- KM-N3-FLK on-panel power monitor
Power meter (multi-circuit power monitor) · Modbus register map
Omron KM-N3-FLK on-panel power monitor Modbus register map
Updated 17 November 2026
The KM-N3-FLK is a panel-mounted power monitor that measures up to four circuits through generic CTs, each circuit answering on its own Modbus RTU address. Every value is a 32-bit integer in two holding registers, high word first, with fixed scaling (voltage x10, current x1000, power x10). The map covers the measured values, energy counters, key settings and the command register.
This page lists 68 Modbus registers for the Omron KM-N3-FLK on-panel power monitor — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Omron’s own free documentation (linked below) and checked against it.
- Manufacturer
- Omron
- Model
- KM-N3-FLK on-panel power monitor
- Equipment type
- Power meter (multi-circuit power monitor)
- Registers
- 68 (10 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- KM-N3-FLK, KM-N3
Integration notes: Omron KM-N3-FLK on-panel power monitor
Read holding registers from 0x0000 with FC03 (even counts): voltage, current, PF, frequency and power as high-word-first 32-bit integers, then energy from 0x0200. Address each circuit by its own slave address.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Voltage 1 | UINT32 ABCD | Voltage 1 (x0.1 V) | Read |
| HR 6 | Current 1 | UINT32 ABCD | Current 1 (x0.001 A) | Read |
| HR 16 | Active power (total) | INT32 ABCD | Active power (x0.1 W) | Read |
| HR 12 | Power factor | INT32 ABCD | Power factor | Read |
| HR 14 | Frequency | UINT32 ABCD | Frequency | Read |
| HR 544 | Active energy import (not resettable) | UINT32 ABCD | Active energy import, kWh | Read |
Enable Modbus control & writes
Modbus is the default protocol (MENU 00 = MODBS). Set circuit A's communication address in MENU A2; circuits B-D follow in order.
Byte order & addressing
- All values are 32-bit: two registers, high word first.
- Settings need a mode-change command to address FFFF before access.
- Commands use FC06; FC16 is for writing settings.
Network setup
- Defaults: 9.6 kbps, 8 data bits (fixed for Modbus), even parity, 1 stop bit (stop bits follow parity in Modbus).
- Every circuit on the RS-485 line needs a unique address 1-99; leave room for circuits B-D after circuit A's address.
Watch out for
- Phase/wire type changes what voltage 1-3 and current 1-3 mean; check the table in section 6.4.
Omron KM-N3-FLK on-panel power monitor Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0000 | Voltage 1 | Phase voltage; meaning depends on phase/wire type. | UINT32 | ABCD | × 0.1 | V | Read | |
| HR | 2doc 0002 | Voltage 2 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 4doc 0004 | Voltage 3 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 6doc 0006 | Current 1 | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 8doc 0008 | Current 2 | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 10doc 000A | Current 3 | UINT32 | ABCD | × 0.001 | A | Read | ||
| HR | 12doc 000C | Power factor | INT32 | ABCD | × 0.01 | Read | |||
| HR | 14doc 000E | Frequency | UINT32 | ABCD | × 0.1 | Hz | Read | ||
| HR | 16doc 0010 | Active power (total) | INT32 | ABCD | × 0.1 | W | Read | ||
| HR | 18doc 0012 | Reactive power (total) | INT32 | ABCD | × 0.1 | var | Read | ||
