Energy meter · Modbus register map

Rishabh Instruments RISH EM 3490 SS single-phase energy meter Modbus register map

Updated 19 November 2026

Short answer

The single-phase RISH EM 3490 SS is a panel energy meter with an optional RS-485 Modbus RTU port. Every measured value and every setting is an IEEE 32-bit float spread over two registers: readings are input registers (FC04) from 30001, settings are holding registers (FC03 read, FC16 write) from 40005. This map covers the full measured-value table, the setup registers and the word-order switch.

This page lists 25 Modbus registers for the Rishabh Instruments RISH EM 3490 SS single-phase energy meter — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.

Manufacturer
Rishabh Instruments
Model
RISH EM 3490 SS single-phase energy meter
Equipment type
Energy meter
Registers
25 (12 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RISH EM 3490 SS 1P, EM3490SS 1P, EM 3490 SS single-phase
Source document
EM 3490 SS Single Phase Energy Meter Installation & Operating Instructions · 15000251 Rev. D · rev. 2013-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Rishabh Instruments RISH EM 3490 SS single-phase energy meter

Integration in brief

Read 30001-30038 and 30071-30082 with FC04 (max 20 floats per request) and decode each pair as a big-endian float. Settings live in 40005-40071 and are written with FC16 as floats.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Volts 1FLOAT32 ABCDVoltageRead
IR 6Current 1FLOAT32 ABCDCurrentRead
IR 12W1FLOAT32 ABCDActive powerRead
IR 30PF1FLOAT32 ABCDPower factorRead
IR 70FrequencyFLOAT32 ABCDFrequencyRead
IR 72Wh (active energy)FLOAT32 ABCDActive energyRead

Enable Modbus control & writes

Modbus is an ordering option. Set node address, baud/parity (RS485 set-up code) and energy unit from the front panel or via 40019/40021/40005.

Byte order & addressing

Network setup

Watch out for

Rishabh Instruments RISH EM 3490 SS single-phase energy meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

25 of 25 shown
Rishabh Instruments RISH EM 3490 SS single-phase energy meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Volts 1FLOAT32ABCDRead
IR6doc 30007Current 1FLOAT32ABCDRead
IR12doc 30013W1FLOAT32ABCDRead
IR18doc 30019VA1FLOAT32ABCDRead
IR24doc 30025VAr1FLOAT32ABCDRead
IR30doc 30031PF1FLOAT32ABCDRead
IR36doc 30037Phase angle 1FLOAT32ABCDRead
IR70doc 30071FrequencyFLOAT32ABCDRead
IR72doc 30073Wh (active energy)Unit follows 40005 (Wh/kWh/MWh).FLOAT32ABCDRead
IR80doc 30081VAh (apparent energy)Unit follows 40005.FLOAT32ABCDRead
HR4doc 40005Energy display on ModbusUnit of the energy registers 30073/30081.FLOAT32ABCDRead/write1 = Wh; 2 = kWh; 3 = MWh
HR6doc 40007System voltageNominal system voltage.FLOAT32ABCDRead
HR8doc 40009System currentNominal system current.FLOAT32ABCDRead
HR12doc 40013Pulse width of relayFLOAT32ABCDRead/write60 = 60 ms; 100 = 100 ms; 200 = 200 ms
HR14doc 40015Reset energy counterWrite 0 to clear the energy counters.FLOAT32ABCDWrite
HR18doc 40019RS485 set-up codeBaud, parity and stop bits in one code.FLOAT32ABCDRead/write0 = 2400 bps, no parity, 1 stop; 1 = 2400 bps, no parity, 2 stop; 2 = 2400 bps, even, 1 stop; 3 = 2400 bps, odd, 1 stop; 4 = 4800 bps, no parity, 1 stop; 5 = 4800 bps, no parity, 2 stop; 6 = 4800 bps, even, 1 stop; 7 = 4800 bps, odd, 1 stop; 8 = 9600 bps, no parity, 1 stop; 9 = 9600 bps, no parity, 2 stop; 10 = 9600 bps, even, 1 stop; 11 = 9600 bps, odd, 1 stop; 12 = 19200 bps, no parity, 1 stop; 13 = 19200 bps, no parity, 2 stop; 14 = 19200 bps, even, 1 stop; 15 = 19200 bps, odd, 1 stop
HR20doc 40021Node address1-247.FLOAT32ABCDRead/write
HR22doc 40023Pulse divisorFLOAT32ABCDRead/write1 = Divisor 1; 10 = Divisor 10; 100 = Divisor 100; 1000 = Divisor 1000
HR32doc 40033PT primaryIn volts, e.g. 2000 for 2 kV.FLOAT32ABCDRead/write
HR34doc 40035CT primaryUp to 9999.FLOAT32ABCDRead/write
HR36doc 40037System powerNominal power from nominal volts and current.FLOAT32ABCDRead
HR38doc 40039Energy digit rollover (reset) countNumber of digits before energy rolls over to zero.FLOAT32ABCDRead/write
HR40doc 40041Register order / word orderWrite 2141.0 in the wanted order to switch normal/reversed float word order.FLOAT32ABCDRead/write
HR44doc 40045PT secondaryRange per manual section 4.2.1.3.FLOAT32ABCDRead/write
HR70doc 40071Password0000-9999; reads 0 when locked, 1 when unlocked.FLOAT32ABCDRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Rishabh Instruments RISH EM 3490 SS single-phase energy meter

What Modbus registers does the Rishabh Instruments RISH EM 3490 SS single-phase energy meter have?

This map lists 25 registers: 10 input registers, 15 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Rishabh Instruments RISH EM 3490 SS single-phase energy meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 30001/40001-style register numbers next to the hex start address that goes on the wire (30001 = 00 00, 40011 = 00 0A). Wire address = printed number - 30001 or - 40001; every row was checked against the printed hex.

What byte order does the Rishabh Instruments RISH EM 3490 SS single-phase energy meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Rishabh Instruments RISH EM 3490 SS single-phase energy meter?

Start with IR 0 Volts 1 (Voltage); IR 6 Current 1 (Current); IR 12 W1 (Active power); IR 30 PF1 (Power factor); IR 70 Frequency (Frequency); IR 72 Wh (active energy) (Active energy).

How do I enable Modbus control of the Rishabh Instruments RISH EM 3490 SS single-phase energy meter?

Modbus is an ordering option. Set node address, baud/parity (RS485 set-up code) and energy unit from the front panel or via 40019/40021/40005.

Where is the official Rishabh Instruments RISH EM 3490 SS single-phase energy meter Modbus documentation?

The source is EM 3490 SS Single Phase Energy Meter Installation & Operating Instructions (15000251 Rev. D), revision 2013-05, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/rish-em3490ss-single-source-energy-meter-154/Energy_Meter_-_3490SS_-_Manual_Rev_D_1P.pdf.

More Rishabh Instruments Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: EM 3490 SS Single Phase Energy Meter Installation & Operating Instructions · 15000251 Rev. D · rev. 2013-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.