Sensor (I/O module, 8 analog inputs) · Modbus register map
Seneca Z-8AI 8-channel analog input module Modbus register map
Updated 17 November 2026
The Z-8AI reads eight ±10 V / ±20 mA analog inputs and reports each as a normalized 16-bit value over RS-485 Modbus RTU. All data are single 16-bit holding registers; each channel has electrical and normalized start/end scale settings and a flag word.
This page lists 54 Modbus registers for the Seneca Z-8AI 8-channel analog input module — 43 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seneca
- Model
- Z-8AI 8-channel analog input module
- Equipment type
- Sensor (I/O module, 8 analog inputs)
- Registers
- 54 (43 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Z-8AI
- Source document
- Z-8AI User Manual · MI00259-3-EN
Integration notes: Seneca Z-8AI 8-channel analog input module
Read holding registers 40003-40010 (wire 2-9) in one request for the eight normalized inputs; by default 0-10 V maps to 0-10000.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2 | IN1 normalized value | INT16 | IN1 | Read |
| HR 3 | IN2 normalized value | INT16 | IN2 | Read |
| HR 4 | IN3 normalized value | INT16 | IN3 | Read |
| HR 5 | IN4 normalized value | INT16 | IN4 | Read |
| HR 1 | Status | BITMAP16 | Status/error bits | Read/write |
| HR 62 | Errors | BITMAP16 | Error bits | Read |
Enable Modbus control & writes
Set the baud rate with DIP switches 1-2 and the address with switches 3-8; with switches 3-8 all OFF the address and baud come from EEPROM (40012/40013).
Byte order & addressing
- 40012 and 40013 each pack two byte-wide settings into one register.
- For a current input, set both the channel's input-type DIP switch (it enables the shunt) and bit 0 of the channel flags register.
Network setup
- DIP switches 9-10 enable the RS-485 terminator.
- Set bit 12 of 40002 to store changed settings in EEPROM.
Watch out for
- Check 40002 bits 13-15 and 40063 for EEPROM, configuration and ADC errors after changing settings.
Seneca Z-8AI 8-channel analog input module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Machine ID | High byte = module ID code (0x0E), low byte = module version. | UINT16 | Read | ||||
| HR | 1doc 40002 | Status | BITMAP16 | Read/write | bit 8 = Reset module (write 1); bit 12 = Save configuration to EEPROM (write 1); bit 13 = EEPROM memory error; bit 14 = Configuration error; bit 15 = Generic error | ||||
| HR | 2doc 40003 | IN1 normalized value | Input 1 scaled between its NSS and NES settings. | INT16 | Read | ||||
| HR | 3doc 40004 | IN2 normalized value | Input 2 scaled between its NSS and NES settings. | INT16 | Read | ||||
| HR | 4doc 40005 | IN3 normalized value | Input 3 scaled between its NSS and NES settings. | INT16 | Read | ||||
| HR | 5doc 40006 | IN4 normalized value | Input 4 scaled between its NSS and NES settings. | INT16 | Read | ||||
| HR | 6doc 40007 | IN5 normalized value | Input 5 scaled between its NSS and NES settings. | INT16 | Read | ||||
| HR | 7doc 40008 | IN6 normalized value | Input 6 scaled between its NSS and NES settings. | INT16 | Read | ||||
| HR | 8doc 40009 | IN7 normalized value | Input 7 scaled between its NSS and NES settings. | INT16 | Read | ||||
| HR | 9doc 40010 | IN8 normalized value | Input 8 scaled between its NSS and NES settings. | INT16 | Read | ||||
| HR | 11doc 40012 | RS485 address and parity | High byte = node address 1-255; low byte = parity (0 none, 1 even, 2 odd). | UINT16 | Read/write | ||||
| HR | 12doc 40013 | RS485 baud rate and delay | High byte = baud code (0=4800,1=9600,2=19200,3=38400,4=57600,5=115200,6=1200,7=2400), low byte = reply delay. | UINT16 | Read/write | ||||
| HR | 13doc 40014 | IN1 electrical start scale | ±10000 mV for voltage, ±20000 µA for current; default 0 mV. | INT16 | mV/µA | Read/write | |||
| HR | 14doc 40015 | IN1 electrical end scale | Default 10000 mV. | INT16 | mV/µA | Read/write | |||
| HR | 15doc 40016 | IN1 normalized start scale | ±32000, default 0. | INT16 | Read/write | ||||
| HR | 16doc 40017 | IN1 normalized end scale | ±32000, default 10000. | INT16 | Read/write | ||||
