Sensor (remote I/O module) · Modbus register map

Moxa ioLogik R1214 RS-485 remote I/O Modbus register map

Updated 17 November 2026

Short answer

The ioLogik R1214 is a Moxa RS-485 Modbus RTU remote I/O module with 6 digital inputs and 6 relay outputs with pulse mode and relay counters. It supports a repeater or dual RS-485 mode and a Modbus host-connection watchdog with safe-mode output states. This map covers the shared system registers (model, watchdog, serial settings) and the DI counters and relay outputs.

This page lists 162 Modbus registers for the Moxa ioLogik R1214 RS-485 remote I/O — 127 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Moxa’s own free documentation (linked below) and checked against it.

Manufacturer
Moxa
Model
ioLogik R1214 RS-485 remote I/O
Equipment type
Sensor (remote I/O module)
Registers
162 (127 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
ioLogik R1214, R1214, R1214-T
Source document
ioLogik R1200 Series User's Manual · Edition 3.4 · rev. 2021-04 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Moxa ioLogik R1214 RS-485 remote I/O

Integration in brief

Poll the I/O block with the function code shown for each register (01/02 for bits, 03/04 for words). Enable the Modbus watchdog (0x7564, timeout 0x7565) so outputs and counters fall back to their safe-mode settings if the master stops polling.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 30000SYS_modelIDUINT16Model ID checkRead
HR 30052SYS_modbusWatchdogFuntionUINT16Enable communication watchdogRead/write
HR 30053SYS_modbusWatchdogTimeoutUINT16Watchdog timeoutRead/write
DI 0DI-00_statusBITFirst digital inputRead
IR 32DI-00_counterValueUINT32 ABCDFirst counter valueRead
CO 320RLY-00_statusBITFirst output on/offRead/write

Enable Modbus control & writes

Set the device ID (1-99) on the two rotary dials. Put the Initial/Run switch on Initial to configure the unit at 9600 baud, no parity, 8 data bits, 1 stop bit (with ioSearch or the SYS_port* registers), then switch back to Run.

Communication loss & watchdog

SYS_modbusWatchdogFuntion (0x7564) enables the host-connection watchdog, SYS_modbusWatchdogTimeout (0x7565) sets the timeout in seconds (factory default 10 s), SYS_modbusWatchdogStatus (0x7566) shows a timeout. It is disabled by default; safe-status settings only act when it is enabled.

Byte order & addressing

Network setup

Watch out for

Moxa ioLogik R1214 RS-485 remote I/O Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

