The RISH LM 1360 load manager is a 96 x 96 mm panel load manager that measures voltage, current, power, power factor, frequency, harmonics and energy on 3-phase 4-wire, 3-phase 3-wire or single-phase networks. Its RS-485 port speaks Modbus RTU and every reading is a 32-bit IEEE float in two registers. This map covers per-phase and system parameters, energies with overflow counters, demands, THD and hour counters (Table 1), plus the main setup registers (system type, CT/PT ratios, demand period, communication and word-order settings).
This page lists 337 Modbus registers for the Rishabh Instruments RISH LM 1360 load manager (LM 13xx) — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.
- Manufacturer
- Rishabh Instruments
- Model
- RISH LM 1360 load manager (LM 13xx)
- Equipment type
- Power meter
- Registers
- 337 (13 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RISH LM 1360, LM1360, LM 13xx, LM1360 RJ12
Integration notes: Rishabh Instruments RISH LM 1360 load manager (LM 13xx)
Read measured values with FC04 (or FC03 at the 4X copies) in pairs of registers and decode them as ABCD floats. Settings are floats too and are written with FC16.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | V1 | FLOAT32 ABCD | Voltage L1 | Read |
| IR 6 | I1 | FLOAT32 ABCD | Current L1 | Read |
| IR 52 | Watt Sum | FLOAT32 ABCD | Total active power (Watt Sum) | Read |
| IR 70 | Freq | FLOAT32 ABCD | Frequency | Read |
| IR 62 | PF Avg | FLOAT32 ABCD | Average power factor | Read |
| IR 72 | Wh import | FLOAT32 ABCD | Active energy import (Wh import) | Read |
Enable Modbus control & writes
Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.
Byte order & addressing
- Each parameter is two registers; reading or writing only half of a float returns an Illegal Data Address exception.
- Addresses are Modicon-style: subtract 30001 or 40001 for the wire address.
- Limit each read to 40 parameters (80 registers) or less.
Network setup
- Slave address range 1-247; broadcast (address 0) is not supported.
- Allow about 300 ms for the meter to answer before retrying.
Watch out for
- If a password lock is set, write the valid password to the Password register before changing any 4X setting; a wrong password returns exception code 2.
Rishabh Instruments RISH LM 1360 load manager (LM 13xx) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | V1 | FLOAT32 | ABCD | Read | ||||
| IR | 2doc 30003 | V2 | FLOAT32 | ABCD | Read | ||||
| IR | 4doc 30005 | V3 | FLOAT32 | ABCD | Read | ||||
| IR | 6doc 30007 | I1 | FLOAT32 | ABCD | Read | ||||
| IR | 8doc 30009 | I2 | FLOAT32 | ABCD | Read | ||||
| IR | 10doc 30011 | I3 | FLOAT32 | ABCD | Read | ||||
| IR | 12doc 30013 | W1 | FLOAT32 | ABCD | Read | ||||
| IR | 14doc 30015 | W2 | FLOAT32 | ABCD | Read | ||||
| IR | 16doc 30017 | W3 | FLOAT32 | ABCD | Read | ||||
| IR | 18doc 30019 | VA1 | FLOAT32 | ABCD | Read | ||||
| IR | 20doc 30021 | VA2 | FLOAT32 | ABCD | Read | ||||
| IR | 22doc 30023 | VA3 | FLOAT32 | ABCD | Read | ||||
| IR | 24doc 30025 | VAR1 | FLOAT32 | ABCD | Read | ||||
| IR | 26doc 30027 | VAR2 | FLOAT32 | ABCD | Read | ||||
| IR | 28doc 30029 | VAR3 | FLOAT32 | ABCD | Read | ||||
| IR | 30doc 30031 | PF1 | FLOAT32 | ABCD | Read | ||||
| IR | 32doc 30033 | PF2 | FLOAT32 | ABCD | Read | ||||
| IR | 34doc 30035 | PF3 | FLOAT32 | ABCD | Read | ||||
| IR | 36doc 30037 | Angle1 | FLOAT32 | ABCD | Read | ||||
| IR | 38doc 30039 | Angle2 | FLOAT32 | ABCD | Read | ||||
| IR | 40doc 30041 | Angle3 | FLOAT32 | ABCD | Read | ||||
| IR | 42doc 30043 | Volt Avg | FLOAT32 | ABCD | Read | ||||
| IR | 44doc 30045 | Volt Sum | FLOAT32 | ABCD | Read | ||||
| IR | 46doc 30047 | Current Avg | FLOAT32 | ABCD | Read | ||||
| IR | 48doc 30049 | Current Sum | FLOAT32 | ABCD | Read | ||||
| IR | 50doc 30051 | Watt Avg | FLOAT32 | ABCD | Read | ||||
| IR | 52doc 30053 | Watt Sum | FLOAT32 | ABCD | Read | ||||
| IR | 54doc 30055 | VA Avg | FLOAT32 | ABCD | Read | ||||
| IR | 56doc 30057 | VA Sum | FLOAT32 | ABCD | Read | ||||
| IR | 58doc 30059 | VAr Avg | FLOAT32 | ABCD | Read | ||||
| IR | 60doc 30061 | VAr Sum | FLOAT32 | ABCD | Read | ||||
| IR | 62doc 30063 | PF Avg | FLOAT32 | ABCD | Read | ||||
| IR | 64doc 30065 | PF Sum | FLOAT32 | ABCD | Read | ||||