| HR | 20doc 0014 | Voltage V1-V2 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 22doc 0016 | Voltage V1-V3 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 24doc 0018 | Voltage V2-V3 | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 26doc 001A | Active power 1 | INT32 | ABCD | × 0.1 | W | Read | ||
| HR | 28doc 001C | Active power 2 | INT32 | ABCD | × 0.1 | W | Read | ||
| HR | 30doc 001E | Active power 3 | INT32 | ABCD | × 0.1 | W | Read | ||
| HR | 32doc 0020 | Reactive power 1 | INT32 | ABCD | × 0.1 | var | Read | ||
| HR | 34doc 0022 | Reactive power 2 | INT32 | ABCD | × 0.1 | var | Read | ||
| HR | 36doc 0024 | Reactive power 3 | INT32 | ABCD | × 0.1 | var | Read | ||
| HR | 512doc 0200 | Active energy import (not resettable) | UINT32 | ABCD | Wh | Read | |||
| HR | 514doc 0202 | Active energy export (regenerative) (not resettable) | UINT32 | ABCD | Wh | Read | |||
| HR | 516doc 0204 | Reactive energy, advance (leading) (not resettable) | UINT32 | ABCD | varh | Read | |||
| HR | 518doc 0206 | Reactive energy, delay (lagging) (not resettable) | UINT32 | ABCD | varh | Read | |||
| HR | 520doc 0208 | Total reactive energy (not resettable) | UINT32 | ABCD | varh | Read | |||
| HR | 522doc 020A | Tariff T1 active energy (not resettable) | UINT32 | ABCD | Wh | Read | |||
| HR | 524doc 020C | Tariff T2 active energy (not resettable) | UINT32 | ABCD | Wh | Read | |||
| HR | 526doc 020E | Tariff T3 active energy (not resettable) | UINT32 | ABCD | Wh | Read | |||
| HR | 528doc 0210 | Tariff T4 active energy (not resettable) | UINT32 | ABCD | Wh | Read | |||
| HR | 544doc 0220 | Active energy import (not resettable) | UINT32 | ABCD | kWh | Read | |||
| HR | 546doc 0222 | Active energy export (regenerative) (not resettable) | UINT32 | ABCD | kWh | Read | |||
| HR | 548doc 0224 | Reactive energy, advance (leading) (not resettable) | UINT32 | ABCD | kvarh | Read | |||
| HR | 550doc 0226 | Reactive energy, delay (lagging) (not resettable) | UINT32 | ABCD | kvarh | Read | |||
| HR | 552doc 0228 | Total reactive energy (not resettable) | UINT32 | ABCD | kvarh | Read | |||
| HR | 554doc 022A | Tariff T1 active energy (not resettable) | UINT32 | ABCD | kWh | Read | |||
| HR | 556doc 022C | Tariff T2 active energy (not resettable) | UINT32 | ABCD | kWh | Read | |||
| HR | 558doc 022E | Tariff T3 active energy (not resettable) | UINT32 | ABCD | kWh | Read | |||
| HR | 560doc 0230 | Tariff T4 active energy (not resettable) | UINT32 | ABCD | kWh | Read | |||
| HR | 576doc 0240 | Active energy import (resettable) | UINT32 | ABCD | Wh | Read | |||
| HR | 578doc 0242 | Active energy export (regenerative) (resettable) | UINT32 | ABCD | Wh | Read | |||
| HR | 580doc 0244 | Reactive energy, advance (leading) (resettable) | UINT32 | ABCD | varh | Read | |||
| HR | 582doc 0246 | Reactive energy, delay (lagging) (resettable) | UINT32 | ABCD | varh | Read | |||
| HR | 584doc 0248 | Total reactive energy (resettable) | UINT32 | ABCD | varh | Read | |||
| HR | 586doc 024A | Tariff T1 active energy (resettable) | UINT32 | ABCD | Wh | Read | |||
| HR | 588doc 024C | Tariff T2 active energy (resettable) | UINT32 | ABCD | Wh | Read | |||
| HR | 590doc 024E | Tariff T3 active energy (resettable) | UINT32 | ABCD | Wh | Read | |||
| HR | 592doc 0250 | Tariff T4 active energy (resettable) | UINT32 | ABCD | Wh | Read | |||
