Easy Modbus
  1. Home
  2. Modbus register maps
  3. Seneca
  4. R203 three-phase power analyzer (Ethernet + RS-485)

Power meter (three-phase network analyzer) · Modbus register map

Seneca R203 three-phase power analyzer (Ethernet + RS-485) Modbus register map

Updated 17 November 2026

Short answer

The Seneca R203 is a DIN-rail three-phase network analyzer with harmonic analysis, digital I/O and a data logger. It serves Modbus TCP on Ethernet and Modbus RTU on RS-485 from one holding-register table. This map covers identity and status, instantaneous electrical values, THD, fundamentals, 64-bit energy counters, system values and the two pulse counters.

This page lists 88 Modbus registers for the Seneca R203 three-phase power analyzer (Ethernet + RS-485) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.

Manufacturer
Seneca
Model
R203 three-phase power analyzer (Ethernet + RS-485)
Equipment type
Power meter (three-phase network analyzer)
Registers
88 (33 writable)
Transport
Modbus TCP, Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8N1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
R203-1, R203-2, Seneca R203
Source document
User Manual R203-1 / R203-2 · MI-00591-4-EN (rev 4) · rev. 2023-02-16
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Seneca R203 three-phase power analyzer (Ethernet + RS-485)

Integration in brief

Read the instantaneous float block 100-187 in one or two requests, and the three-phase 64-bit energy totals at 1878-1905. Status at 17 flags reversed CTs and wiring errors during commissioning.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100Voltage L1-L2FLOAT32 ABCDLine voltage L1-L2Read
HR 106Current L1FLOAT32 ABCDCurrent L1Read
HR 168Active power totalFLOAT32 ABCDTotal active powerRead
HR 174Power factor totalFLOAT32 ABCDTotal power factorRead
HR 144Frequency L1FLOAT32 ABCDFrequencyRead
HR 1878Active energy imported totalUINT64 ABCDImported active energy totalRead/write
HR 1882Active energy exported totalUINT64 ABCDExported active energy totalRead/write
HR 17StatusBITMAP16Status and wiring error flagsRead/write

Enable Modbus control & writes

The Modbus TCP server and RTU slave are active by default. Network and serial parameters are set with the Easy Setup 2 software or the web server.

Communication loss & watchdog

The manual documents a Modbus TCP connection timeout (default 60 s) that closes idle client connections; no output watchdog is described.

Byte order & addressing

Network setup

Watch out for

Seneca R203 three-phase power analyzer (Ethernet + RS-485) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