| IR | 66doc 30067 | Phase Angle Avg | FLOAT32 | ABCD | Read | ||||
| IR | 68doc 30069 | Phase Angle Sum | FLOAT32 | ABCD | Read | ||||
| IR | 70doc 30071 | Freq | FLOAT32 | ABCD | Read | ||||
| IR | 72doc 30073 | Wh import | FLOAT32 | ABCD | Read | ||||
| IR | 74doc 30075 | Wh export | FLOAT32 | ABCD | Read | ||||
| IR | 76doc 30077 | VArh Capacitive | FLOAT32 | ABCD | Read | ||||
| IR | 78doc 30079 | VArh Inductive | FLOAT32 | ABCD | Read | ||||
| IR | 80doc 30081 | VAh | FLOAT32 | ABCD | Read | ||||
| IR | 84doc 30085 | kW imp demand | FLOAT32 | ABCD | Read | ||||
| IR | 86doc 30087 | max kW imp demand | FLOAT32 | ABCD | Read | ||||
| IR | 88doc 30089 | kW exp demand | FLOAT32 | ABCD | Read | ||||
| IR | 90doc 30091 | max kW exp demand | FLOAT32 | ABCD | Read | ||||
| IR | 92doc 30093 | kVAr Cap. demand | FLOAT32 | ABCD | Read | ||||
| IR | 94doc 30095 | max kVAr Cap. demand | FLOAT32 | ABCD | Read | ||||
| IR | 96doc 30097 | kVAr Ind. demand | FLOAT32 | ABCD | Read | ||||
| IR | 98doc 30099 | max kVAr Ind. demand | FLOAT32 | ABCD | Read | ||||
| IR | 100doc 30101 | KVA demand | FLOAT32 | ABCD | Read | ||||
| IR | 102doc 30103 | max KVA demand | FLOAT32 | ABCD | Read | ||||
| IR | 104doc 30105 | current demand | FLOAT32 | ABCD | Read | ||||
| IR | 106doc 30107 | max current demand | FLOAT32 | ABCD | Read | ||||
| IR | 108doc 30109 | Wh import Overflow count | FLOAT32 | ABCD | Read | ||||
| IR | 110doc 30111 | Wh Import | FLOAT32 | ABCD | Read | ||||
| IR | 112doc 30113 | Wh export Overflow count | FLOAT32 | ABCD | Read | ||||
| IR | 114doc 30115 | Wh export | FLOAT32 | ABCD | Read | ||||
| IR | 116doc 30117 | VArh Cap. Overflow count | FLOAT32 | ABCD | Read | ||||
| IR | 118doc 30119 | VArh Capacitive | FLOAT32 | ABCD | Read | ||||
| IR | 120doc 30121 | VArh Ind. Overflow count | FLOAT32 | ABCD | Read | ||||
| IR | 122doc 30123 | VARh Inductive | FLOAT32 | ABCD | Read | ||||
| IR | 124doc 30125 | VAh Overflow count | FLOAT32 | ABCD | Read | ||||
| IR | 126doc 30127 | VAh | FLOAT32 | ABCD | Read | ||||
| IR | 132doc 30133 | System Voltage Max | FLOAT32 | ABCD | Read | ||||
| IR | 134doc 30135 | System Voltage Min | FLOAT32 | ABCD | Read | ||||
| IR | 136doc 30137 | RPM | FLOAT32 | ABCD | Read | ||||
| IR | 138doc 30139 | Impulse Rate | FLOAT32 | ABCD | Read | ||||
| IR | 140doc 30141 | System Current Max | FLOAT32 | ABCD | Read | ||||
| IR | 142doc 30143 | System Current Min | FLOAT32 | ABCD | Read | ||||
| IR | 144doc 30145 | Wh imp. depending on update rate* | FLOAT32 | ABCD | Read | ||||
| IR | 146doc 30147 | Wh exp. depending on update rate* | FLOAT32 | ABCD | Read | ||||
| IR | 148doc 30149 | VArh cap. depending on update rate* | FLOAT32 | ABCD | Read | ||||
| IR | 150doc 30151 | VArh ind. depending on update rate* | FLOAT32 | ABCD | Read | ||||
| IR | 152doc 30153 | VAh depending on update rate* | FLOAT32 | ABCD | Read | ||||
| IR | 156doc 30157 | Wh imp OFC depending on update rate* | FLOAT32 | ABCD | Read | ||||
| IR | 158doc 30159 | Wh exp OFC depending on update rate* | FLOAT32 | ABCD | Read | ||||
| IR | 160doc 30161 | VArh Cap. OFC depending on update rate * | FLOAT32 | ABCD | Read | ||||
| IR | 162doc 30163 | VArh Ind. OFC depending on update rate * | FLOAT32 | ABCD | Read | ||||
| IR | 164doc 30165 | VAh OFC depending on update rate* | FLOAT32 | ABCD | Read | ||||
| IR | 168doc 30169 | Old Wh imp OFC | FLOAT32 | ABCD | Read | ||||
| IR | 170doc 30171 | Old Wh imp | FLOAT32 | ABCD | Read | ||||
| IR | 172doc 30173 | Old Wh exp OFC | FLOAT32 | ABCD | Read | ||||
| IR | 174doc 30175 | Old Wh exp | FLOAT32 | ABCD | Read | ||||
| IR | 176doc 30177 | Old VArh Cap. OFC | FLOAT32 | ABCD | Read | ||||
| IR | 178doc 30179 | Old VArh Cap. | FLOAT32 | ABCD | Read | ||||
| IR | 180doc 30181 | Old VArh Ind.OFC | FLOAT32 | ABCD | Read | ||||
| IR | 182doc 30183 | Old VArh Ind. | FLOAT32 | ABCD | Read | ||||
| IR | 184doc 30185 | Old VAh OFC | FLOAT32 | ABCD | Read | ||||
| IR | 186doc 30187 | Old VAh | FLOAT32 | ABCD | Read | ||||
| IR | 200doc 30201 | V12 | FLOAT32 | ABCD | Read | ||||
| IR | 202doc 30203 | V23 | FLOAT32 | ABCD | Read | ||||
| IR | 204doc 30205 | V31 | FLOAT32 | ABCD | Read | ||||
| IR | 206doc 30207 | VTHD-R | FLOAT32 | ABCD | Read | ||||
| IR | 208doc 30209 | VTHD-Y | FLOAT32 | ABCD | Read | ||||
