Energy meter · Modbus register map

Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters Modbus register map

Updated 17 November 2026

Short answer

The RISH EC43xx / ER43xx is a DIN-rail digital energy meter that measures voltage, current, power, power factor, frequency, THD and energy on 3-phase 4-wire, 3-phase 3-wire or single-phase networks. Its RS-485 port speaks Modbus RTU and every reading is a 32-bit IEEE float in two registers. This map covers per-phase and system measurements, demands, THD, run/on hours and the float energy registers including per-phase and tariff energies, plus the read-only system type and CT/PT ratio registers.

This page lists 132 Modbus registers for the Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rishabh Instruments’s own free documentation (linked below) and checked against it.

Manufacturer
Rishabh Instruments
Model
RISH EC43xx / ER43xx DIN-rail energy meters
Equipment type
Energy meter
Registers
132 (1 writable)
Transport
Modbus RTU
Default unit ID
1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
EC4311, EC4321, ER4311, ER4321, RISH EC43X1, EC43XX, ER43XX
Source document
EC43XX / ER43XX Interface Definition · DMAN-00IM-09xx Rev. F · rev. 2025-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters

Integration in brief

Read measured values with FC04 (or FC03 at the 4X copies) in pairs of registers and decode them as ABCD floats. Settings are floats too and are written with FC16.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Voltage L1 (Voltage L12 for 3P3W)FLOAT32 ABCDVoltage L1Read
IR 6Current L1FLOAT32 ABCDCurrent L1Read
IR 52Watt SumFLOAT32 ABCDTotal active power (Watt Sum)Read
IR 70FreqFLOAT32 ABCDFrequencyRead
IR 72Wh importFLOAT32 ABCDActive energy importRead
IR 62PF AvgFLOAT32 ABCDAverage power factorRead

Enable Modbus control & writes

Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.

