Sensor (counter / rate panel meter) · Modbus register map

Red Lion PAX2D counter / rate panel meter (Modbus) Modbus register map

Updated 17 November 2026

Short answer

The PAX2D is a counter and rate meter with three counters, three rate channels, up to four setpoint outputs and an optional linear output card. Its serial port runs Modbus RTU or Modbus ASCII. This map covers the frequently used block (counts, rates, min/max, setpoints, scale factors, count loads, manual output control) and the counter mode, decimal point and scaling settings.

This page lists 34 Modbus registers for the Red Lion PAX2D counter / rate panel meter (Modbus) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Red Lion’s own free documentation (linked below) and checked against it.

Manufacturer
Red Lion
Model
PAX2D counter / rate panel meter (Modbus)
Equipment type
Sensor (counter / rate panel meter)
Registers
34 (31 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
247
Default serial
38400 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
PAX2D, PAX2 D, Red Lion PAX2D counter
Source document
PAX2D Modbus Register Table · LP0930A · rev. 2013-04-11 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Red Lion PAX2D counter / rate panel meter (Modbus)

Integration in brief

Read 40001-40016 in one request for counts, rates and min/max, then apply the decimal point settings. Write setpoints as two registers, high word first; take manual control of outputs through the MMR and SOR.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Counter A valueINT32 ABCDCounter A valueRead/write
HR 6Rate A valueINT32 ABCDRate A valueRead
HR 16Setpoint 1 valueINT32 ABCDSetpoint 1Read/write
HR 36Setpoint output register (SOR)BITMAP16Setpoint output statesRead/write
HR 121Counter A decimal pointUINT16Counter A decimal pointRead/write

Enable Modbus control & writes

Set the serial Type register (40482) to 1 for Modbus RTU or 2 for Modbus ASCII. The factory setting is 2 (Modbus ASCII), so change it for an RTU master. Port settings 40481-40487 only take effect after writing 1 to Load Serial Settings (40490).

Byte order & addressing

Network setup

Watch out for

Red Lion PAX2D counter / rate panel meter (Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