| IR | 210doc 30211 | VTHD-B | FLOAT32 | ABCD | Read | ||||
| IR | 212doc 30213 | ITHD-R | FLOAT32 | ABCD | Read | ||||
| IR | 214doc 30215 | ITHD-Y | FLOAT32 | ABCD | Read | ||||
| IR | 216doc 30217 | ITHD-B | FLOAT32 | ABCD | Read | ||||
| IR | 218doc 30219 | System V-THD | FLOAT32 | ABCD | Read | ||||
| IR | 220doc 30221 | System I-THD | FLOAT32 | ABCD | Read | ||||
| IR | 224doc 30225 | Neutral Current | FLOAT32 | ABCD | Read | ||||
| IR | 226doc 30227 | Run hour | FLOAT32 | ABCD | Read | ||||
| IR | 228doc 30229 | On Hour | FLOAT32 | ABCD | Read | ||||
| IR | 230doc 30231 | No. of interrupts | FLOAT32 | ABCD | Read | ||||
| IR | 250doc 30251 | Old run hour | FLOAT32 | ABCD | Read | ||||
| IR | 254doc 30255 | Old on hour | FLOAT32 | ABCD | Read | ||||
| IR | 262doc 30263 | Old No. of int. | FLOAT32 | ABCD | Read | ||||
| IR | 266doc 30267 | Relay 1 status | FLOAT32 | ABCD | Read | ||||
| IR | 268doc 30269 | Relay 2 status | FLOAT32 | ABCD | Read | ||||
| IR | 270doc 30271 | old max imp W demand | FLOAT32 | ABCD | Read | ||||
| IR | 272doc 30273 | old max exp W demand | FLOAT32 | ABCD | Read | ||||
| IR | 274doc 30275 | old max Cap. VArh demand | FLOAT32 | ABCD | Read | ||||
| IR | 276doc 30277 | old max Ind. VArh demand | FLOAT32 | ABCD | Read | ||||
| IR | 278doc 30279 | old max VA demand | FLOAT32 | ABCD | Read | ||||
| IR | 280doc 30281 | old max A demand | FLOAT32 | ABCD | Read | ||||
| IR | 292doc 30293 | RTC Minute | FLOAT32 | ABCD | Read | ||||
| IR | 294doc 30295 | RTC Hour | FLOAT32 | ABCD | Read | ||||
| IR | 296doc 30297 | RTC Day | FLOAT32 | ABCD | Read | ||||
| IR | 298doc 30299 | RTC Date | FLOAT32 | ABCD | Read | ||||
| IR | 300doc 30301 | RTC Month | FLOAT32 | ABCD | Read | ||||
| IR | 302doc 30303 | RTC Year | FLOAT32 | ABCD | Read | ||||
| IR | 304doc 30305 | RTC Complete date | FLOAT32 | ABCD | Read | ||||
| IR | 306doc 30307 | RTC Complete time | FLOAT32 | ABCD | Read | ||||
| IR | 332doc 30333 | Phase indicate | FLOAT32 | ABCD | Read | ||||
| IR | 336doc 30337 | Reserved | FLOAT32 | ABCD | Read | ||||
| IR | 344doc 30345 | Power Down RTC Minute | FLOAT32 | ABCD | Read | ||||
| IR | 346doc 30347 | Power Down RTC Hour | FLOAT32 | ABCD | Read | ||||
| IR | 348doc 30349 | Power Down RTC Day | FLOAT32 | ABCD | Read | ||||
| IR | 350doc 30351 | Power Down RTC Date | FLOAT32 | ABCD | Read | ||||
| IR | 352doc 30353 | Power Down RTC Month | FLOAT32 | ABCD | Read | ||||
| IR | 354doc 30355 | Power Down RTC Year | FLOAT32 | ABCD | Read | ||||
| IR | 356doc 30357 | Timer 1 On delay | FLOAT32 | ABCD | Read | ||||
| IR | 358doc 30359 | Timer 2 On delay | FLOAT32 | ABCD | Read | ||||
| IR | 360doc 30361 | Timer 1 Off delay | FLOAT32 | ABCD | Read | ||||
| IR | 362doc 30363 | Timer 2 Off delay | FLOAT32 | ABCD | Read | ||||
| IR | 364doc 30365 | Timer 1 No. of Cycles | FLOAT32 | ABCD | Read | ||||
| IR | 366doc 30367 | Timer 2 No. of Cycles | FLOAT32 | ABCD | Read | ||||
| IR | 400doc 30401 | VR Harmonic-1 | FLOAT32 | ABCD | Read | ||||
| IR | 402doc 30403 | IR Harmonic-1 | FLOAT32 | ABCD | Read | ||||
| IR | 404doc 30405 | VR Harmonic-2 | FLOAT32 | ABCD | Read | ||||
| IR | 406doc 30407 | IR Harmonic-2 | FLOAT32 | ABCD | Read | ||||
| IR | 408doc 30409 | VR Harmonic-3 | FLOAT32 | ABCD | Read | ||||
| IR | 410doc 30411 | IR Harmonic-3 | FLOAT32 | ABCD | Read | ||||
| IR | 412doc 30413 | VR Harmonic-4 | FLOAT32 | ABCD | Read | ||||
| IR | 414doc 30415 | IR Harmonic-4 | FLOAT32 | ABCD | Read | ||||
| IR | 416doc 30417 | VR Harmonic-5 | FLOAT32 | ABCD | Read | ||||
| IR | 418doc 30419 | IR Harmonic-5 | FLOAT32 | ABCD | Read | ||||
| IR | 420doc 30421 | VR Harmonic-6 | FLOAT32 | ABCD | Read | ||||
| IR | 422doc 30423 | IR Harmonic-6 | FLOAT32 | ABCD | Read | ||||
| IR | 424doc 30425 | VR Harmonic-7 | FLOAT32 | ABCD | Read | ||||
| IR | 426doc 30427 | IR Harmonic-7 | FLOAT32 | ABCD | Read | ||||
| IR | 428doc 30429 | VR Harmonic-8 | FLOAT32 | ABCD | Read | ||||
| IR | 430doc 30431 | IR Harmonic-8 | FLOAT32 | ABCD | Read | ||||
| IR | 432doc 30433 | VR Harmonic-9 | FLOAT32 | ABCD | Read | ||||
| IR | 434doc 30435 | IR Harmonic-9 | FLOAT32 | ABCD | Read | ||||
| IR | 436doc 30437 | VR Harmonic-10 | FLOAT32 | ABCD | Read | ||||
| IR | 438doc 30439 | IR Harmonic-10 | FLOAT32 | ABCD | Read | ||||