| HR | 18doc 40019 | IN1 flags | BITMAP16 | Read/write | bit 0 = Input type: 1 = current, 0 = voltage; bit 2 = Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms); bit 3 = Sampling time bit 1; bit 7 = Input enabled | ||||
| HR | 19doc 40020 | IN2 electrical start scale | ±10000 mV for voltage, ±20000 µA for current; default 0 mV. | INT16 | mV/µA | Read/write | |||
| HR | 20doc 40021 | IN2 electrical end scale | Default 10000 mV. | INT16 | mV/µA | Read/write | |||
| HR | 21doc 40022 | IN2 normalized start scale | ±32000, default 0. | INT16 | Read/write | ||||
| HR | 22doc 40023 | IN2 normalized end scale | ±32000, default 10000. | INT16 | Read/write | ||||
| HR | 24doc 40025 | IN2 flags | BITMAP16 | Read/write | bit 0 = Input type: 1 = current, 0 = voltage; bit 2 = Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms); bit 3 = Sampling time bit 1; bit 7 = Input enabled | ||||
| HR | 25doc 40026 | IN3 electrical start scale | ±10000 mV for voltage, ±20000 µA for current; default 0 mV. | INT16 | mV/µA | Read/write | |||
| HR | 26doc 40027 | IN3 electrical end scale | Default 10000 mV. | INT16 | mV/µA | Read/write | |||
| HR | 27doc 40028 | IN3 normalized start scale | ±32000, default 0. | INT16 | Read/write | ||||
| HR | 28doc 40029 | IN3 normalized end scale | ±32000, default 10000. | INT16 | Read/write | ||||
| HR | 30doc 40031 | IN3 flags | BITMAP16 | Read/write | bit 0 = Input type: 1 = current, 0 = voltage; bit 2 = Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms); bit 3 = Sampling time bit 1; bit 7 = Input enabled | ||||
| HR | 31doc 40032 | IN4 electrical start scale | ±10000 mV for voltage, ±20000 µA for current; default 0 mV. | INT16 | mV/µA | Read/write | |||
| HR | 32doc 40033 | IN4 electrical end scale | Default 10000 mV. | INT16 | mV/µA | Read/write | |||
| HR | 33doc 40034 | IN4 normalized start scale | ±32000, default 0. | INT16 | Read/write | ||||
| HR | 34doc 40035 | IN4 normalized end scale | ±32000, default 10000. | INT16 | Read/write | ||||
| HR | 36doc 40037 | IN4 flags | BITMAP16 | Read/write | bit 0 = Input type: 1 = current, 0 = voltage; bit 2 = Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms); bit 3 = Sampling time bit 1; bit 7 = Input enabled | ||||
| HR | 37doc 40038 | IN5 electrical start scale | ±10000 mV for voltage, ±20000 µA for current; default 0 mV. | INT16 | mV/µA | Read/write | |||
| HR | 38doc 40039 | IN5 electrical end scale | Default 10000 mV. | INT16 | mV/µA | Read/write | |||
| HR | 39doc 40040 | IN5 normalized start scale | ±32000, default 0. | INT16 | Read/write | ||||
| HR | 40doc 40041 | IN5 normalized end scale | ±32000, default 10000. | INT16 | Read/write | ||||
| HR | 42doc 40043 | IN5 flags | BITMAP16 | Read/write | bit 0 = Input type: 1 = current, 0 = voltage; bit 2 = Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms); bit 3 = Sampling time bit 1; bit 7 = Input enabled | ||||
| HR | 43doc 40044 | IN6 electrical start scale | ±10000 mV for voltage, ±20000 µA for current; default 0 mV. | INT16 | mV/µA | Read/write | |||
| HR | 44doc 40045 | IN6 electrical end scale | Default 10000 mV. | INT16 | mV/µA | Read/write | |||
| HR | 45doc 40046 | IN6 normalized start scale | ±32000, default 0. | INT16 | Read/write | ||||
| HR | 46doc 40047 | IN6 normalized end scale | ±32000, default 10000. | INT16 | Read/write | ||||
| HR | 48doc 40049 | IN6 flags | BITMAP16 | Read/write | bit 0 = Input type: 1 = current, 0 = voltage; bit 2 = Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms); bit 3 = Sampling time bit 1; bit 7 = Input enabled | ||||
| HR | 49doc 40050 | IN7 electrical start scale | ±10000 mV for voltage, ±20000 µA for current; default 0 mV. | INT16 | mV/µA | Read/write | |||
| HR | 50doc 40051 | IN7 electrical end scale | Default 10000 mV. | INT16 | mV/µA | Read/write | |||
| HR | 51doc 40052 | IN7 normalized start scale | ±32000, default 0. | INT16 | Read/write | ||||
| HR | 52doc 40053 | IN7 normalized end scale | ±32000, default 10000. | INT16 | Read/write | ||||
| HR | 54doc 40055 | IN7 flags | BITMAP16 | Read/write | bit 0 = Input type: 1 = current, 0 = voltage; bit 2 = Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms); bit 3 = Sampling time bit 1; bit 7 = Input enabled | ||||
