Power meter (three-phase network analyzer) · Modbus register map
Seneca R203 three-phase power analyzer (Ethernet + RS-485) Modbus register map
Updated 17 November 2026
The Seneca R203 is a DIN-rail three-phase network analyzer with harmonic analysis, digital I/O and a data logger. It serves Modbus TCP on Ethernet and Modbus RTU on RS-485 from one holding-register table. This map covers identity and status, instantaneous electrical values, THD, fundamentals, 64-bit energy counters, system values and the two pulse counters.
This page lists 88 Modbus registers for the Seneca R203 three-phase power analyzer (Ethernet + RS-485) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seneca
- Model
- R203 three-phase power analyzer (Ethernet + RS-485)
- Equipment type
- Power meter (three-phase network analyzer)
- Registers
- 88 (33 writable)
- Transport
- Modbus TCP, Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- R203-1, R203-2, Seneca R203
Integration notes: Seneca R203 three-phase power analyzer (Ethernet + RS-485)
Read the instantaneous float block 100-187 in one or two requests, and the three-phase 64-bit energy totals at 1878-1905. Status at 17 flags reversed CTs and wiring errors during commissioning.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 100 | Voltage L1-L2 | FLOAT32 ABCD | Line voltage L1-L2 | Read |
| HR 106 | Current L1 | FLOAT32 ABCD | Current L1 | Read |
| HR 168 | Active power total | FLOAT32 ABCD | Total active power | Read |
| HR 174 | Power factor total | FLOAT32 ABCD | Total power factor | Read |
| HR 144 | Frequency L1 | FLOAT32 ABCD | Frequency | Read |
| HR 1878 | Active energy imported total | UINT64 ABCD | Imported active energy total | Read/write |
| HR 1882 | Active energy exported total | UINT64 ABCD | Exported active energy total | Read/write |
| HR 17 | Status | BITMAP16 | Status and wiring error flags | Read/write |
Enable Modbus control & writes
The Modbus TCP server and RTU slave are active by default. Network and serial parameters are set with the Easy Setup 2 software or the web server.
Communication loss & watchdog
The manual documents a Modbus TCP connection timeout (default 60 s) that closes idle client connections; no output watchdog is described.
Byte order & addressing
- Table offsets are the wire addresses; 4x numbers are offset + 40001.
- 32-bit floats are MSW first and 64-bit energies MMSW first as printed in the tables.
Network setup
- Factory IP is 192.168.90.101: change it before putting a second unit on the same network.
- RS-485 defaults to 38400 baud, 8 data bits, no parity, 1 stop bit; the manual does not print a default RTU station address.
Watch out for
- Check status bits 7-12 after wiring: reversed CTs and voltage/current mismatches are flagged there.
- Power sign follows the quadrant convention: negative active power means generation.
Seneca R203 three-phase power analyzer (Ethernet + RS-485) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Machine ID | Device identification code. | UINT16 | Read | ||||
| HR | 1doc 40002 | Firmware revision (major/minor) | UINT16 | Read | |||||
| HR | 2doc 40003 | Firmware revision (fix/build) | UINT16 | Read | |||||
| HR | 3doc 40004 | Firmware code | UINT16 | Read | |||||
| HR | 6doc 40007 | Board ID | Hardware revision. | UINT16 | Read | ||||