| IR | 440doc 30441 | VR Harmonic-11 | FLOAT32 | ABCD | Read | ||||
| IR | 442doc 30443 | IR Harmonic-11 | FLOAT32 | ABCD | Read | ||||
| IR | 444doc 30445 | VR Harmonic-12 | FLOAT32 | ABCD | Read | ||||
| IR | 446doc 30447 | IR Harmonic-12 | FLOAT32 | ABCD | Read | ||||
| IR | 448doc 30449 | VR Harmonic-13 | FLOAT32 | ABCD | Read | ||||
| IR | 450doc 30451 | IR Harmonic-13 | FLOAT32 | ABCD | Read | ||||
| IR | 452doc 30453 | VR Harmonic-14 | FLOAT32 | ABCD | Read | ||||
| IR | 454doc 30455 | IR Harmonic-14 | FLOAT32 | ABCD | Read | ||||
| IR | 456doc 30457 | VR Harmonic-15 | FLOAT32 | ABCD | Read | ||||
| IR | 458doc 30459 | IR Harmonic-15 | FLOAT32 | ABCD | Read | ||||
| IR | 460doc 30461 | VR Harmonic-16 | FLOAT32 | ABCD | Read | ||||
| IR | 462doc 30463 | IR Harmonic-16 | FLOAT32 | ABCD | Read | ||||
| IR | 464doc 30465 | VR Harmonic-17 | FLOAT32 | ABCD | Read | ||||
| IR | 466doc 30467 | IR Harmonic-17 | FLOAT32 | ABCD | Read | ||||
| IR | 468doc 30469 | VR Harmonic-18 | FLOAT32 | ABCD | Read | ||||
| IR | 470doc 30471 | IR Harmonic-18 | FLOAT32 | ABCD | Read | ||||
| IR | 472doc 30473 | VR Harmonic-19 | FLOAT32 | ABCD | Read | ||||
| IR | 474doc 30475 | IR Harmonic-19 | FLOAT32 | ABCD | Read | ||||
| IR | 476doc 30477 | VR Harmonic-20 | FLOAT32 | ABCD | Read | ||||
| IR | 478doc 30479 | IR Harmonic-20 | FLOAT32 | ABCD | Read | ||||
| IR | 480doc 30481 | VR Harmonic-21 | FLOAT32 | ABCD | Read | ||||
| IR | 482doc 30483 | IR Harmonic-21 | FLOAT32 | ABCD | Read | ||||
| IR | 484doc 30485 | VR Harmonic-22 | FLOAT32 | ABCD | Read | ||||
| IR | 486doc 30487 | IR Harmonic-22 | FLOAT32 | ABCD | Read | ||||
| IR | 488doc 30489 | VR Harmonic-23 | FLOAT32 | ABCD | Read | ||||
| IR | 490doc 30491 | IR Harmonic-23 | FLOAT32 | ABCD | Read | ||||
| IR | 492doc 30493 | VR Harmonic-24 | FLOAT32 | ABCD | Read | ||||
| IR | 494doc 30495 | IR Harmonic-24 | FLOAT32 | ABCD | Read | ||||
| IR | 496doc 30497 | VR Harmonic-25 | FLOAT32 | ABCD | Read | ||||
| IR | 498doc 30499 | IR Harmonic-25 | FLOAT32 | ABCD | Read | ||||
| IR | 500doc 30501 | VR Harmonic-26 | FLOAT32 | ABCD | Read | ||||
| IR | 502doc 30503 | IR Harmonic-26 | FLOAT32 | ABCD | Read | ||||
| IR | 504doc 30505 | VR Harmonic-27 | FLOAT32 | ABCD | Read | ||||
| IR | 506doc 30507 | IR Harmonic-27 | FLOAT32 | ABCD | Read | ||||
| IR | 508doc 30509 | VR Harmonic-28 | FLOAT32 | ABCD | Read | ||||
| IR | 510doc 30511 | IR Harmonic-28 | FLOAT32 | ABCD | Read | ||||
| IR | 512doc 30513 | VR Harmonic-29 | FLOAT32 | ABCD | Read | ||||
| IR | 514doc 30515 | IR Harmonic-29 | FLOAT32 | ABCD | Read | ||||
| IR | 516doc 30517 | VR Harmonic-30 | FLOAT32 | ABCD | Read | ||||
| IR | 518doc 30519 | IR Harmonic-30 | FLOAT32 | ABCD | Read | ||||
| IR | 520doc 30521 | VR Harmonic-31 | FLOAT32 | ABCD | Read | ||||
| IR | 522doc 30523 | IR Harmonic-31 | FLOAT32 | ABCD | Read | ||||
| IR | 524doc 30525 | VR Harmonic-32 | FLOAT32 | ABCD | Read | ||||
| IR | 526doc 30527 | IR Harmonic-32 | FLOAT32 | ABCD | Read | ||||
| IR | 528doc 30529 | VY Harmonic-1 | FLOAT32 | ABCD | Read | ||||
| IR | 530doc 30531 | IY Harmonic-1 | FLOAT32 | ABCD | Read | ||||
| IR | 532doc 30533 | VY Harmonic-2 | FLOAT32 | ABCD | Read | ||||
| IR | 534doc 30535 | IY Harmonic-2 | FLOAT32 | ABCD | Read | ||||
| IR | 536doc 30537 | VY Harmonic-3 | FLOAT32 | ABCD | Read | ||||
| IR | 538doc 30539 | IY Harmonic-3 | FLOAT32 | ABCD | Read | ||||
| IR | 540doc 30541 | VY Harmonic-4 | FLOAT32 | ABCD | Read | ||||
| IR | 542doc 30543 | IY Harmonic-4 | FLOAT32 | ABCD | Read | ||||
| IR | 544doc 30545 | VY Harmonic-5 | FLOAT32 | ABCD | Read | ||||
| IR | 546doc 30547 | IY Harmonic-5 | FLOAT32 | ABCD | Read | ||||
| IR | 548doc 30549 | VY Harmonic-6 | FLOAT32 | ABCD | Read | ||||
| IR | 550doc 30551 | IY Harmonic-6 | FLOAT32 | ABCD | Read | ||||
| IR | 552doc 30553 | VY Harmonic-7 | FLOAT32 | ABCD | Read | ||||
| IR | 554doc 30555 | IY Harmonic-7 | FLOAT32 | ABCD | Read | ||||
| IR | 556doc 30557 | VY Harmonic-8 | FLOAT32 | ABCD | Read | ||||
| IR | 558doc 30559 | IY Harmonic-8 | FLOAT32 | ABCD | Read | ||||
| IR | 560doc 30561 | VY Harmonic-9 | FLOAT32 | ABCD | Read | ||||
| IR | 562doc 30563 | IY Harmonic-9 | FLOAT32 | ABCD | Read | ||||
| IR | 564doc 30565 | VY Harmonic-10 | FLOAT32 | ABCD | Read | ||||