| HR | 608doc 0260 | Active energy import (resettable) | UINT32 | ABCD | kWh | Read | |||
| HR | 610doc 0262 | Active energy export (regenerative) (resettable) | UINT32 | ABCD | kWh | Read | |||
| HR | 612doc 0264 | Reactive energy, advance (leading) (resettable) | UINT32 | ABCD | kvarh | Read | |||
| HR | 614doc 0266 | Reactive energy, delay (lagging) (resettable) | UINT32 | ABCD | kvarh | Read | |||
| HR | 616doc 0268 | Total reactive energy (resettable) | UINT32 | ABCD | kvarh | Read | |||
| HR | 618doc 026A | Tariff T1 active energy (resettable) | UINT32 | ABCD | kWh | Read | |||
| HR | 620doc 026C | Tariff T2 active energy (resettable) | UINT32 | ABCD | kWh | Read | |||
| HR | 622doc 026E | Tariff T3 active energy (resettable) | UINT32 | ABCD | kWh | Read | |||
| HR | 624doc 0270 | Tariff T4 active energy (resettable) | UINT32 | ABCD | kWh | Read | |||
| HR | 768doc 0300 | Converted value x1000 | Conversion value, raw is 1000x the value. | UINT32 | ABCD | × 0.001 | Read | ||
| HR | 770doc 0302 | Converted value x0.001 | Raw is 0.001x the value, for large totals. | UINT32 | ABCD | × 1000 | Read | ||
| HR | 8192doc 2000 | Phase and wire type | UINT32 | ABCD | Read/write | 0 = 1P2W; 1 = 1P3W; 2 = 3P3W; 3 = 1P2W2; 4 = 1P3W2; 5 = 3P4W | |||
| HR | 8194doc 2002 | Communication address | 1-99 for Modbus; one per circuit. | UINT32 | ABCD | Read | |||
| HR | 8212doc 2014 | CT secondary current | UINT32 | ABCD | Read/write | 0 = 1 A; 1 = 5 A | |||
| HR | 8214doc 2016 | CT primary current | Primary amps, x1. | UINT32 | ABCD | Read/write | |||
| HR | 8704doc 2200 | Protocol | UINT32 | ABCD | Read/write | 0 = CompoWay/F; 1 = Modbus | |||
| HR | 8706doc 2202 | Communication speed | UINT32 | ABCD | Read/write | 0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps | |||
| HR | 8710doc 2206 | Stop bit | UINT32 | ABCD | Read/write | 0 = 1 bit; 1 = 2 bits | |||
| HR | 8712doc 2208 | Parity | UINT32 | ABCD | Read/write | 0 = None; 1 = Odd; 2 = Even | |||
| HR | 8714doc 220A | Transmission wait time | 0-99 ms. | UINT32 | ABCD | Read/write | |||
| HR | 8718doc 220E | VT ratio | Stored x100. | UINT32 | ABCD | × 0.01 | Read/write | ||
| HR | 65535doc FFFF | Command | Write with FC06 only: command code in the high byte, 00 in the low byte. | UINT16 | Write | 768 = 0x0300: reset resettable energy; 1024 = 0x0400: move to measuring mode; 1792 = 0x0700: move to setting mode; 2304 = 0x0900: initialise resettable energy and settings; 39168 = 0x9900: restart |
Notes on this map
- Word order: the read example returns 0000 then 0960 for voltage 1 (2400 = 240.0 V), so the high word comes first (ABCD). Negative values are two's complement.
- Scaling per the address map: voltage x10, current x1000, power factor x100, frequency x10, active and reactive power x10; energy counters are x1 in the unit named.
- Each circuit of the unit is its own Modbus slave. Circuit A's address is set in MENU A2 (default 01); circuits B-D automatically take the next addresses in order. The registers here repeat for every circuit.
- Settings in the 2000-2210 range can only be read or written after the 'move to setting mode' command (0x0700 to address FFFF); send 'move to measuring mode' (0x0400) afterwards. Measured values can be read in either mode.
- Read requests are limited to 2-50 registers and only over consecutive addresses.
