Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters Modbus register map

Updated 19 November 2026

Short answer

Single-phase DIN-rail energy meters from Rishabh in direct-connected (ED), CT-connected (EC) and RJ12 CT (ER) versions; the Modbus variants have an RS-485 port speaking Modbus RTU. Every measured value is an IEEE 754 float in two registers, readable as input registers from 30001 or as holding registers at the same offset from 40001. This map covers voltage, current, power, PF, frequency, demands, total/tariff/partial energies and the main setup registers.

This page lists 84 Modbus registers for the Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.

Manufacturer
Rishabh Instruments
Model
RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters
Equipment type
Energy meter
Registers
84 (5 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RISH ED11X1, RISH EC11X1, RISH ER11X1, ED1111, EC1111, ER1111, RISH ED11XX, RISH EC11XX, RISH ER11XX
Source document
Operating Manual RISH ED11XX / EC11XX / ER11XX DIN rail mount Single Phase AC Energy Meter · DMAN-00IM-1071 Rev. M · rev. 09/26
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters

Integration in brief

Read 30001-30038 for instantaneous values and 30107-30142 for energies with FC04 (or FC03 at 40001+) and decode each register pair as a big-endian float.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0VoltageFLOAT32 ABCDVoltageRead
IR 6CurrentFLOAT32 ABCDCurrentRead
IR 12Active PowerFLOAT32 ABCDActive powerRead
IR 30Power FactorFLOAT32 ABCDPower factorRead
IR 70FrequencyFLOAT32 ABCDFrequencyRead
IR 108Active Import EnergyFLOAT32 ABCDActive import energy (kWh)Read

Enable Modbus control & writes

Only the x1 (Modbus) variants have RS-485. Set address and baud/parity from the front-panel setup (address 001 and 9600 baud, no parity by default; check stop bits, see notes) or via 46025/46027.