| IR | 566doc 30567 | IY Harmonic-10 | FLOAT32 | ABCD | Read | ||||
| IR | 568doc 30569 | VY Harmonic-11 | FLOAT32 | ABCD | Read | ||||
| IR | 570doc 30571 | IY Harmonic-11 | FLOAT32 | ABCD | Read | ||||
| IR | 572doc 30573 | VY Harmonic-12 | FLOAT32 | ABCD | Read | ||||
| IR | 574doc 30575 | IY Harmonic-12 | FLOAT32 | ABCD | Read | ||||
| IR | 576doc 30577 | VY Harmonic-13 | FLOAT32 | ABCD | Read | ||||
| IR | 578doc 30579 | IY Harmonic-13 | FLOAT32 | ABCD | Read | ||||
| IR | 580doc 30581 | VY Harmonic-14 | FLOAT32 | ABCD | Read | ||||
| IR | 582doc 30583 | IY Harmonic-14 | FLOAT32 | ABCD | Read | ||||
| IR | 584doc 30585 | VY Harmonic-15 | FLOAT32 | ABCD | Read | ||||
| IR | 586doc 30587 | IY Harmonic-15 | FLOAT32 | ABCD | Read | ||||
| IR | 588doc 30589 | VY Harmonic-16 | FLOAT32 | ABCD | Read | ||||
| IR | 590doc 30591 | IY Harmonic-16 | FLOAT32 | ABCD | Read | ||||
| IR | 592doc 30593 | VY Harmonic-17 | FLOAT32 | ABCD | Read | ||||
| IR | 594doc 30595 | IY Harmonic-17 | FLOAT32 | ABCD | Read | ||||
| IR | 596doc 30597 | VY Harmonic-18 | FLOAT32 | ABCD | Read | ||||
| IR | 598doc 30599 | IY Harmonic-18 | FLOAT32 | ABCD | Read | ||||
| IR | 600doc 30601 | VY Harmonic-19 | FLOAT32 | ABCD | Read | ||||
| IR | 602doc 30603 | IY Harmonic-19 | FLOAT32 | ABCD | Read | ||||
| IR | 604doc 30605 | VY Harmonic-20 | FLOAT32 | ABCD | Read | ||||
| IR | 606doc 30607 | IY Harmonic-20 | FLOAT32 | ABCD | Read | ||||
| IR | 608doc 30609 | VY Harmonic-21 | FLOAT32 | ABCD | Read | ||||
| IR | 610doc 30611 | IY Harmonic-21 | FLOAT32 | ABCD | Read | ||||
| IR | 612doc 30613 | VY Harmonic-22 | FLOAT32 | ABCD | Read | ||||
| IR | 614doc 30615 | IY Harmonic-22 | FLOAT32 | ABCD | Read | ||||
| IR | 616doc 30617 | VY Harmonic-23 | FLOAT32 | ABCD | Read | ||||
| IR | 618doc 30619 | IY Harmonic-23 | FLOAT32 | ABCD | Read | ||||
| IR | 620doc 30621 | VY Harmonic-24 | FLOAT32 | ABCD | Read | ||||
| IR | 622doc 30623 | IY Harmonic-24 | FLOAT32 | ABCD | Read | ||||
| IR | 624doc 30625 | VY Harmonic-25 | FLOAT32 | ABCD | Read | ||||
| IR | 626doc 30627 | IY Harmonic-25 | FLOAT32 | ABCD | Read | ||||
| IR | 628doc 30629 | VY Harmonic-26 | FLOAT32 | ABCD | Read | ||||
| IR | 630doc 30631 | IY Harmonic-26 | FLOAT32 | ABCD | Read | ||||
| IR | 632doc 30633 | VY Harmonic-27 | FLOAT32 | ABCD | Read | ||||
| IR | 634doc 30635 | IY Harmonic-27 | FLOAT32 | ABCD | Read | ||||
| IR | 636doc 30637 | VY Harmonic-28 | FLOAT32 | ABCD | Read | ||||
| IR | 638doc 30639 | IY Harmonic-28 | FLOAT32 | ABCD | Read | ||||
| IR | 640doc 30641 | VY Harmonic-29 | FLOAT32 | ABCD | Read | ||||
| IR | 642doc 30643 | IY Harmonic-29 | FLOAT32 | ABCD | Read | ||||
| IR | 644doc 30645 | VY Harmonic-30 | FLOAT32 | ABCD | Read | ||||
| IR | 646doc 30647 | IY Harmonic-30 | FLOAT32 | ABCD | Read | ||||
| IR | 648doc 30649 | VY Harmonic-31 | FLOAT32 | ABCD | Read | ||||
| IR | 650doc 30651 | IY Harmonic-31 | FLOAT32 | ABCD | Read | ||||
| IR | 652doc 30653 | VY Harmonic-32 | FLOAT32 | ABCD | Read | ||||
| IR | 654doc 30655 | IY Harmonic-32 | FLOAT32 | ABCD | Read | ||||
| IR | 656doc 30657 | VB Harmonic-1 | FLOAT32 | ABCD | Read | ||||
| IR | 658doc 30659 | IB Harmonic-1 | FLOAT32 | ABCD | Read | ||||
| IR | 660doc 30661 | VB Harmonic-2 | FLOAT32 | ABCD | Read | ||||
| IR | 662doc 30663 | IB Harmonic-2 | FLOAT32 | ABCD | Read | ||||
| IR | 664doc 30665 | VB Harmonic-3 | FLOAT32 | ABCD | Read | ||||
| IR | 666doc 30667 | IB Harmonic-3 | FLOAT32 | ABCD | Read | ||||
| IR | 668doc 30669 | VB Harmonic-4 | FLOAT32 | ABCD | Read | ||||
| IR | 670doc 30671 | IB Harmonic-4 | FLOAT32 | ABCD | Read | ||||
| IR | 672doc 30673 | VB Harmonic-5 | FLOAT32 | ABCD | Read | ||||
| IR | 674doc 30675 | IB Harmonic-5 | FLOAT32 | ABCD | Read | ||||
| IR | 676doc 30677 | VB Harmonic-6 | FLOAT32 | ABCD | Read | ||||
| IR | 678doc 30679 | IB Harmonic-6 | FLOAT32 | ABCD | Read | ||||
| IR | 680doc 30681 | VB Harmonic-7 | FLOAT32 | ABCD | Read | ||||
| IR | 682doc 30683 | IB Harmonic-7 | FLOAT32 | ABCD | Read | ||||
| IR | 684doc 30685 | VB Harmonic-8 | FLOAT32 | ABCD | Read | ||||
| IR | 686doc 30687 | IB Harmonic-8 | FLOAT32 | ABCD | Read | ||||
| IR | 688doc 30689 | VB Harmonic-9 | FLOAT32 | ABCD | Read | ||||
| IR | 690doc 30691 | IB Harmonic-9 | FLOAT32 | ABCD | Read | ||||
