
Also known as: RISH Master 3440i, RISH Master 3440iDL, RM3440i, RM3440iDL - Power meter (revenue / power quality)
SATEC EM235 / PM335 PRO advanced power meter
SATEC EM235 and PM335 PRO advanced power meters, per Modbus reference guide BG0613 Rev. A8 (Sept 2025).
Also known as: EM235, PM335 PRO, PM335PRO, SATEC EM235, SATEC PM335
All power & energy meters Modbus register maps →
Source: NR30 Rail mounted power network meter - User's manual · NR30-09E_R1. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.