| HR | 16doc 40017 | Command | Write 49568 to reboot the meter. | UINT16 | Read/write | 49568 = Reboot | |||
| HR | 17doc 40018 | Status | Wiring, alarm and digital I/O status flags. | BITMAP16 | Read/write | bit 0 = Cyclic phase sequence error; bit 1 = Alarm active; bit 2 = DOUT1 active; bit 3 = DOUT2 active; bit 4 = DIN1 high; bit 5 = DIN2 high; bit 6 = Current cutoff active; bit 7 = L1 CT connected reversed; bit 8 = L2 CT connected reversed; bit 9 = L3 CT connected reversed; bit 10 = Line 1 voltage/current connection error; bit 11 = Line 2 voltage/current connection error; bit 12 = Line 3 voltage/current connection error | |||
| HR | 21doc 40022 | Digital inputs | BITMAP16 | Read/write | bit 0 = Input 1; bit 1 = Input 2 | ||||
| HR | 22doc 40023 | Digital outputs | BITMAP16 | Read/write | bit 0 = Output 1; bit 1 = Output 2 | ||||
| HR | 26doc 40027 | Analog output manual value | Output level in manual mode: 0 = 0 %, 8190 = 100 %. | UINT16 | Read/write | ||||
| HR | 100doc 40101 | Voltage L1-L2 | RMS line-to-line voltage. | FLOAT32 | ABCD | V | Read | ||
| HR | 102doc 40103 | Voltage L2-L3 | RMS line-to-line voltage. | FLOAT32 | ABCD | V | Read | ||
| HR | 104doc 40105 | Voltage L3-L1 | RMS line-to-line voltage. | FLOAT32 | ABCD | V | Read | ||
| HR | 106doc 40107 | Current L1 | RMS current. | FLOAT32 | ABCD | A | Read | ||
| HR | 108doc 40109 | Current L2 | RMS current. | FLOAT32 | ABCD | A | Read | ||
| HR | 110doc 40111 | Current L3 | RMS current. | FLOAT32 | ABCD | A | Read | ||
| HR | 112doc 40113 | Current N | RMS current. | FLOAT32 | ABCD | A | Read | ||
| HR | 114doc 40115 | V-I phase angle L1 | Angle between voltage and current. | FLOAT32 | ABCD | ° | Read | ||
| HR | 116doc 40117 | V-I phase angle L2 | Angle between voltage and current. | FLOAT32 | ABCD | ° | Read | ||
| HR | 118doc 40119 | V-I phase angle L3 | Angle between voltage and current. | FLOAT32 | ABCD | ° | Read | ||
| HR | 120doc 40121 | Active power L1 | Positive = absorbed, negative = generated. | FLOAT32 | ABCD | W | Read | ||
| HR | 122doc 40123 | Active power L2 | Positive = absorbed, negative = generated. | FLOAT32 | ABCD | W | Read | ||
| HR | 124doc 40125 | Active power L3 | Positive = absorbed, negative = generated. | FLOAT32 | ABCD | W | Read | ||
| HR | 126doc 40127 | Reactive power L1 | FLOAT32 | ABCD | VAR | Read | |||
| HR | 128doc 40129 | Reactive power L2 | FLOAT32 | ABCD | VAR | Read | |||
| HR | 130doc 40131 | Reactive power L3 | FLOAT32 | ABCD | VAR | Read | |||
| HR | 132doc 40133 | Apparent power L1 | FLOAT32 | ABCD | VA | Read | |||
| HR | 134doc 40135 | Apparent power L2 | FLOAT32 | ABCD | VA | Read | |||
| HR | 136doc 40137 | Apparent power L3 | FLOAT32 | ABCD | VA | Read | |||
| HR | 138doc 40139 | Power factor L1 | Positive = load (user), negative = generator. | FLOAT32 | ABCD | Read | |||
| HR | 140doc 40141 | Power factor L2 | Positive = load (user), negative = generator. | FLOAT32 | ABCD | Read | |||
| HR | 142doc 40143 | Power factor L3 | Positive = load (user), negative = generator. | FLOAT32 | ABCD | Read | |||
| HR | 144doc 40145 | Frequency L1 | FLOAT32 | ABCD | Hz | Read | |||
| HR | 146doc 40147 | Frequency L2 | FLOAT32 | ABCD | Hz | Read | |||
| HR | 148doc 40149 | Frequency L3 | FLOAT32 | ABCD | Hz | Read | |||
| HR | 150doc 40151 | Period L1 | FLOAT32 | ABCD | s | Read | |||