| IR | 692doc 30693 | VB Harmonic-10 | FLOAT32 | ABCD | Read | ||||
| IR | 694doc 30695 | IB Harmonic-10 | FLOAT32 | ABCD | Read | ||||
| IR | 696doc 30697 | VB Harmonic-11 | FLOAT32 | ABCD | Read | ||||
| IR | 698doc 30699 | IB Harmonic-11 | FLOAT32 | ABCD | Read | ||||
| IR | 700doc 30701 | VB Harmonic-12 | FLOAT32 | ABCD | Read | ||||
| IR | 702doc 30703 | IB Harmonic-12 | FLOAT32 | ABCD | Read | ||||
| IR | 704doc 30705 | VB Harmonic-13 | FLOAT32 | ABCD | Read | ||||
| IR | 706doc 30707 | IB Harmonic-13 | FLOAT32 | ABCD | Read | ||||
| IR | 708doc 30709 | VB Harmonic-14 | FLOAT32 | ABCD | Read | ||||
| IR | 710doc 30711 | IB Harmonic-14 | FLOAT32 | ABCD | Read | ||||
| IR | 712doc 30713 | VB Harmonic-15 | FLOAT32 | ABCD | Read | ||||
| IR | 714doc 30715 | IB Harmonic-15 | FLOAT32 | ABCD | Read | ||||
| IR | 716doc 30717 | VB Harmonic-16 | FLOAT32 | ABCD | Read | ||||
| IR | 718doc 30719 | IB Harmonic-16 | FLOAT32 | ABCD | Read | ||||
| IR | 720doc 30721 | VB Harmonic-17 | FLOAT32 | ABCD | Read | ||||
| IR | 722doc 30723 | IB Harmonic-17 | FLOAT32 | ABCD | Read | ||||
| IR | 724doc 30725 | VB Harmonic-18 | FLOAT32 | ABCD | Read | ||||
| IR | 726doc 30727 | IB Harmonic-18 | FLOAT32 | ABCD | Read | ||||
| IR | 728doc 30729 | VB Harmonic-19 | FLOAT32 | ABCD | Read | ||||
| IR | 730doc 30731 | IB Harmonic-19 | FLOAT32 | ABCD | Read | ||||
| IR | 732doc 30733 | VB Harmonic-20 | FLOAT32 | ABCD | Read | ||||
| IR | 734doc 30735 | IB Harmonic-20 | FLOAT32 | ABCD | Read | ||||
| IR | 736doc 30737 | VB Harmonic-21 | FLOAT32 | ABCD | Read | ||||
| IR | 738doc 30739 | IB Harmonic-21 | FLOAT32 | ABCD | Read | ||||
| IR | 740doc 30741 | VB Harmonic-22 | FLOAT32 | ABCD | Read | ||||
| IR | 742doc 30743 | IB Harmonic-22 | FLOAT32 | ABCD | Read | ||||
| IR | 744doc 30745 | VB Harmonic-23 | FLOAT32 | ABCD | Read | ||||
| IR | 746doc 30747 | IB Harmonic-23 | FLOAT32 | ABCD | Read | ||||
| IR | 748doc 30749 | VB Harmonic-24 | FLOAT32 | ABCD | Read | ||||
| IR | 750doc 30751 | IB Harmonic-24 | FLOAT32 | ABCD | Read | ||||
| IR | 752doc 30753 | VB Harmonic-25 | FLOAT32 | ABCD | Read | ||||
| IR | 754doc 30755 | IB Harmonic-25 | FLOAT32 | ABCD | Read | ||||
| IR | 756doc 30757 | VB Harmonic-26 | FLOAT32 | ABCD | Read | ||||
| IR | 758doc 30759 | IB Harmonic-26 | FLOAT32 | ABCD | Read | ||||
| IR | 760doc 30761 | VB Harmonic-27 | FLOAT32 | ABCD | Read | ||||
| IR | 762doc 30763 | IB Harmonic-27 | FLOAT32 | ABCD | Read | ||||
| IR | 764doc 30765 | VB Harmonic-28 | FLOAT32 | ABCD | Read | ||||
| IR | 766doc 30767 | IB Harmonic-28 | FLOAT32 | ABCD | Read | ||||
| HR | 6002doc 46003 | Demand integration time | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6004doc 46005 | Energy Resolution / unit | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6010doc 46011 | System type | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6014doc 46015 | Reset parameters | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6018doc 46019 | RS485 setup code | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6020doc 46021 | Node address | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6032doc 46033 | PT primary | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6034doc 46035 | CT primary | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6040doc 46041 | Register Order/Word Order | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6042doc 46043 | CTSecondary | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6044doc 46045 | PTSecondary | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6070doc 46071 | Password | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6076doc 46077 | Auto scroll | Setup parameter (float). | FLOAT32 | ABCD | Read/write | |||
| HR | 6176doc 46177 | Serial Number Higher Digits | Read-only identification value (float). | FLOAT32 | ABCD | Read | |||
| HR | 6180doc 46181 | Version no. | Read-only identification value (float). | FLOAT32 | ABCD | Read | |||
| HR | 6182doc 46183 | Serial Number Lower Digits | Read-only identification value (float). | FLOAT32 | ABCD | Read |
Notes on this map
- Measured values are IEEE-754 32-bit floats in two registers. The manual's example responses (e.g. data bytes 43 5B 41 21 for a current reading) put the most significant register first, so ABCD is the default order.