88 of 88 shown
Seneca R203 three-phase power analyzer (Ethernet + RS-485) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Machine IDDevice identification code.UINT16Read
HR1doc 40002Firmware revision (major/minor)UINT16Read
HR2doc 40003Firmware revision (fix/build)UINT16Read
HR3doc 40004Firmware codeUINT16Read
HR6doc 40007Board IDHardware revision.UINT16Read
HR16doc 40017CommandWrite 49568 to reboot the meter.UINT16Read/write49568 = Reboot
HR17doc 40018StatusWiring, alarm and digital I/O status flags.BITMAP16Read/writebit 0 = Cyclic phase sequence error; bit 1 = Alarm active; bit 2 = DOUT1 active; bit 3 = DOUT2 active; bit 4 = DIN1 high; bit 5 = DIN2 high; bit 6 = Current cutoff active; bit 7 = L1 CT connected reversed; bit 8 = L2 CT connected reversed; bit 9 = L3 CT connected reversed; bit 10 = Line 1 voltage/current connection error; bit 11 = Line 2 voltage/current connection error; bit 12 = Line 3 voltage/current connection error
HR21doc 40022Digital inputsBITMAP16Read/writebit 0 = Input 1; bit 1 = Input 2
HR22doc 40023Digital outputsBITMAP16Read/writebit 0 = Output 1; bit 1 = Output 2
HR26doc 40027Analog output manual valueOutput level in manual mode: 0 = 0 %, 8190 = 100 %.UINT16Read/write
HR100doc 40101Voltage L1-L2RMS line-to-line voltage.FLOAT32ABCDVRead
HR102doc 40103Voltage L2-L3RMS line-to-line voltage.FLOAT32ABCDVRead
HR104doc 40105Voltage L3-L1RMS line-to-line voltage.FLOAT32ABCDVRead
HR106doc 40107Current L1RMS current.FLOAT32ABCDARead
HR108doc 40109Current L2RMS current.FLOAT32ABCDARead
HR110doc 40111Current L3RMS current.FLOAT32ABCDARead
HR112doc 40113Current NRMS current.FLOAT32ABCDARead
HR114doc 40115V-I phase angle L1Angle between voltage and current.FLOAT32ABCD°Read
HR116doc 40117V-I phase angle L2Angle between voltage and current.FLOAT32ABCD°Read
HR118doc 40119V-I phase angle L3Angle between voltage and current.FLOAT32ABCD°Read
HR120doc 40121Active power L1Positive = absorbed, negative = generated.FLOAT32ABCDWRead
HR122doc 40123Active power L2Positive = absorbed, negative = generated.FLOAT32ABCDWRead
HR124doc 40125Active power L3Positive = absorbed, negative = generated.FLOAT32ABCDWRead
HR126doc 40127Reactive power L1FLOAT32ABCDVARRead
HR128doc 40129Reactive power L2FLOAT32ABCDVARRead
HR130doc 40131Reactive power L3FLOAT32ABCDVARRead
HR132doc 40133Apparent power L1FLOAT32ABCDVARead
HR134doc 40135Apparent power L2FLOAT32ABCDVARead
HR136doc 40137Apparent power L3FLOAT32ABCDVARead
HR138doc 40139Power factor L1Positive = load (user), negative = generator.FLOAT32ABCDRead
HR140doc 40141Power factor L2Positive = load (user), negative = generator.FLOAT32ABCDRead
HR142doc 40143Power factor L3Positive = load (user), negative = generator.FLOAT32ABCDRead
HR144doc 40145Frequency L1FLOAT32ABCDHzRead
HR146doc 40147Frequency L2FLOAT32ABCDHzRead
HR148doc 40149Frequency L3FLOAT32ABCDHzRead
HR150doc 40151Period L1FLOAT32ABCDsRead
HR152doc 40153Period L2FLOAT32ABCDsRead
HR154doc 40155Period L3FLOAT32ABCDsRead
HR156doc 40157V-V phase angle L1-L2Angle between two line voltages.FLOAT32ABCD°Read
HR158doc 40159V-V phase angle L2-L3Angle between two line voltages.FLOAT32ABCD°Read
HR160doc 40161V-V phase angle L3-L1Angle between two line voltages.FLOAT32ABCD°Read
HR162doc 40163Voltage L1-NRMS phase-to-neutral voltage.FLOAT32ABCDVRead
HR164doc 40165Voltage L2-NRMS phase-to-neutral voltage.FLOAT32ABCDVRead
HR166doc 40167Voltage L3-NRMS phase-to-neutral voltage.FLOAT32ABCDVRead
HR168doc 40169Active power totalPositive = absorbed, negative = generated.FLOAT32ABCDWRead
HR170doc 40171Reactive power totalFLOAT32ABCDVARRead
HR172doc 40173Apparent power totalFLOAT32ABCDVARead
HR174doc 40175Power factor totalPositive = load (user), negative = generator.FLOAT32ABCDRead
HR176doc 40177Voltage THD L1Total harmonic distortion relative to the fundamental.FLOAT32ABCD%Read
HR178doc 40179Voltage THD L2Total harmonic distortion relative to the fundamental.FLOAT32ABCD%Read
HR180doc 40181Voltage THD L3Total harmonic distortion relative to the fundamental.FLOAT32ABCD%Read
HR182doc 40183Current THD L1Total harmonic distortion relative to the fundamental.FLOAT32ABCD%Read
HR184doc 40185Current THD L2Total harmonic distortion relative to the fundamental.FLOAT32ABCD%Read
HR186doc 40187Current THD L3Total harmonic distortion relative to the fundamental.FLOAT32ABCD%Read
HR188doc 40189Fundamental voltage L1-NRMS of the fundamental only.FLOAT32ABCDVRead
HR190doc 40191Fundamental voltage L2-NRMS of the fundamental only.FLOAT32ABCDVRead
HR192doc 40193Fundamental voltage L3-NRMS of the fundamental only.FLOAT32ABCDVRead
HR518doc 40519Fundamental current L1RMS of the fundamental only.FLOAT32ABCDARead
HR520doc 40521Fundamental current L2RMS of the fundamental only.FLOAT32ABCDARead
HR522doc 40523Fundamental current L3RMS of the fundamental only.FLOAT32ABCDARead
HR1746doc 41747Active energy imported L1Import only (Q1/Q4).UINT64ABCDWhRead/write
HR1750doc 41751Active energy imported L2Import only (Q1/Q4).UINT64ABCDWhRead/write
HR1754doc 41755Active energy imported L3Import only (Q1/Q4).UINT64ABCDWhRead/write
HR1758doc 41759Active energy exported L1Export only (Q2/Q3).UINT64ABCDWhRead/write
HR1762doc 41763Active energy exported L2Export only (Q2/Q3).UINT64ABCDWhRead/write
HR1766doc 41767Active energy exported L3Export only (Q2/Q3).UINT64ABCDWhRead/write
HR1770doc 41771Reactive energy positive L1Q1 + Q2.UINT64ABCDVARhRead/write
HR1774doc 41775Reactive energy positive L2Q1 + Q2.UINT64ABCDVARhRead/write
HR1778doc 41779Reactive energy positive L3Q1 + Q2.UINT64ABCDVARhRead/write
HR1782doc 41783Reactive energy negative L1Q3 + Q4.UINT64ABCDVARhRead/write
HR1786doc 41787Reactive energy negative L2Q3 + Q4.UINT64ABCDVARhRead/write
HR1790doc 41791Reactive energy negative L3Q3 + Q4.UINT64ABCDVARhRead/write
HR1846doc 41847Active energy net L2Signed import/export balance.INT64ABCDWhRead/write
HR1850doc 41851Active energy net L3Signed import/export balance.INT64ABCDWhRead/write
HR1854doc 41855Reactive energy net L1Signed balance.INT64ABCDVARhRead/write
HR1858doc 41859Reactive energy net L2Signed balance.INT64ABCDVARhRead/write
HR1862doc 41863Reactive energy net L3Signed balance.INT64ABCDVARhRead/write
HR1878doc 41879Active energy imported totalThree-phase, import only (Q1/Q4).UINT64ABCDWhRead/write
HR1882doc 41883Active energy exported totalThree-phase, export only (Q2/Q3).UINT64ABCDWhRead/write
HR1886doc 41887Reactive energy positive totalThree-phase, Q1 + Q2.UINT64ABCDVARhRead/write
HR1890doc 41891Reactive energy negative totalThree-phase, Q3 + Q4.UINT64ABCDVARhRead/write
HR1894doc 41895Active energy net totalThree-phase signed balance.INT64ABCDWhRead/write
HR1898doc 41899Reactive energy net totalThree-phase signed balance.INT64ABCDVARhRead/write
HR1902doc 41903Apparent energy totalThree-phase apparent energy.INT64ABCDVAhRead/write
HR1994doc 41995System voltageAverage of the three phase voltages.FLOAT32ABCDVRead/write
HR1996doc 41997System currentSystem current value as labelled in the table.FLOAT32ABCDARead/write
HR2018doc 42019Digital input 1 counterUINT32ABCDRead/write
HR2020doc 42021Digital input 2 counterUINT32ABCDRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Seneca R203 three-phase power analyzer (Ethernet + RS-485)