| HR | 152doc 40153 | Period L2 | FLOAT32 | ABCD | s | Read | |||
| HR | 154doc 40155 | Period L3 | FLOAT32 | ABCD | s | Read | |||
| HR | 156doc 40157 | V-V phase angle L1-L2 | Angle between two line voltages. | FLOAT32 | ABCD | ° | Read | ||
| HR | 158doc 40159 | V-V phase angle L2-L3 | Angle between two line voltages. | FLOAT32 | ABCD | ° | Read | ||
| HR | 160doc 40161 | V-V phase angle L3-L1 | Angle between two line voltages. | FLOAT32 | ABCD | ° | Read | ||
| HR | 162doc 40163 | Voltage L1-N | RMS phase-to-neutral voltage. | FLOAT32 | ABCD | V | Read | ||
| HR | 164doc 40165 | Voltage L2-N | RMS phase-to-neutral voltage. | FLOAT32 | ABCD | V | Read | ||
| HR | 166doc 40167 | Voltage L3-N | RMS phase-to-neutral voltage. | FLOAT32 | ABCD | V | Read | ||
| HR | 168doc 40169 | Active power total | Positive = absorbed, negative = generated. | FLOAT32 | ABCD | W | Read | ||
| HR | 170doc 40171 | Reactive power total | FLOAT32 | ABCD | VAR | Read | |||
| HR | 172doc 40173 | Apparent power total | FLOAT32 | ABCD | VA | Read | |||
| HR | 174doc 40175 | Power factor total | Positive = load (user), negative = generator. | FLOAT32 | ABCD | Read | |||
| HR | 176doc 40177 | Voltage THD L1 | Total harmonic distortion relative to the fundamental. | FLOAT32 | ABCD | % | Read | ||
| HR | 178doc 40179 | Voltage THD L2 | Total harmonic distortion relative to the fundamental. | FLOAT32 | ABCD | % | Read | ||
| HR | 180doc 40181 | Voltage THD L3 | Total harmonic distortion relative to the fundamental. | FLOAT32 | ABCD | % | Read | ||
| HR | 182doc 40183 | Current THD L1 | Total harmonic distortion relative to the fundamental. | FLOAT32 | ABCD | % | Read | ||
| HR | 184doc 40185 | Current THD L2 | Total harmonic distortion relative to the fundamental. | FLOAT32 | ABCD | % | Read | ||
| HR | 186doc 40187 | Current THD L3 | Total harmonic distortion relative to the fundamental. | FLOAT32 | ABCD | % | Read | ||
| HR | 188doc 40189 | Fundamental voltage L1-N | RMS of the fundamental only. | FLOAT32 | ABCD | V | Read | ||
| HR | 190doc 40191 | Fundamental voltage L2-N | RMS of the fundamental only. | FLOAT32 | ABCD | V | Read | ||
| HR | 192doc 40193 | Fundamental voltage L3-N | RMS of the fundamental only. | FLOAT32 | ABCD | V | Read | ||
| HR | 518doc 40519 | Fundamental current L1 | RMS of the fundamental only. | FLOAT32 | ABCD | A | Read | ||
| HR | 520doc 40521 | Fundamental current L2 | RMS of the fundamental only. | FLOAT32 | ABCD | A | Read | ||
| HR | 522doc 40523 | Fundamental current L3 | RMS of the fundamental only. | FLOAT32 | ABCD | A | Read | ||
| HR | 1746doc 41747 | Active energy imported L1 | Import only (Q1/Q4). | UINT64 | ABCD | Wh | Read/write | ||
| HR | 1750doc 41751 | Active energy imported L2 | Import only (Q1/Q4). | UINT64 | ABCD | Wh | Read/write | ||
| HR | 1754doc 41755 | Active energy imported L3 | Import only (Q1/Q4). | UINT64 | ABCD | Wh | Read/write | ||
| HR | 1758doc 41759 | Active energy exported L1 | Export only (Q2/Q3). | UINT64 | ABCD | Wh | Read/write | ||
| HR | 1762doc 41763 | Active energy exported L2 | Export only (Q2/Q3). | UINT64 | ABCD | Wh | Read/write | ||
| HR | 1766doc 41767 | Active energy exported L3 | Export only (Q2/Q3). | UINT64 | ABCD | Wh | Read/write | ||
| HR | 1770doc 41771 | Reactive energy positive L1 | Q1 + Q2. | UINT64 | ABCD | VARh | Read/write | ||