- Register 46041 (Word Order) can switch the meter to reversed register order; the manual says to write 2141.0 to it and the meter detects which order was used. If floats look wrong, check this setting.
- Every measured value is also readable as a holding register (FC03) at the 4X address printed next to it in the manual; this map lists the 3X (input register, FC04) copies only.
- Rows whose printed hex address does not match the decimal 3X/4X address in the manual were left out rather than guessed.
- Left out: the 32-bit integer energy tables (their integer word order is not demonstrated in the manual), user-assignable registers and data-log blocks.
- Where the register table has no unit column, units are left blank; energy registers follow the energy unit (Wh/kWh/MWh) configured on the meter, and 'OF' / overflow registers count roll-overs of the matching energy register.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Rishabh Instruments RISH LM 1360 load manager (LM 13xx)
What Modbus registers does the Rishabh Instruments RISH LM 1360 load manager (LM 13xx) have?
This map lists 337 registers: 321 input registers, 16 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Rishabh Instruments RISH LM 1360 load manager (LM 13xx) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 30001/40001-style addresses next to the hex start address actually sent (30001 = 0x0000). Wire address = printed number - 30001 (input registers) or - 40001 (holding registers); every value here was cross-checked against the printed hex address.
What byte order does the Rishabh Instruments RISH LM 1360 load manager (LM 13xx) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Rishabh Instruments RISH LM 1360 load manager (LM 13xx)?
Start with IR 0 V1 (Voltage L1); IR 6 I1 (Current L1); IR 52 Watt Sum (Total active power (Watt Sum)); IR 70 Freq (Frequency); IR 62 PF Avg (Average power factor); IR 72 Wh import (Active energy import (Wh import)).
How do I enable Modbus control of the Rishabh Instruments RISH LM 1360 load manager (LM 13xx)?
Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.
Where is the official Rishabh Instruments RISH LM 1360 load manager (LM 13xx) Modbus documentation?
The source is Interface Definition - LM 13xx (DMAN-00IM-0662 Rev. D), revision 2024-01, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/rish-lm-1360-load-manager-138/Interface_Definition_-_LM_13xx_Rev-D.pdf.
More Rishabh Instruments Modbus register maps
- Energy meter (DC)
Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter
Rishabh RISH DC2111 MOD single-channel DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-1669 Rev. D (08/25).
Also known as: RISH DC2111 MOD, DC2111 - Energy meter
Rishabh Instruments RISH Delta Energy NX multifunction energy meter
Rishabh RISH Delta Energy NX panel energy meters with RS-485 Modbus RTU, per the operating manual on the product page (standard CT version).
Also known as: RISH Delta Energy NX, Delta Energy NX, RISH Delta Energy - Power meter
Rishabh Instruments RISH Delta Power NX multifunction power meter
Rishabh RISH Delta Power NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0117 Rev. E.
Also known as: RISH Delta Power NX, Delta Power NX, RISH Delta Power - Power meter
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
Rishabh RISH Delta VAF NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0118 Rev. F.
Also known as: RISH Delta VAF NX, Delta VAF NX, RISH Delta VAF - Power meter (demand controller)
Rishabh Instruments RISH DMCi touch-screen demand controller with TOD
Rishabh RISH DMCi 96 x 96 mm touch-screen demand controllers with the optional RS-485 Modbus output, per interface definition DMAN-00IM-0578 Rev. A (09/16).
Also known as: RISH DMCi, DMCi, Rish DMCi demand controller - Energy meter
Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters
Rishabh RISH EC43xx and ER43xx DIN-rail digital energy meters with RS-485 Modbus, per interface definition DMAN-00IM-09xx Rev. F (11/25).
Also known as: EC4311, EC4321, ER4311, ER4321, RISH EC43X1, EC43XX, ER43XX - Energy meter
Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters
Rishabh RISH ED11XX (direct), EC11XX (CT) and ER11XX (RJ12 CT) single-phase DIN-rail meters in their Modbus (x1) versions, per operating manual DMAN-00IM-1071 Rev. M.
Also known as: RISH ED11X1, RISH EC11X1, RISH ER11X1, ED1111, EC1111, ER1111, RISH ED11XX, RISH EC11XX, RISH ER11XX - Energy meter
Rishabh Instruments RISH ED21XX / EC21XX / ER21XX single-phase energy meters
Rishabh RISH ED21XX (direct), EC21XX (CT) and ER21XX (RJ12 CT) single-phase meters in their Modbus versions, per operating manual DMAN-00IM-1073 Rev. M.
