- PAX2D counter / rate panel meter (Modbus)
Sensor (counter / rate panel meter) · Modbus register map
Red Lion PAX2D counter / rate panel meter (Modbus) Modbus register map
Updated 17 November 2026
The PAX2D is a counter and rate meter with three counters, three rate channels, up to four setpoint outputs and an optional linear output card. Its serial port runs Modbus RTU or Modbus ASCII. This map covers the frequently used block (counts, rates, min/max, setpoints, scale factors, count loads, manual output control) and the counter mode, decimal point and scaling settings.
This page lists 34 Modbus registers for the Red Lion PAX2D counter / rate panel meter (Modbus) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Red Lion’s own free documentation (linked below) and checked against it.
- Manufacturer
- Red Lion
- Model
- PAX2D counter / rate panel meter (Modbus)
- Equipment type
- Sensor (counter / rate panel meter)
- Registers
- 34 (31 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 247
- Default serial
- 38400 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- PAX2D, PAX2 D, Red Lion PAX2D counter
Integration notes: Red Lion PAX2D counter / rate panel meter (Modbus)
Read 40001-40016 in one request for counts, rates and min/max, then apply the decimal point settings. Write setpoints as two registers, high word first; take manual control of outputs through the MMR and SOR.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Counter A value | INT32 ABCD | Counter A value | Read/write |
| HR 6 | Rate A value | INT32 ABCD | Rate A value | Read |
| HR 16 | Setpoint 1 value | INT32 ABCD | Setpoint 1 | Read/write |
| HR 36 | Setpoint output register (SOR) | BITMAP16 | Setpoint output states | Read/write |
| HR 121 | Counter A decimal point | UINT16 | Counter A decimal point | Read/write |
Enable Modbus control & writes
Set the serial Type register (40482) to 1 for Modbus RTU or 2 for Modbus ASCII. The factory setting is 2 (Modbus ASCII), so change it for an RTU master. Port settings 40481-40487 only take effect after writing 1 to Load Serial Settings (40490).
Byte order & addressing
- Values carry no decimal point; scale them with the decimal point registers.
- The Slave ID block (41001+) reports a maximum of 64 registers per read or write.
Network setup
- Factory settings: Modbus ASCII, 38400 baud, 8 data bits, no parity, address 247 (Modbus range 1-247).
- Baud (40483), data bits (40484), parity (40485), address (40486) and transmit delay (40487, 1 = 1 ms) are registers; write 1 to 40490 to apply them, then switch the master to the new settings.
Watch out for
- Counter values are writable; a write overwrites the count.
- Out of the box the port speaks Modbus ASCII, not RTU.
Red Lion PAX2D counter / rate panel meter (Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Counter A value | Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read/write | |||
| HR | 2doc 40003 | Counter B value | Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read/write | |||
| HR | 4doc 40005 | Counter C value | Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read/write | |||
| HR | 6doc 40007 | Rate A value | Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read | |||
| HR | 8doc 40009 | Rate B value | Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read | |||
| HR | 10doc 40011 | Rate C value | Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read | |||
| HR | 12doc 40013 | Maximum (Hi) value | Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read/write | |||
| HR | 14doc 40015 | Minimum (Lo) value | Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read/write | |||
| HR | 16doc 40017 | Setpoint 1 value | Active list (A or B). Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read/write | |||
| HR | 18doc 40019 | Setpoint 2 value | Active list (A or B). Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read/write | |||
| HR | 20doc 40021 | Setpoint 3 value | Active list (A or B). Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read/write | |||
