Sensor (counter / rate panel meter) · Modbus register map

Red Lion PAXI counter / rate panel meter (Modbus) Modbus register map

Updated 17 November 2026

Short answer

The PAXI is a counter and rate indicator with three counters (A, B, C), a rate channel, up to four setpoint outputs and an optional linear output card. Its serial port can run Modbus RTU or Modbus ASCII; this map covers the frequently used block (counts, rate, min/max, scale factors, count loads, setpoints, manual output control) plus counter A and rate settings.

This page lists 34 Modbus registers for the Red Lion PAXI counter / rate panel meter (Modbus) — 34 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Red Lion’s own free documentation (linked below) and checked against it.

Manufacturer
Red Lion
Model
PAXI counter / rate panel meter (Modbus)
Equipment type
Sensor (counter / rate panel meter)
Registers
34 (34 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
247
Default serial
38400 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
PAXI, PAX I, Red Lion PAXI counter
Source document
PAXI Modbus Register Table · LP0897A · rev. 2012-07-10 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Red Lion PAXI counter / rate panel meter (Modbus)

Integration in brief

Read 40001-40012 in one request for counts, rate and min/max (high word first). Change setpoints or count loads by writing both words of 40019-40032; take direct control of outputs by setting MMR bits and then writing the SOR.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Counter A valueINT32 ABCDCounter A valueRead/write
HR 6Rate valueINT32 ABCDRate valueRead/write
HR 24Setpoint 1 valueINT32 ABCDSetpoint 1Read/write
HR 37Setpoint output register (SOR)BITMAP16Setpoint output statesRead/write
HR 102Counter A decimal pointUINT16Counter A decimal pointRead/write
HR 163Rate decimal pointUINT16Rate decimal pointRead/write

Enable Modbus control & writes

Set Serial Protocol (40301) to 1 for Modbus RTU or 2 for Modbus ASCII (factory setting is RTU). Serial settings 40301-40306 only take effect after writing 1 to Load Serial Settings (40309).

Byte order & addressing

Network setup

Watch out for

Red Lion PAXI counter / rate panel meter (Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