Also known as: RISH ED21X1, RISH EC21X1, RISH ER21X1, RISH ED21XX, RISH EC21XX, RISH ER21XX - Energy meter
Rishabh Instruments RISH EM 1320 / 1330 / 1340 / 2340 programmable energy meters
Rishabh RISH EM 1320/1330/1340 and EM 2320/2330/2340 panel energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0721 Rev. B (06/2020). Rows marked 'only 2340' apply to the dual-source EM 2340.
Also known as: RISH EM 1320, RISH EM 1330, RISH EM 1340, RISH EM 2320, RISH EM 2330, RISH EM 2340, EM2340DS - Energy meter
Rishabh Instruments RISH EM 3490 DS dual-source (utility/generator) energy meter
Rishabh RISH EM 3490 DS dual-source energy meters (separate utility and generator energy) with RS-485 Modbus, per manual Rev G.
Also known as: RISH EM 3490 DS, EM3490DS, EM 3490DS - Energy meter
Rishabh Instruments RISH EM 3490 SS single-phase energy meter
Rishabh RISH EM 3490 SS single-phase energy meters with the optional RS-485 Modbus output, per the 1-phase manual Rev D.
Also known as: RISH EM 3490 SS 1P, EM3490SS 1P, EM 3490 SS single-phase - Energy meter
Rishabh Instruments RISH EM 3490 SS three-phase single-source energy meter
Rishabh RISH EM 3490 SS three-phase energy meters with the optional RS-485 Modbus output, per the 3-phase manual Rev E.
Also known as: RISH EM 3490 SS 3P, EM3490SS 3P, EM 3490 SS three-phase - Energy meter (DC)
Rishabh Instruments RISH EM DC 6000 programmable DC energy meter
Rishabh RISH EM DC 6000 single-channel programmable DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0862 Rev. 0 (12/2020).
Also known as: RISH EM DC 6000, EMDC 6000, EM DC6000 - Energy meter (DC)
Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter
Rishabh RISH EM DC 6001 / 6002 multi-channel DC energy meters with RS-485 Modbus, per interface definition 2-60-006-00-00627 Rev. 0 (10/2015).
Also known as: RISH EM DC 6001, RISH EM DC 6002, EM DC 6001, EM DC 6002 - Power meter
Rishabh Instruments RISH LM 1340 multifunction meter
Rishabh RISH LM 1340 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. D (03/2026).
Also known as: RISH LM 1340, LM1340 - Power meter
Rishabh Instruments RISH LM 1380 multifunction meter
Rishabh RISH LM 1380 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0925 Rev. A (04/2022).
Also known as: RISH LM 1380, LM1380 - Power meter
Rishabh Instruments RISH LM1360+ RJ12 smart energy meter
Rishabh RISH LM1360 PLUS RJ12 smart energy meters (RJ12 CT inputs) with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. A (01/2026).
Also known as: RISH LM 1360+, LM1360 PLUS RJ12, LM1360+ - Power meter
Rishabh Instruments RISH Master 3440 (class 0.2S) multifunction meter
Rishabh RISH Master 3440 class 0.2S panel meters with RS-485 Modbus, per interface definition DMAN-00IM-0711 Rev. C (05/2019).
Also known as: RISH Master 3440, RM3440, Master 3440 0.2S - Power meter
Rishabh Instruments RISH Master 3440i / 3440iDL (class 0.2S) touch-screen meter
Rishabh RISH Master 3440i and 3440iDL touch-screen class 0.2S meters with RS-485 Modbus, per interface definition DMAN-00IM-0712 Rev. F (10/2026).
Also known as: RISH Master 3440i, RISH Master 3440iDL, RM3440i, RM3440iDL - Power meter (multi-circuit energy meter)
Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)
RISH Multiload Monitor (12 current channels, 4 voltage channels) per interface definition DMAN-00IM-0795 Rev A (08/2020).
Also known as: RISH ML 1400, RISH ML 1410, RISH MLM, Multiload Monitor - Power meter (power factor controller)
Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller
Rishabh RISH PFC 96 and PFC 144 automatic power factor (APFC) controllers with RS-485 Modbus RTU, per interface definition version D (12/18).
Also known as: RISH PFC 96, RISH PFC 144, PFC96, PFC144, RISH PFC-12, APFC
Other power & energy meters register maps
- Energy meter
Saia Burgess Controls ALE3 three-phase 65 A energy meter (Modbus RTU)
ALE3 unidirectional (ALE3D5FD10C3A00) and bidirectional (ALE3B5FD00C3A00) Modbus types, assembly and operating instructions 431951130.
Also known as: ALE3D5FD10C3A00, ALE3B5FD00C3A00, ALE3D5FD10, ALE3B5FD00, SBC ALE3 Modbus - Power meter (power quality analyzer)
SATEC PM180 expertmeter high performance analyzer
SATEC PM180 expertmeter, per Modbus reference guide BG0527 Rev. A11 (Sep 2024).
Also known as: PM180, expertmeter PM180, SATEC PM180 - Power meter (multi-circuit)
Setra Systems Setra Power Meter (SPM) multi-circuit power meter
Setra Power Meter (SPM) family, per Modbus register master list SS-SPM-MODBUS_G; this map covers the device block, both voltage inputs and Load 1.
Also known as: SPM, Setra Power Meter, SS-SPM-MODBUS_G - Energy meter (heat / cooling meter)
Sontex Supercal 531 / Superstatic 440 / 449 with Modbus EIA-485 module
Sontex Modbus EIA-485 plug-in module in a Supercal 531 integrator or Superstatic 440/449 heat meter, integrator firmware 3.7 or later; user manual V05 (2019-09).
Also known as: Supercal 531, Superstatic 440, Superstatic 449, Sontex Modbus EIA-485 module, 0531P217 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Power meter
Accuenergy AcuRev 1310 series DIN-rail power meter
Accuenergy AcuRev 1310 series (1312/1313/1314) DIN-rail meters, Modbus map workbook revision 1.1.
Also known as: AcuRev 1312, AcuRev 1313, AcuRev 1314, AcuRev 1310
All power & energy meters Modbus register maps →
Source: Interface Definition - LM 13xx · DMAN-00IM-0662 Rev. D · rev. 2024-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.