| HR | 22doc 40023 | Setpoint 4 value | Active list (A or B). Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read/write | |||
| HR | 24doc 40025 | Counter A scale factor | Active list (A or B); 1-999999, 100000 = 1.00000. | INT32 | ABCD | × 0.00001 | Read/write | ||
| HR | 26doc 40027 | Counter B scale factor | Active list (A or B); 1-999999, 100000 = 1.00000. | INT32 | ABCD | × 0.00001 | Read/write | ||
| HR | 28doc 40029 | Counter C scale factor | Active list (A or B); 1-999999, 100000 = 1.00000. | INT32 | ABCD | × 0.00001 | Read/write | ||
| HR | 30doc 40031 | Counter A count load | Active list (A or B). Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read/write | |||
| HR | 32doc 40033 | Counter B count load | Active list (A or B). Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read/write | |||
| HR | 34doc 40035 | Counter C count load | Active list (A or B). Display digits without the decimal point; see the decimal point setting. | INT32 | ABCD | Read/write | |||
| HR | 36doc 40037 | Setpoint output register (SOR) | Output states; writable only for outputs in manual (MMR). | BITMAP16 | Read/write | bit 0 = S4 on; bit 1 = S3 on; bit 2 = S2 on; bit 3 = S1 on | |||
| HR | 37doc 40038 | Manual mode register (MMR) | 1 = manual, 0 = auto. | BITMAP16 | Read/write | bit 0 = Linear output manual; bit 1 = S4 manual; bit 2 = S3 manual; bit 3 = S2 manual; bit 4 = S1 manual | |||
| HR | 38doc 40039 | Reset output register | Write 1 to reset an output; the bit self-clears. | BITMAP16 | Read/write | bit 0 = Reset S4; bit 1 = Reset S3; bit 2 = Reset S2; bit 3 = Reset S1 | |||
| HR | 39doc 40040 | Analog output register (AOR) | 0-4095; used only when MMR bit 0 = 1. | UINT16 | Read/write | ||||
| HR | 120doc 40121 | Counter A operating mode | UINT16 | Read/write | 0 = None; 1 = Count; 2 = Count up/down; 3 = Dual count up/down; 4 = Add/Add; 5 = Add/Sub; 6 = Quad x1; 7 = Quad x2; 8 = Quad x4; 9 = Dual quad x1; 10 = Dual quad x2; 11 = Count x2; 12 = Count up/down x2; 13 = Dual count up/down x2 | ||||
| HR | 121doc 40122 | Counter A decimal point | UINT16 | Read/write | 0 = 0; 1 = 0.0; 2 = 0.00; 3 = 0.000; 4 = 0.0000; 5 = 0.00000 | ||||
| HR | 122doc 40123 | Counter A scale multiplier | UINT16 | Read/write | 0 = x1; 1 = x0.1; 2 = x0.01; 3 = x10 | ||||
| HR | 123doc 40124 | Counter A reset action | UINT16 | Read/write | 0 = Reset to zero; 1 = Reset to count load | ||||
| HR | 124doc 40125 | Counter A reset at power-up | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 125doc 40126 | Input A active count edge | UINT16 | Read/write | 0 = Falling edge; 1 = Rising edge | ||||
| HR | 130doc 40131 | Counter B operating mode | UINT16 | Read/write | 0 = None; 1 = Batch; 2 = Count; 3 = Dual count up/down; 4 = Dual quad x1; 5 = Dual quad x2; 6 = Count x2; 7 = Dual count up/down x2 | ||||
| HR | 131doc 40132 | Counter B decimal point | UINT16 | Read/write | 0 = 0; 1 = 0.0; 2 = 0.00; 3 = 0.000; 4 = 0.0000; 5 = 0.00000 | ||||
| HR | 132doc 40133 | Counter B scale multiplier | UINT16 | Read/write | 0 = x1; 1 = x0.1; 2 = x0.01; 3 = x10 | ||||
| HR | 140doc 40141 | Counter C operating mode | UINT16 | Read/write | 0 = None; 1 = Counter A; 2 = Counter B; 3 = Add (A+B); 4 = Subtract (A-B); 5 = Batch; 6 = Slave | ||||
| HR | 141doc 40142 | Counter C decimal point | UINT16 | Read/write | 0 = 0; 1 = 0.0; 2 = 0.00; 3 = 0.000; 4 = 0.0000; 5 = 0.00000 | ||||
| HR | 142doc 40143 | Counter C scale multiplier | UINT16 | Read/write | 0 = x1; 1 = x0.1; 2 = x0.01; 3 = x10 |
Notes on this map
- No direct Red Lion download of this table was found; the link is an unaltered copy of the Red Lion table (LP0930A) on a distributor's file host.
- 32-bit values are a Hi word register followed by a Lo word register (ABCD); limits such as -999999999 show they are signed.
- Counts, rates, setpoints and count loads are the displayed digits without the decimal point (the A/B list section says 1 = 1 in the least significant digit, decimal point disregarded).