| HR | 1774doc 41775 | Reactive energy positive L2 | Q1 + Q2. | UINT64 | ABCD | VARh | Read/write | ||
| HR | 1778doc 41779 | Reactive energy positive L3 | Q1 + Q2. | UINT64 | ABCD | VARh | Read/write | ||
| HR | 1782doc 41783 | Reactive energy negative L1 | Q3 + Q4. | UINT64 | ABCD | VARh | Read/write | ||
| HR | 1786doc 41787 | Reactive energy negative L2 | Q3 + Q4. | UINT64 | ABCD | VARh | Read/write | ||
| HR | 1790doc 41791 | Reactive energy negative L3 | Q3 + Q4. | UINT64 | ABCD | VARh | Read/write | ||
| HR | 1846doc 41847 | Active energy net L2 | Signed import/export balance. | INT64 | ABCD | Wh | Read/write | ||
| HR | 1850doc 41851 | Active energy net L3 | Signed import/export balance. | INT64 | ABCD | Wh | Read/write | ||
| HR | 1854doc 41855 | Reactive energy net L1 | Signed balance. | INT64 | ABCD | VARh | Read/write | ||
| HR | 1858doc 41859 | Reactive energy net L2 | Signed balance. | INT64 | ABCD | VARh | Read/write | ||
| HR | 1862doc 41863 | Reactive energy net L3 | Signed balance. | INT64 | ABCD | VARh | Read/write | ||
| HR | 1878doc 41879 | Active energy imported total | Three-phase, import only (Q1/Q4). | UINT64 | ABCD | Wh | Read/write | ||
| HR | 1882doc 41883 | Active energy exported total | Three-phase, export only (Q2/Q3). | UINT64 | ABCD | Wh | Read/write | ||
| HR | 1886doc 41887 | Reactive energy positive total | Three-phase, Q1 + Q2. | UINT64 | ABCD | VARh | Read/write | ||
| HR | 1890doc 41891 | Reactive energy negative total | Three-phase, Q3 + Q4. | UINT64 | ABCD | VARh | Read/write | ||
| HR | 1894doc 41895 | Active energy net total | Three-phase signed balance. | INT64 | ABCD | Wh | Read/write | ||
| HR | 1898doc 41899 | Reactive energy net total | Three-phase signed balance. | INT64 | ABCD | VARh | Read/write | ||
| HR | 1902doc 41903 | Apparent energy total | Three-phase apparent energy. | INT64 | ABCD | VAh | Read/write | ||
| HR | 1994doc 41995 | System voltage | Average of the three phase voltages. | FLOAT32 | ABCD | V | Read/write | ||
| HR | 1996doc 41997 | System current | System current value as labelled in the table. | FLOAT32 | ABCD | A | Read/write | ||
| HR | 2018doc 42019 | Digital input 1 counter | UINT32 | ABCD | Read/write | ||||
| HR | 2020doc 42021 | Digital input 2 counter | UINT32 | ABCD | Read/write |
Notes on this map
- Only function codes 03, 06 and 16 are supported; everything is a holding register.
- Every 32-bit row is marked MSW at the lower address and every 64-bit energy is marked MMSW first, so the map uses ABCD. The manual says the two words can be swapped when reading; this map follows the order printed in the tables.
- Energy totals are in Wh / VARh / VAh as unsigned or signed 64-bit integers as printed.
- Left out: the per-harmonic voltage and current tables, the averaged and min/max values from 41497 upward, and the L1 net active energy (41843), which is typed UNSIGNED64 while its L2/L3 siblings are SIGNED64.
- Left out: the per-phase apparent energy rows 41867-41878, whose register name says reactive energy while the description says apparent energy.
- Factory network settings: static IP 192.168.90.101, gateway 192.168.90.1, Modbus TCP port 502, TCP station address 1; RS-485 38400 baud 8N1.
- RW* registers live in flash and tolerate about 10,000 writes.