Byte order & addressing

Network setup

Watch out for

Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

84 of 84 shown
Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001VoltageFLOAT32ABCDVRead
IR6doc 30007CurrentFLOAT32ABCDARead
IR12doc 30013Active PowerFLOAT32ABCDWRead
IR18doc 30019Apparent PowerFLOAT32ABCDVARead
IR24doc 30025Reactive PowerFLOAT32ABCDVArRead
IR30doc 30031Power FactorFLOAT32ABCDRead
IR70doc 30071FrequencyFLOAT32ABCDHzRead
IR72doc 30073W Import DemandFLOAT32ABCDWRead
IR74doc 30075W Import Max DemandFLOAT32ABCDWRead
IR76doc 30077W Export DemandFLOAT32ABCDWRead
IR78doc 30079W Exp. Max DemandFLOAT32ABCDWRead
IR80doc 30081var Imp.\ Ind DemandFLOAT32ABCDVArRead
IR82doc 30083var Imp.\ Ind Max DemandFLOAT32ABCDVArRead
IR86doc 30087var Exp. \ Cap Max DemandFLOAT32ABCDVArRead
IR88doc 30089va Imp. DemandFLOAT32ABCDVARead
IR90doc 30091va Imp. Max DemandFLOAT32ABCDVARead
IR92doc 30093va Exp. DemandFLOAT32ABCDVARead
IR94doc 30095va Exp. Max DemandFLOAT32ABCDVARead
IR96doc 30097Current Imp. DemandFLOAT32ABCDARead
IR98doc 30099Current Imp Max. DemandFLOAT32ABCDARead
IR106doc 30107Active Import Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR108doc 30109Active Import EnergyFLOAT32ABCDkWhRead
IR110doc 30111Active Export Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR112doc 30113Active Export EnergyFLOAT32ABCDkWhRead
IR114doc 30115Reactive Import Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR116doc 30117Reactive Import EnergyFLOAT32ABCDkVArhRead
IR118doc 30119Reactive Export Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR120doc 30121Reactive Export EnergyFLOAT32ABCDkVArhRead
IR130doc 30131Total Active Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR132doc 30133Total Active EnergyFLOAT32ABCDkWhRead
IR134doc 30135Total Reactive Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR136doc 30137Total Reactive EnergyFLOAT32ABCDkVArhRead
IR138doc 30139Total Apparent Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR140doc 30141Total Apparent EnergyFLOAT32ABCDkVAhRead
IR142doc 30143T1 Active Import Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR144doc 30145T1 Active Import EnergyFLOAT32ABCDkWhRead
IR146doc 30147T1 Active Export Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR148doc 30149T1 Active Export EnergyFLOAT32ABCDkWhRead
IR150doc 30151T1 Reactive Import Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR152doc 30153T1 Reactive Import EnergyFLOAT32ABCDkVArhRead
IR154doc 30155T1 Reactive Export Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR156doc 30157T1 Reactive Export EnergyFLOAT32ABCDkVArhRead
IR166doc 30167T1 Total Active Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR168doc 30169T1 Total Active EnergyFLOAT32ABCDkWhRead
IR170doc 30171T1 Total Reactive Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR172doc 30173T1 Total Reactive EnergyFLOAT32ABCDkVArhRead
IR174doc 30175T1 Total Apparent Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR176doc 30177T1 Total Apparent EnergyFLOAT32ABCDkVAhRead
IR178doc 30179T2 Active Import Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR180doc 30181T2 Active Import EnergyFLOAT32ABCDkWhRead
IR182doc 30183T2 Active Export Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR184doc 30185T2 Active Export EnergyFLOAT32ABCDkWhRead
IR186doc 30187T2 Reactive Import Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR188doc 30189T2 Reactive Import EnergyFLOAT32ABCDkVArhRead
IR190doc 30191T2 Reactive Export Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR192doc 30193T2 Reactive Export EnergyFLOAT32ABCDkVArhRead
IR202doc 30203T2 Total Active Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR204doc 30205T2 Total Active EnergyFLOAT32ABCDkWhRead
IR206doc 30207T2 Total Reactive Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR208doc 30209T2 Total Reactive EnergyFLOAT32ABCDkVArhRead
IR210doc 30211T2 Total Apparent Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR212doc 30213T2 Total Apparent EnergyFLOAT32ABCDkVAhRead
IR214doc 30215Partial Active Import Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR218doc 30219Partial Active Export Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR220doc 30221Partial Active Export EnergyFLOAT32ABCDkWhRead
IR222doc 30223Partial Reactive Import Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR224doc 30225Partial Reactive Import EnergyFLOAT32ABCDkVArhRead
IR226doc 30227Partial Reactive Export Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR228doc 30229Partial Reactive Export EnergyFLOAT32ABCDkVArhRead
IR238doc 30239Partial Total Active Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR240doc 30241Partial Total Active EnergyFLOAT32ABCDkWhRead
IR242doc 30243Partial Total Reactive Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR244doc 30245Partial Total Reactive EnergyUnit misprinted in the manual; reactive energy.FLOAT32ABCDRead
IR246doc 30247Partial Total Apparent Energy Overflow CountRoll-overs of the matching energy register.FLOAT32ABCDRead
IR248doc 30249Partial Total Apparent EnergyFLOAT32ABCDkVAhRead
IR254doc 30255No of InterruptsFLOAT32ABCDRead
IR256doc 30257Impulse RateFLOAT32ABCDRead
IR260doc 30261Tariff StatusFLOAT32ABCDRead
IR262doc 30263Current DirectionFLOAT32ABCDRead0 = Current in the marked direction; 1 = Current reversed
HR6002doc 46003Demand integration timeDemand period in minutes.FLOAT32ABCDRead/write5 = 5 min; 10 = 10 min; 15 = 15 min; 30 = 30 min
HR6006doc 46007Total energy counter formulaFLOAT32ABCDRead/write1 = Import only; 2 = Export only; 3 = Import + export
HR6008doc 46009Import/export reactive energy formulaFLOAT32ABCDRead/write1 = Import/export (Q1+Q2 / Q3+Q4); 2 = Inductive/capacitive (Q1+Q3 / Q2+Q4)
HR6024doc 46025Modbus address1-247.FLOAT32ABCDRead/write
HR6026doc 46027ComsetupBaud, parity and stop bits in one code.FLOAT32ABCDRead/write0 = 2400 bps, no parity, 1 stop; 1 = 2400 bps, no parity, 2 stop; 2 = 2400 bps, even, 1 stop; 3 = 2400 bps, odd, 1 stop; 4 = 4800 bps, no parity, 1 stop; 5 = 4800 bps, no parity, 2 stop; 6 = 4800 bps, even, 1 stop; 7 = 4800 bps, odd, 1 stop; 8 = 9600 bps, no parity, 1 stop; 9 = 9600 bps, no parity, 2 stop; 10 = 9600 bps, even, 1 stop; 11 = 9600 bps, odd, 1 stop; 12 = 19200 bps, no parity, 1 stop; 13 = 19200 bps, no parity, 2 stop; 14 = 19200 bps, even, 1 stop; 15 = 19200 bps, odd, 1 stop; 16 = 38400 bps, no parity, 1 stop; 17 = 38400 bps, no parity, 2 stop; 18 = 38400 bps, even, 1 stop; 19 = 38400 bps, odd, 1 stop

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters

What Modbus registers does the Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters have?

This map lists 84 registers: 79 input registers, 5 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Table 4 prints 3X and 4X numbers next to the hex start address (30001 = 00 00, 30071 = 00 46). Wire address = number - 30001 (FC04) or - 40001 (FC03); every row was checked against the printed hex and parameter number. The setup example reads 46007 at 17 76.

What byte order does the Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters?

Start with IR 0 Voltage (Voltage); IR 6 Current (Current); IR 12 Active Power (Active power); IR 30 Power Factor (Power factor); IR 70 Frequency (Frequency); IR 108 Active Import Energy (Active import energy (kWh)).

How do I enable Modbus control of the Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters?

Only the x1 (Modbus) variants have RS-485. Set address and baud/parity from the front-panel setup (address 001 and 9600 baud, no parity by default; check stop bits, see notes) or via 46025/46027.

Where is the official Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters Modbus documentation?

The source is Operating Manual RISH ED11XX / EC11XX / ER11XX DIN rail mount Single Phase AC Energy Meter (DMAN-00IM-1071 Rev. M), revision 09/26, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/rish-ed11x1-66/RISH%20ED_EC_ER_11XX_Operating_Manual%20-%20REV_M.pdf.

More Rishabh Instruments Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Operating Manual RISH ED11XX / EC11XX / ER11XX DIN rail mount Single Phase AC Energy Meter · DMAN-00IM-1071 Rev. M · rev. 09/26. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.