- Scale factor scaling (1 = 0.00001, decimal point fixed) is printed in the A/B list section for the same parameter and applied here to the active-list copies.
- Left out: A/B list copies 40041-40100, rate, user input, setpoint output, display and port settings later in the table (the serial port registers 40482-40490 are described under integration).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Red Lion PAX2D counter / rate panel meter (Modbus)
What Modbus registers does the Red Lion PAX2D counter / rate panel meter (Modbus) have?
This map lists 34 registers: 34 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Red Lion PAX2D counter / rate panel meter (Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as 4xxxx holding registers (40001 = first). Request 40001 as address 0.
What byte order does the Red Lion PAX2D counter / rate panel meter (Modbus) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Red Lion PAX2D counter / rate panel meter (Modbus)?
Start with HR 0 Counter A value (Counter A value); HR 6 Rate A value (Rate A value); HR 16 Setpoint 1 value (Setpoint 1); HR 36 Setpoint output register (SOR) (Setpoint output states); HR 121 Counter A decimal point (Counter A decimal point).
How do I enable Modbus control of the Red Lion PAX2D counter / rate panel meter (Modbus)?
Set the serial Type register (40482) to 1 for Modbus RTU or 2 for Modbus ASCII. The factory setting is 2 (Modbus ASCII), so change it for an RTU master. Port settings 40481-40487 only take effect after writing 1 to Load Serial Settings (40490).
Where is the official Red Lion PAX2D counter / rate panel meter (Modbus) Modbus documentation?
The source is PAX2D Modbus Register Table (LP0930A), revision 2013-04-11. Red Lion doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.logic-control.com/docs/red-lion/Datasheets/PAX2D%20Modbus%20Register%20Table.pdf. It may be an older revision, so check it against the live unit.
More Red Lion Modbus register maps
- Thermostat / temperature and process PID controller
Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII)
PAX2C version 2.0 register table (LP0905F, 2017-02-27); the FlexCard (PX2FCA0/PX2FCA1) blocks of the same table are not included.
Also known as: PAX2CHZVR, PAX2C00000, PX2FCA0, PX2FCA1 - Sensor (counter / rate panel meter)
Red Lion PAXI counter / rate panel meter (Modbus)
PAXI counter/rate meters with a Modbus serial card, per register table LP0897A (revised 7/10/12).
Also known as: PAXI, PAX I, Red Lion PAXI counter
Other power & energy meters register maps
- Energy meter
Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters
Rishabh RISH EC43xx and ER43xx DIN-rail digital energy meters with RS-485 Modbus, per interface definition DMAN-00IM-09xx Rev. F (11/25).
Also known as: EC4311, EC4321, ER4311, ER4321, RISH EC43X1, EC43XX, ER43XX - Energy meter (DC)
Rishabh Instruments RISH EM DC 6000 programmable DC energy meter
Rishabh RISH EM DC 6000 single-channel programmable DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0862 Rev. 0 (12/2020).
Also known as: RISH EM DC 6000, EMDC 6000, EM DC6000 - Power meter
Rishabh Instruments RISH Master 3440i / 3440iDL (class 0.2S) touch-screen meter
Rishabh RISH Master 3440i and 3440iDL touch-screen class 0.2S meters with RS-485 Modbus, per interface definition DMAN-00IM-0712 Rev. F (10/2026).
Also known as: RISH Master 3440i, RISH Master 3440iDL, RM3440i, RM3440iDL - Power meter (revenue / power quality)
SATEC EM235 / PM335 PRO advanced power meter
SATEC EM235 and PM335 PRO advanced power meters, per Modbus reference guide BG0613 Rev. A8 (Sept 2025).
Also known as: EM235, PM335 PRO, PM335PRO, SATEC EM235, SATEC PM335 - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Siemens SICAM P power meter (Modbus RTU/ASCII)
SICAM P (7KG7xxx) power meters with the Modbus serial interface, per manual E50417-B1076-C241-A5 (release 11.2012).
Also known as: 7KG7750, 7KG7751, 7KG7755, SICAM P50, SICAM P55, 7KG7610, 7KG7660
All power & energy meters Modbus register maps →
Source: PAX2D Modbus Register Table · LP0930A · rev. 2013-04-11 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.