| HR | 55doc 40056 | IN8 electrical start scale | ±10000 mV for voltage, ±20000 µA for current; default 0 mV. | INT16 | mV/µA | Read/write | |||
| HR | 56doc 40057 | IN8 electrical end scale | Default 10000 mV. | INT16 | mV/µA | Read/write | |||
| HR | 57doc 40058 | IN8 normalized start scale | ±32000, default 0. | INT16 | Read/write | ||||
| HR | 58doc 40059 | IN8 normalized end scale | ±32000, default 10000. | INT16 | Read/write | ||||
| HR | 60doc 40061 | IN8 flags | BITMAP16 | Read/write | bit 0 = Input type: 1 = current, 0 = voltage; bit 2 = Sampling time bit 0 (00=10 ms, 01=30 ms, 10=40 ms, 11=120 ms); bit 3 = Sampling time bit 1; bit 7 = Input enabled | ||||
| HR | 61doc 40062 | Firmware code | UINT16 | Read | |||||
| HR | 62doc 40063 | Errors | BITMAP16 | Read | bit 0 = ADC error; bit 8 = Calibration error in memory; bit 9 = Setting error in memory |
Notes on this map
- Every register is a single 16-bit word; there are no 32-bit values in this map.
- Address 1, 38400 baud and no parity are the EEPROM defaults; they apply only when the address DIP switches select 'from memory'. Otherwise the DIP switches set address and baud.
- The table has no registers 40011, 40018, 40024, 40030, 40036, 40042, 40048, 40054 or 40060; they are not listed.
- Scale units for the electrical start/end registers are mV for a voltage input and µA for a current input, set by the channel flag and DIP switches.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seneca Z-8AI 8-channel analog input module
What Modbus registers does the Seneca Z-8AI 8-channel analog input module have?
This map lists 54 registers: 54 holding registers. 43 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seneca Z-8AI 8-channel analog input module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints 4xxxx numbers (40001 = first holding register), so 40003 is wire address 2.
What are the minimum Modbus registers to integrate the Seneca Z-8AI 8-channel analog input module?
Start with HR 2 IN1 normalized value (IN1); HR 3 IN2 normalized value (IN2); HR 4 IN3 normalized value (IN3); HR 5 IN4 normalized value (IN4); HR 1 Status (Status/error bits); HR 62 Errors (Error bits).
How do I enable Modbus control of the Seneca Z-8AI 8-channel analog input module?
Set the baud rate with DIP switches 1-2 and the address with switches 3-8; with switches 3-8 all OFF the address and baud come from EEPROM (40012/40013).
Where is the official Seneca Z-8AI 8-channel analog input module Modbus documentation?
The source is Z-8AI User Manual (MI00259-3-EN), published free by Seneca at https://www.seneca.it/media/6849154/mi00259-3-en.pdf.
More Seneca Modbus register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2 - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN
Other remote i/o modules register maps
- Sensor (remote I/O module)
Unipi Technology Unipi Extension xS52 resistance input module
Unipi Extension xS52 RS-485 module per the Unipi Extension xS52 Modbus map v2.0.
Also known as: Unipi Extension xS52, xS52 - Sensor / remote I/O module
Brainboxes ED-588 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-588 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-588, ED588 - Sensor (remote I/O module)
Moxa ioLogik R1214 RS-485 remote I/O
ioLogik R1214 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1214, R1214, R1214-T - Sensor (Ethernet I/O module)
Teracom TCW241 Ethernet I/O module
TCW241 per the Teracom TCW241 user manual Revision R4.30, firmware v2.012 or later.
Also known as: TCW241 - Sensor (Ethernet digital I/O module)
Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP)
BusWorks XT1121-000 per user's manual 8500950P (revision P, 18 Nov 2022).
Also known as: XT1121-000, XT1121, BusWorks XT1121 - Sensor (PWM output and counter input module)
ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)
ICP DAS M-7088 eight-channel PWM output module with eight digital inputs and counters, Modbus RTU firmware.
Also known as: M-7088, M7088
All remote i/o modules Modbus register maps →
Source: Z-8AI User Manual · MI00259-3-EN. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.