- Left out: pulse output, voltage selection, data length, conversion factor, LCD, alarm, tariff, model and status registers (2010-2012, 2204, 220C, 2210-240A).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Omron KM-N3-FLK on-panel power monitor
What Modbus registers does the Omron KM-N3-FLK on-panel power monitor have?
This map lists 68 registers: 68 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Omron KM-N3-FLK on-panel power monitor Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The address map prints Modbus addresses in hex and they go on the wire unchanged; the manual's example reads voltage 1 with start address 0000 and 2 registers. Each value takes two registers, so read an even count.
What byte order does the Omron KM-N3-FLK on-panel power monitor use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Omron KM-N3-FLK on-panel power monitor?
Start with HR 0 Voltage 1 (Voltage 1 (x0.1 V)); HR 6 Current 1 (Current 1 (x0.001 A)); HR 16 Active power (total) (Active power (x0.1 W)); HR 12 Power factor (Power factor); HR 14 Frequency (Frequency); HR 544 Active energy import (not resettable) (Active energy import, kWh).
How do I enable Modbus control of the Omron KM-N3-FLK on-panel power monitor?
Modbus is the default protocol (MENU 00 = MODBS). Set circuit A's communication address in MENU A2; circuits B-D follow in order.
Where is the official Omron KM-N3-FLK on-panel power monitor Modbus documentation?
The source is On-Panel Power Monitor model KM-N3-FLK Users Manual (N214-E1-04), revision 2023-03, published free by Omron at https://assets.omron.eu/downloads/latest/manual/en/n214_km-n3-flk_users_manual_en.pdf.
More Omron Modbus register maps
- Sensor (digital temperature controller)
Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
Omron E5CC, E5EC, E5AC, E5DC and E5CC-U controllers with RS-485, per the E5_C Communications Manual H175; registers present depend on model and options.
Also known as: E5CC, E5EC, E5AC, E5DC, E5CC-U, E5@C, E5_C - Power meter (multi-circuit power monitor)
Omron KM-N2-FLK multi-circuit power monitor
Omron KM-N2-FLK power monitor (catalog N200-E1-04).
Also known as: KM-N2-FLK, KM-N2
Other power & energy meters register maps
- Sensor (counter / rate panel meter)
Red Lion PAX2D counter / rate panel meter (Modbus)
PAX2D dual counter / rate meter, per register table LP0930A (4/11/13).
Also known as: PAX2D, PAX2 D, Red Lion PAX2D counter - Energy meter
Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters
Rishabh RISH EC43xx and ER43xx DIN-rail digital energy meters with RS-485 Modbus, per interface definition DMAN-00IM-09xx Rev. F (11/25).
Also known as: EC4311, EC4321, ER4311, ER4321, RISH EC43X1, EC43XX, ER43XX - Energy meter (DC)
Rishabh Instruments RISH EM DC 6000 programmable DC energy meter
Rishabh RISH EM DC 6000 single-channel programmable DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0862 Rev. 0 (12/2020).
Also known as: RISH EM DC 6000, EMDC 6000, EM DC6000 - Power meter
Rishabh Instruments RISH Master 3440i / 3440iDL (class 0.2S) touch-screen meter
Rishabh RISH Master 3440i and 3440iDL touch-screen class 0.2S meters with RS-485 Modbus, per interface definition DMAN-00IM-0712 Rev. F (10/2026).
Also known as: RISH Master 3440i, RISH Master 3440iDL, RM3440i, RM3440iDL - Power meter (revenue / power quality)
SATEC EM235 / PM335 PRO advanced power meter
SATEC EM235 and PM335 PRO advanced power meters, per Modbus reference guide BG0613 Rev. A8 (Sept 2025).
Also known as: EM235, PM335 PRO, PM335PRO, SATEC EM235, SATEC PM335 - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203
All power & energy meters Modbus register maps →
Source: On-Panel Power Monitor model KM-N3-FLK Users Manual · N214-E1-04 · rev. 2023-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.