- Left out: the demand averaging time (45075), typed 32-bit but printed as a single row with no MSW/LSW marking.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seneca R203 three-phase power analyzer (Ethernet + RS-485)
What Modbus registers does the Seneca R203 three-phase power analyzer (Ethernet + RS-485) have?
This map lists 88 registers: 88 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seneca R203 three-phase power analyzer (Ethernet + RS-485) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each table row prints the 4x number (40001) beside a 0-based ADDRESS OFFSET (0); the manual's addressing chapter says the offset is the 0-based address. Request the offset on the wire.
What byte order does the Seneca R203 three-phase power analyzer (Ethernet + RS-485) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Seneca R203 three-phase power analyzer (Ethernet + RS-485)?
Start with HR 100 Voltage L1-L2 (Line voltage L1-L2); HR 106 Current L1 (Current L1); HR 168 Active power total (Total active power); HR 174 Power factor total (Total power factor); HR 144 Frequency L1 (Frequency); HR 1878 Active energy imported total (Imported active energy total); HR 1882 Active energy exported total (Exported active energy total); HR 17 Status (Status and wiring error flags).
How do I enable Modbus control of the Seneca R203 three-phase power analyzer (Ethernet + RS-485)?
The Modbus TCP server and RTU slave are active by default. Network and serial parameters are set with the Easy Setup 2 software or the web server.
What happens when the Seneca R203 three-phase power analyzer (Ethernet + RS-485) loses Modbus communication?
The manual documents a Modbus TCP connection timeout (default 60 s) that closes idle client connections; no output watchdog is described.
Where is the official Seneca R203 three-phase power analyzer (Ethernet + RS-485) Modbus documentation?
The source is User Manual R203-1 / R203-2 (MI-00591-4-EN (rev 4)), revision 2023-02-16, published free by Seneca at https://www.seneca.it/media/6849393/mi00591-4-en.pdf.
More Seneca Modbus register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2 - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN
Other power & energy meters register maps
- Power meter
Siemens SICAM P power meter (Modbus RTU/ASCII)
SICAM P (7KG7xxx) power meters with the Modbus serial interface, per manual E50417-B1076-C241-A5 (release 11.2012).
Also known as: 7KG7750, 7KG7751, 7KG7755, SICAM P50, SICAM P55, 7KG7610, 7KG7660 - Power meter
Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU)
Enercept H8035 (energy only) and H8036 (enhanced data stream) split-core three-phase power transducers, 100-2400 A, installation guide Z201686-0K.
Also known as: Enercept H8035, Enercept H8036, H8035-0100-2, H8035-0300-2, H8035-0400-3, H8035-0800-3, H8035-0800-4, H8035-1600-4, H8035-2400-4, H8036-0100-2, H8036-0300-2, H8036-0400-3, H8036-0800-3, H8036-0800-4, H8036-1600-4, H8036-2400-4 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Actuator / valve (pressure-independent control valve with energy metering)
Belimo Energy Valve DN 15-50 (Version 4) Modbus RTU / TCP
Belimo Energy Valve Version 4, DN 15-50 (EV..R2+(K)BAC, EV..R2+MID, EV..R3+BAC), per Energy Valve Modbus interface description en-gb 2023-08.
Also known as: EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Energy Valve 4 - Energy meter (energy analyzer)
Carlo Gavazzi EM210 (AV versions)
EM210 three-phase energy analyzers, AV input versions with the RS485 Modbus RTU option, protocol version 4 revision 3 (newest variables need firmware A.5/A.6).
Also known as: EM210, EM210-72D, EM210 AV - Energy meter
Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)
EM511 direct-connected single-phase DIN meters with RS485 and digital input (X, PFA, PFB, SFA versions), protocol rev. 1.8.
Also known as: EM511-IS, EM511DINAV81XS1X, EM511DINAV81XS1PFA, EM511DINAV81XS1PFB, EM511DINAV81XS1SFA
All power & energy meters Modbus register maps →
Source: User Manual R203-1 / R203-2 · MI-00591-4-EN (rev 4) · rev. 2023-02-16. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.