34 of 34 shown
Red Lion PAXI counter / rate panel meter (Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Counter A valueIn display units without the decimal point (see the decimal point setting).INT32ABCDRead/write
HR2doc 40003Counter B valueIn display units without the decimal point (see the decimal point setting).INT32ABCDRead/write
HR4doc 40005Counter C valueIn display units without the decimal point (see the decimal point setting).INT32ABCDRead/write
HR6doc 40007Rate valueIn display units without the decimal point (see the decimal point setting).INT32ABCDRead/write
HR8doc 40009Minimum (Lo) valueIn display units without the decimal point (see the decimal point setting).INT32ABCDRead/write
HR10doc 40011Maximum (Hi) valueIn display units without the decimal point (see the decimal point setting).INT32ABCDRead/write
HR12doc 40013Counter A scale factorActive list (A or B); 1-999999, factory 100000 = 1.00000.INT32ABCD× 0.00001Read/write
HR14doc 40015Counter B scale factorActive list (A or B); 1-999999, factory 100000 = 1.00000.INT32ABCD× 0.00001Read/write
HR16doc 40017Counter C scale factorActive list (A or B); 1-999999, factory 100000 = 1.00000.INT32ABCD× 0.00001Read/write
HR18doc 40019Counter A count loadActive list (A or B); display units without the decimal point.INT32ABCDRead/write
HR20doc 40021Counter B count loadActive list (A or B); display units without the decimal point.INT32ABCDRead/write
HR22doc 40023Counter C count loadActive list (A or B); display units without the decimal point.INT32ABCDRead/write
HR24doc 40025Setpoint 1 valueActive list (A or B); display units without the decimal point.INT32ABCDRead/write
HR26doc 40027Setpoint 2 valueActive list (A or B); display units without the decimal point.INT32ABCDRead/write
HR28doc 40029Setpoint 3 valueActive list (A or B); display units without the decimal point.INT32ABCDRead/write
HR30doc 40031Setpoint 4 valueActive list (A or B); display units without the decimal point.INT32ABCDRead/write
HR35doc 40036Manual mode register (MMR)1 = manual, 0 = auto for each output.BITMAP16Read/writebit 0 = Linear output manual; bit 1 = S4 manual; bit 2 = S3 manual; bit 3 = S2 manual; bit 4 = S1 manual
HR36doc 40037Analog output register (AOR)0-4095; drives the linear output card only when MMR bit 0 = 1.UINT16Read/write
HR37doc 40038Setpoint output register (SOR)Output states; writable only for outputs in manual (MMR).BITMAP16Read/writebit 0 = S4 on; bit 1 = S3 on; bit 2 = S2 on; bit 3 = S1 on
HR38doc 40039Reset output registerWrite 1 to reset an output; the bit self-clears.BITMAP16Read/writebit 0 = Reset S4; bit 1 = Reset S3; bit 2 = Reset S2; bit 3 = Reset S1
HR100doc 40101Counter A operating modeUINT16Read/write0 = None; 1 = Count; 2 = Count up/down; 3 = Dual count up/down; 4 = Quad x1; 5 = Quad x2; 6 = Quad x4; 7 = Dual quad x1; 8 = Dual quad x2; 9 = Count x2; 10 = Count up/down x2; 11 = Dual count up/down x2
HR101doc 40102Counter A reset actionUINT16Read/write0 = Reset to zero; 1 = Reset to count load value
HR102doc 40103Counter A decimal pointUINT16Read/write0 = 0; 1 = 0.0; 2 = 0.00; 3 = 0.000; 4 = 0.0000; 5 = 0.00000
HR103doc 40104Counter A scale multiplierUINT16Read/write0 = x1; 1 = x0.1; 2 = x0.01
HR104doc 40105Counter A reset at power-upUINT16Read/write0 = No; 1 = Yes
HR105doc 40106Prescaler output enableUINT16Read/write0 = No; 1 = Yes
HR106doc 40107Prescaler scale value1-10000.UINT16× 0.0001Read/write
HR158doc 40159Security code0-999.UINT16Read/write
HR160doc 40161Rate assignmentUINT16Read/write0 = No; 1 = Rate A; 2 = Rate B
HR161doc 40162Rate low update timeUINT16× 0.1sRead/write
HR162doc 40163Rate high update timeUINT16× 0.1sRead/write
HR163doc 40164Rate decimal pointUINT16Read/write0 = 0; 1 = 0.0; 2 = 0.00; 3 = 0.000; 4 = 0.0000
HR167doc 40168Max (Hi) capture delayUINT16× 0.1sRead/write
HR168doc 40169Min (Lo) capture delayUINT16× 0.1sRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Red Lion PAXI counter / rate panel meter (Modbus)

What Modbus registers does the Red Lion PAXI counter / rate panel meter (Modbus) have?

This map lists 34 registers: 34 holding registers. 34 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Red Lion PAXI counter / rate panel meter (Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as 4xxxx holding registers (40001 = first). Request 40001 as address 0.

What byte order does the Red Lion PAXI counter / rate panel meter (Modbus) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Red Lion PAXI counter / rate panel meter (Modbus)?

Start with HR 0 Counter A value (Counter A value); HR 6 Rate value (Rate value); HR 24 Setpoint 1 value (Setpoint 1); HR 37 Setpoint output register (SOR) (Setpoint output states); HR 102 Counter A decimal point (Counter A decimal point); HR 163 Rate decimal point (Rate decimal point).

How do I enable Modbus control of the Red Lion PAXI counter / rate panel meter (Modbus)?

Set Serial Protocol (40301) to 1 for Modbus RTU or 2 for Modbus ASCII (factory setting is RTU). Serial settings 40301-40306 only take effect after writing 1 to Load Serial Settings (40309).

Where is the official Red Lion PAXI counter / rate panel meter (Modbus) Modbus documentation?

The source is PAXI Modbus Register Table (LP0897A), revision 2012-07-10. Red Lion doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.logic-control.com/docs/red-lion/Datasheets/PAXI%20Modbus%20Register%20Table.pdf. It may be an older revision, so check it against the live unit.