Byte order & addressing

Network setup

Watch out for

Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

132 of 132 shown
Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Voltage L1 (Voltage L12 for 3P3W)FLOAT32ABCDVRead
IR2doc 30003Voltage L2 (Voltage L23 for 3P3W)FLOAT32ABCDVRead
IR4doc 30005Voltage L3 (Voltage L31 for 3P3W)FLOAT32ABCDVRead
IR6doc 30007Current L1FLOAT32ABCDARead
IR8doc 30009Current L2FLOAT32ABCDARead
IR10doc 30011Current L3FLOAT32ABCDARead
IR12doc 30013Watt L1FLOAT32ABCDWRead
IR14doc 30015Watt L2FLOAT32ABCDWRead
IR16doc 30017Watt L3FLOAT32ABCDWRead
IR18doc 30019VA L1FLOAT32ABCDVARead
IR20doc 30021VA L2FLOAT32ABCDVARead
IR22doc 30023VA L3FLOAT32ABCDVARead
IR24doc 30025VAR L1FLOAT32ABCDvarRead
IR26doc 30027VAR L2FLOAT32ABCDvarRead
IR28doc 30029VAR L3FLOAT32ABCDvarRead
IR30doc 30031Power Factor L1FLOAT32ABCDRead
IR32doc 30033Power Factor L2FLOAT32ABCDRead
IR34doc 30035Power Factor L3FLOAT32ABCDRead
IR36doc 30037Phase Angle L1FLOAT32ABCD°Read
IR38doc 30039Phase Angle L2FLOAT32ABCD°Read
IR40doc 30041Phase Angle L3FLOAT32ABCD°Read
IR42doc 30043Voltage AvgFLOAT32ABCDVRead
IR44doc 30045Voltage SumFLOAT32ABCDVRead
IR46doc 30047Current AvgFLOAT32ABCDARead
IR48doc 30049Current SumFLOAT32ABCDARead
IR52doc 30053Watt SumFLOAT32ABCDWRead
IR54doc 30055VA AvgFLOAT32ABCDVARead
IR56doc 30057VA SumFLOAT32ABCDVARead
IR58doc 30059VAR AvgFLOAT32ABCDvarRead
IR60doc 30061VAr SumFLOAT32ABCDvarRead
IR62doc 30063PF AvgFLOAT32ABCDRead
IR64doc 30065PF SumFLOAT32ABCDRead
IR66doc 30067Phase Angle AvgFLOAT32ABCD°Read
IR68doc 30069Phase Angle SumFLOAT32ABCD°Read
IR70doc 30071FreqFLOAT32ABCDHzRead
IR72doc 30073Wh importFLOAT32ABCDkWhRead
IR74doc 30075Wh exportFLOAT32ABCDkWhRead
IR76doc 30077VArh importFLOAT32ABCDkvarhRead
IR78doc 30079VArh exportFLOAT32ABCDkvarhRead
IR80doc 30081VAhFLOAT32ABCDkVAhRead
IR84doc 30085W imp demandFLOAT32ABCDWRead
IR86doc 30087Max W imp demandFLOAT32ABCDWRead
IR88doc 30089W exp demandFLOAT32ABCDWRead
IR90doc 30091Max W exp demandFLOAT32ABCDWRead
IR92doc 30093VAr Imp. demandFLOAT32ABCDvarRead
IR94doc 30095max kVAr Imp. demandFLOAT32ABCDvarRead
IR96doc 30097VAr Exp. demandFLOAT32ABCDvarRead
IR98doc 30099Max VAr Exp. demandFLOAT32ABCDvarRead
IR100doc 30101VA demandFLOAT32ABCDVARead
IR102doc 30103max VA demandFLOAT32ABCDVARead
IR104doc 30105current demandFLOAT32ABCDARead
IR106doc 30107Max current demandFLOAT32ABCDARead
IR110doc 30111Wh ImportFLOAT32ABCDkWhRead
IR114doc 30115Wh exportFLOAT32ABCDkWhRead
IR118doc 30119VArh ImportFLOAT32ABCDkvarhRead
IR122doc 30123VARh ExportFLOAT32ABCDkvarhRead
IR126doc 30127VAhFLOAT32ABCDkVAhRead
IR132doc 30133System Voltage MaxFLOAT32ABCDVRead
IR134doc 30135System Voltage MinFLOAT32ABCDVRead
IR138doc 30139Impulse RateFLOAT32ABCDRead
IR140doc 30141System Current MaxFLOAT32ABCDARead
IR142doc 30143System Current MinFLOAT32ABCDARead
IR144doc 30145Wh Import ResetableFLOAT32ABCDkWhRead
IR146doc 30147Wh export ResetableFLOAT32ABCDkWhRead
IR148doc 30149VARh import ResetableFLOAT32ABCDkvarhRead
IR150doc 30151VARh export ResetableFLOAT32ABCDkvarhRead
IR152doc 30153Wh Total ResetableFLOAT32ABCDkWhRead
IR154doc 30155VArh Total ResetableFLOAT32ABCDkvarhRead
IR200doc 30201V12FLOAT32ABCDVRead
IR202doc 30203V23FLOAT32ABCDVRead
IR204doc 30205V31FLOAT32ABCDVRead
IR206doc 30207VTHD-RFLOAT32ABCD%Read
IR208doc 30209VTHD-YFLOAT32ABCD%Read
IR210doc 30211VTHD-BFLOAT32ABCD%Read
IR212doc 30213I THD-RFLOAT32ABCD%Read
IR214doc 30215I THD-YFLOAT32ABCD%Read
IR216doc 30217I THD -BFLOAT32ABCD%Read
IR218doc 30219System V-THDFLOAT32ABCD%Read
IR220doc 30221System I-THDFLOAT32ABCD%Read
IR224doc 30225Neutral Current (3P4W only)FLOAT32ABCDARead
IR226doc 30227Run hourFLOAT32ABCDhRead
IR228doc 30229On HourFLOAT32ABCDhRead
IR230doc 30231No. of interruptsFLOAT32ABCDRead
IR1800doc 31801Sys Active Energy ImportFLOAT32ABCDkWhRead
IR1802doc 31803Sys Active Energy ExportFLOAT32ABCDkWhRead
IR1804doc 31805Sys Reactive Energy ImportFLOAT32ABCDkvarhRead
IR1806doc 31807Sys Reactive Energy ExportFLOAT32ABCDkvarhRead
IR1808doc 31809Sys Apparent EnergyFLOAT32ABCDkVAhRead
IR1848doc 31849Sys Total Active EnergyFLOAT32ABCDkWhRead
IR1850doc 31851Sys Total Reactive EnergyFLOAT32ABCDkvarhRead
IR1852doc 31853Sys Total Apparent EnergyFLOAT32ABCDkVAhRead
IR1874doc 31875Active Energy Import L2FLOAT32ABCDkWhRead
IR1876doc 31877Active Energy Import L3FLOAT32ABCDkWhRead
IR1878doc 31879Active Energy Export L1FLOAT32ABCDkWhRead
IR1880doc 31881Active Energy Export L2FLOAT32ABCDkWhRead
IR1882doc 31883Active Energy Export L3FLOAT32ABCDkWhRead
IR1884doc 31885Reactive Energy Import L1FLOAT32ABCDkvarhRead
IR1886doc 31887Reactive Energy Import L2FLOAT32ABCDkvarhRead
IR1888doc 31889Reactive Energy Import L3FLOAT32ABCDkvarhRead
IR1890doc 31891Reactive Energy ExportL1FLOAT32ABCDkvarhRead
IR1892doc 31893Reactive Energy ExportL2FLOAT32ABCDkvarhRead
IR1894doc 31895Reactive Energy Export L3FLOAT32ABCDkvarhRead
IR1896doc 31897Apparent Energy L1FLOAT32ABCDkVAhRead
IR1898doc 31899Apparent Energy L2FLOAT32ABCDkVAhRead
IR1900doc 31901Apparent Energy L3FLOAT32ABCDkVAhRead
IR1908doc 31909Total Active Energy L1FLOAT32ABCDkWhRead
IR1910doc 31911Total Active Energy L2FLOAT32ABCDkWhRead
IR1912doc 31913Total Active Energy L3FLOAT32ABCDkWhRead
IR1914doc 31915Total Reactive Energy L1FLOAT32ABCDkvarhRead
IR1916doc 31917Total Reactive Energy L2FLOAT32ABCDkvarhRead
IR1918doc 31919Total Reactive Energy L3FLOAT32ABCDkvarhRead
IR1920doc 31921Total Apparent Energy L1FLOAT32ABCDkVAhRead
IR1922doc 31923Total Apparent Energy L2FLOAT32ABCDkVAhRead
IR1924doc 31925Total Apparent Energy L3FLOAT32ABCDkVAhRead
IR4000doc 34001Tariff 1 Total KWh EnergyFLOAT32ABCDkWhRead
IR4002doc 34003Tarif 1 Import KWh EnergyFLOAT32ABCDkWhRead
IR4004doc 34005Tariff 1 Export KWh EnergyFLOAT32ABCDkWhRead
IR4006doc 34007Tariff 1 Total KVArh EnergyFLOAT32ABCDkvarhRead
IR4008doc 34009Tariff 1 Import KVArh EnergyFLOAT32ABCDkvarhRead
IR4010doc 34011Tariff 1 Export KVArh EnergyFLOAT32ABCDkvarhRead
IR4024doc 34025Tariff 2 Total KWh EnergyFLOAT32ABCDkWhRead
IR4026doc 34027Tariff 2 Import KWh EnergyFLOAT32ABCDkWhRead
IR4028doc 34029Tariff 2 Export KWh EnergyFLOAT32ABCDkWhRead
IR4030doc 34031Tariff 2 Total KVAr EnergyFLOAT32ABCDkvarRead
IR4032doc 34033Tariff 2 Import KVAr EnergyFLOAT32ABCDkvarRead
IR4034doc 34035Tariff 2 Export KVAr EnergyFLOAT32ABCDkvarRead
HR6002doc 46003System TypeSetup parameter (float).FLOAT32ABCDRead
HR6004doc 46005PT PrimarySetup parameter (float).FLOAT32ABCDRead
HR6006doc 46007CT PrimarySetup parameter (float).FLOAT32ABCDRead
HR6008doc 46009PT SecondarySetup parameter (float).FLOAT32ABCDRead
HR6010doc 46011CT SecondarySetup parameter (float).FLOAT32ABCDRead
HR6356doc 46357Version NoSetup parameter (float).FLOAT32ABCDRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters

What Modbus registers does the Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters have?

This map lists 132 registers: 126 input registers, 6 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 30001/40001-style addresses next to the hex start address actually sent (30001 = 0x0000). Wire address = printed number - 30001 (input registers) or - 40001 (holding registers); every value here was cross-checked against the printed hex address.

What byte order does the Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters?

Start with IR 0 Voltage L1 (Voltage L12 for 3P3W) (Voltage L1); IR 6 Current L1 (Current L1); IR 52 Watt Sum (Total active power (Watt Sum)); IR 70 Freq (Frequency); IR 72 Wh import (Active energy import); IR 62 PF Avg (Average power factor).

How do I enable Modbus control of the Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters?

Modbus RTU on RS-485 is built in; set the slave address, baud rate and parity from the meter's setup menu or the RS-485 setup register.

Where is the official Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters Modbus documentation?

The source is EC43XX / ER43XX Interface Definition (DMAN-00IM-09xx Rev. F), revision 2025-11, published free by Rishabh Instruments at https://rishabh.co.in/uploads/product/rish-ec43x1-260/RISH_EC43XX_ER43XX_INTERFACE_DEFINITION_REV_F.pdf.

More Rishabh Instruments Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: EC43XX / ER43XX Interface Definition · DMAN-00IM-09xx Rev. F · rev. 2025-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.