34 of 34 shown
Red Lion PAX2D counter / rate panel meter (Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Counter A valueDisplay digits without the decimal point; see the decimal point setting.INT32ABCDRead/write
HR2doc 40003Counter B valueDisplay digits without the decimal point; see the decimal point setting.INT32ABCDRead/write
HR4doc 40005Counter C valueDisplay digits without the decimal point; see the decimal point setting.INT32ABCDRead/write
HR6doc 40007Rate A valueDisplay digits without the decimal point; see the decimal point setting.INT32ABCDRead
HR8doc 40009Rate B valueDisplay digits without the decimal point; see the decimal point setting.INT32ABCDRead
HR10doc 40011Rate C valueDisplay digits without the decimal point; see the decimal point setting.INT32ABCDRead
HR12doc 40013Maximum (Hi) valueDisplay digits without the decimal point; see the decimal point setting.INT32ABCDRead/write
HR14doc 40015Minimum (Lo) valueDisplay digits without the decimal point; see the decimal point setting.INT32ABCDRead/write
HR16doc 40017Setpoint 1 valueActive list (A or B). Display digits without the decimal point; see the decimal point setting.INT32ABCDRead/write
HR18doc 40019Setpoint 2 valueActive list (A or B). Display digits without the decimal point; see the decimal point setting.INT32ABCDRead/write
HR20doc 40021Setpoint 3 valueActive list (A or B). Display digits without the decimal point; see the decimal point setting.INT32ABCDRead/write
HR22doc 40023Setpoint 4 valueActive list (A or B). Display digits without the decimal point; see the decimal point setting.INT32ABCDRead/write
HR24doc 40025Counter A scale factorActive list (A or B); 1-999999, 100000 = 1.00000.INT32ABCD× 0.00001Read/write
HR26doc 40027Counter B scale factorActive list (A or B); 1-999999, 100000 = 1.00000.INT32ABCD× 0.00001Read/write
HR28doc 40029Counter C scale factorActive list (A or B); 1-999999, 100000 = 1.00000.INT32ABCD× 0.00001Read/write
HR30doc 40031Counter A count loadActive list (A or B). Display digits without the decimal point; see the decimal point setting.INT32ABCDRead/write
HR32doc 40033Counter B count loadActive list (A or B). Display digits without the decimal point; see the decimal point setting.INT32ABCDRead/write
HR34doc 40035Counter C count loadActive list (A or B). Display digits without the decimal point; see the decimal point setting.INT32ABCDRead/write
HR36doc 40037Setpoint output register (SOR)Output states; writable only for outputs in manual (MMR).BITMAP16Read/writebit 0 = S4 on; bit 1 = S3 on; bit 2 = S2 on; bit 3 = S1 on
HR37doc 40038Manual mode register (MMR)1 = manual, 0 = auto.BITMAP16Read/writebit 0 = Linear output manual; bit 1 = S4 manual; bit 2 = S3 manual; bit 3 = S2 manual; bit 4 = S1 manual
HR38doc 40039Reset output registerWrite 1 to reset an output; the bit self-clears.BITMAP16Read/writebit 0 = Reset S4; bit 1 = Reset S3; bit 2 = Reset S2; bit 3 = Reset S1
HR39doc 40040Analog output register (AOR)0-4095; used only when MMR bit 0 = 1.UINT16Read/write
HR120doc 40121Counter A operating modeUINT16Read/write0 = None; 1 = Count; 2 = Count up/down; 3 = Dual count up/down; 4 = Add/Add; 5 = Add/Sub; 6 = Quad x1; 7 = Quad x2; 8 = Quad x4; 9 = Dual quad x1; 10 = Dual quad x2; 11 = Count x2; 12 = Count up/down x2; 13 = Dual count up/down x2
HR121doc 40122Counter A decimal pointUINT16Read/write0 = 0; 1 = 0.0; 2 = 0.00; 3 = 0.000; 4 = 0.0000; 5 = 0.00000
HR122doc 40123Counter A scale multiplierUINT16Read/write0 = x1; 1 = x0.1; 2 = x0.01; 3 = x10
HR123doc 40124Counter A reset actionUINT16Read/write0 = Reset to zero; 1 = Reset to count load
HR124doc 40125Counter A reset at power-upUINT16Read/write0 = No; 1 = Yes
HR125doc 40126Input A active count edgeUINT16Read/write0 = Falling edge; 1 = Rising edge
HR130doc 40131Counter B operating modeUINT16Read/write0 = None; 1 = Batch; 2 = Count; 3 = Dual count up/down; 4 = Dual quad x1; 5 = Dual quad x2; 6 = Count x2; 7 = Dual count up/down x2
HR131doc 40132Counter B decimal pointUINT16Read/write0 = 0; 1 = 0.0; 2 = 0.00; 3 = 0.000; 4 = 0.0000; 5 = 0.00000
HR132doc 40133Counter B scale multiplierUINT16Read/write0 = x1; 1 = x0.1; 2 = x0.01; 3 = x10
HR140doc 40141Counter C operating modeUINT16Read/write0 = None; 1 = Counter A; 2 = Counter B; 3 = Add (A+B); 4 = Subtract (A-B); 5 = Batch; 6 = Slave
HR141doc 40142Counter C decimal pointUINT16Read/write0 = 0; 1 = 0.0; 2 = 0.00; 3 = 0.000; 4 = 0.0000; 5 = 0.00000
HR142doc 40143Counter C scale multiplierUINT16Read/write0 = x1; 1 = x0.1; 2 = x0.01; 3 = x10

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Red Lion PAX2D counter / rate panel meter (Modbus)

What Modbus registers does the Red Lion PAX2D counter / rate panel meter (Modbus) have?

This map lists 34 registers: 34 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Red Lion PAX2D counter / rate panel meter (Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as 4xxxx holding registers (40001 = first). Request 40001 as address 0.

What byte order does the Red Lion PAX2D counter / rate panel meter (Modbus) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Red Lion PAX2D counter / rate panel meter (Modbus)?

Start with HR 0 Counter A value (Counter A value); HR 6 Rate A value (Rate A value); HR 16 Setpoint 1 value (Setpoint 1); HR 36 Setpoint output register (SOR) (Setpoint output states); HR 121 Counter A decimal point (Counter A decimal point).

How do I enable Modbus control of the Red Lion PAX2D counter / rate panel meter (Modbus)?

Set the serial Type register (40482) to 1 for Modbus RTU or 2 for Modbus ASCII. The factory setting is 2 (Modbus ASCII), so change it for an RTU master. Port settings 40481-40487 only take effect after writing 1 to Load Serial Settings (40490).

Where is the official Red Lion PAX2D counter / rate panel meter (Modbus) Modbus documentation?

The source is PAX2D Modbus Register Table (LP0930A), revision 2013-04-11. Red Lion doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.logic-control.com/docs/red-lion/Datasheets/PAX2D%20Modbus%20Register%20Table.pdf. It may be an older revision, so check it against the live unit.

More Red Lion Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: PAX2D Modbus Register Table · LP0930A · rev. 2013-04-11 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.