What Modbus registers does the Seneca R203 three-phase power analyzer (Ethernet + RS-485) have?

This map lists 88 registers: 88 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Seneca R203 three-phase power analyzer (Ethernet + RS-485) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each table row prints the 4x number (40001) beside a 0-based ADDRESS OFFSET (0); the manual's addressing chapter says the offset is the 0-based address. Request the offset on the wire.

What byte order does the Seneca R203 three-phase power analyzer (Ethernet + RS-485) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Seneca R203 three-phase power analyzer (Ethernet + RS-485)?

Start with HR 100 Voltage L1-L2 (Line voltage L1-L2); HR 106 Current L1 (Current L1); HR 168 Active power total (Total active power); HR 174 Power factor total (Total power factor); HR 144 Frequency L1 (Frequency); HR 1878 Active energy imported total (Imported active energy total); HR 1882 Active energy exported total (Exported active energy total); HR 17 Status (Status and wiring error flags).

How do I enable Modbus control of the Seneca R203 three-phase power analyzer (Ethernet + RS-485)?

The Modbus TCP server and RTU slave are active by default. Network and serial parameters are set with the Easy Setup 2 software or the web server.

What happens when the Seneca R203 three-phase power analyzer (Ethernet + RS-485) loses Modbus communication?

The manual documents a Modbus TCP connection timeout (default 60 s) that closes idle client connections; no output watchdog is described.

Where is the official Seneca R203 three-phase power analyzer (Ethernet + RS-485) Modbus documentation?

The source is User Manual R203-1 / R203-2 (MI-00591-4-EN (rev 4)), revision 2023-02-16, published free by Seneca at https://www.seneca.it/media/6849393/mi00591-4-en.pdf.

More Seneca Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: User Manual R203-1 / R203-2 · MI-00591-4-EN (rev 4) · rev. 2023-02-16. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.