162 of 162 shown
Moxa ioLogik R1214 RS-485 remote I/O Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 0x0000DI-00_counterStatusBITRead/write0 = STOP; 1 = START
CO1doc 0x0001DI-01_counterStatusBITRead/write0 = STOP; 1 = START
CO2doc 0x0002DI-02_counterStatusBITRead/write0 = STOP; 1 = START
CO3doc 0x0003DI-03_counterStatusBITRead/write0 = STOP; 1 = START
CO4doc 0x0004DI-04_counterStatusBITRead/write0 = STOP; 1 = START
CO5doc 0x0005DI-05_counterStatusBITRead/write0 = STOP; 1 = START
CO32doc 0x0020DI-00_counterResetBITRead/write1 = reset to initial value
CO33doc 0x0021DI-01_counterResetBITRead/write1 = reset to initial value
CO34doc 0x0022DI-02_counterResetBITRead/write1 = reset to initial value
CO35doc 0x0023DI-03_counterResetBITRead/write1 = reset to initial value
CO36doc 0x0024DI-04_counterResetBITRead/write1 = reset to initial value
CO37doc 0x0025DI-05_counterResetBITRead/write1 = reset to initial value
CO64doc 0x0040DI-00_counterOverflowFlagBITRead/write1 = clear overflow flag
CO65doc 0x0041DI-01_counterOverflowFlagBITRead/write1 = clear overflow flag
CO66doc 0x0042DI-02_counterOverflowFlagBITRead/write1 = clear overflow flag
CO67doc 0x0043DI-03_counterOverflowFlagBITRead/write1 = clear overflow flag
CO68doc 0x0044DI-04_counterOverflowFlagBITRead/write1 = clear overflow flag
CO69doc 0x0045DI-05_counterOverflowFlagBITRead/write1 = clear overflow flag
CO96doc 0x0060DI-00_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO97doc 0x0061DI-01_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO98doc 0x0062DI-02_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO99doc 0x0063DI-03_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO100doc 0x0064DI-04_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO101doc 0x0065DI-05_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO128doc 0x0080DI-00_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO129doc 0x0081DI-01_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO130doc 0x0082DI-02_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO131doc 0x0083DI-03_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO132doc 0x0084DI-04_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO133doc 0x0085DI-05_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO160doc 0x00A0DI-00_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO161doc 0x00A1DI-01_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO162doc 0x00A2DI-02_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO163doc 0x00A3DI-03_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO164doc 0x00A4DI-04_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO165doc 0x00A5DI-05_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO320doc 0x0140RLY-00_statusBITRead/write0 = OFF; 1 = ON
CO321doc 0x0141RLY-01_statusBITRead/write0 = OFF; 1 = ON
CO322doc 0x0142RLY-02_statusBITRead/write0 = OFF; 1 = ON
CO323doc 0x0143RLY-03_statusBITRead/write0 = OFF; 1 = ON
CO324doc 0x0144RLY-04_statusBITRead/write0 = OFF; 1 = ON
CO325doc 0x0145RLY-05_statusBITRead/write0 = OFF; 1 = ON
CO352doc 0x0160RLY-00_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO353doc 0x0161RLY-01_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO354doc 0x0162RLY-02_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO355doc 0x0163RLY-03_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO356doc 0x0164RLY-04_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO357doc 0x0165RLY-05_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO384doc 0x0180RLY-00_pulseStatusBITRead/write0 = STOP; 1 = START
CO385doc 0x0181RLY-01_pulseStatusBITRead/write0 = STOP; 1 = START
CO386doc 0x0182RLY-02_pulseStatusBITRead/write0 = STOP; 1 = START
CO387doc 0x0183RLY-03_pulseStatusBITRead/write0 = STOP; 1 = START
CO388doc 0x0184RLY-04_pulseStatusBITRead/write0 = STOP; 1 = START
CO389doc 0x0185RLY-05_pulseStatusBITRead/write0 = STOP; 1 = START
CO416doc 0x01A0RLY-00_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO417doc 0x01A1RLY-01_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO418doc 0x01A2RLY-02_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO419doc 0x01A3RLY-03_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO420doc 0x01A4RLY-04_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO421doc 0x01A5RLY-05_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO448doc 0x01C0RLY-00_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO449doc 0x01C1RLY-01_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO450doc 0x01C2RLY-02_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO451doc 0x01C3RLY-03_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO452doc 0x01C4RLY-04_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO453doc 0x01C5RLY-05_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO479doc 0x01DFRLY-00_pulseResetBITRead/write1 = reset pulse count
CO480doc 0x01E0RLY-01_pulseResetBITRead/write1 = reset pulse count
CO481doc 0x01E1RLY-02_pulseResetBITRead/write1 = reset pulse count
CO482doc 0x01E2RLY-03_pulseResetBITRead/write1 = reset pulse count
CO483doc 0x01E3RLY-04_pulseResetBITRead/write1 = reset pulse count
CO484doc 0x01E4RLY-05_pulseResetBITRead/write1 = reset pulse count
DI0doc 0x0000DI-00_statusBITRead0 = OFF; 1 = ON
DI1doc 0x0001DI-01_statusBITRead0 = OFF; 1 = ON
DI2doc 0x0002DI-02_statusBITRead0 = OFF; 1 = ON
DI3doc 0x0003DI-03_statusBITRead0 = OFF; 1 = ON
DI4doc 0x0004DI-04_statusBITRead0 = OFF; 1 = ON
DI5doc 0x0005DI-05_statusBITRead0 = OFF; 1 = ON
IR0doc 0x0000DI-00_statusUINT16Read0 = OFF; 1 = ON
IR1doc 0x0001DI-01_statusUINT16Read0 = OFF; 1 = ON
IR2doc 0x0002DI-02_statusUINT16Read0 = OFF; 1 = ON
IR3doc 0x0003DI-03_statusUINT16Read0 = OFF; 1 = ON
IR4doc 0x0004DI-04_statusUINT16Read0 = OFF; 1 = ON
IR5doc 0x0005DI-05_statusUINT16Read0 = OFF; 1 = ON
IR32doc 0x0020DI-00_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR34doc 0x0022DI-01_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR36doc 0x0024DI-02_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR38doc 0x0026DI-03_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR40doc 0x0028DI-04_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR42doc 0x002ADI-05_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR320doc 0x0140RLY-00_totalCountHigh word at this address, low word next.UINT32ABCDRead
IR322doc 0x0142RLY-01_totalCountHigh word at this address, low word next.UINT32ABCDRead
IR324doc 0x0144RLY-02_totalCountHigh word at this address, low word next.UINT32ABCDRead
IR326doc 0x0146RLY-03_totalCountHigh word at this address, low word next.UINT32ABCDRead
IR328doc 0x0148RLY-04_totalCountHigh word at this address, low word next.UINT32ABCDRead
IR330doc 0x014ARLY-05_totalCountHigh word at this address, low word next.UINT32ABCDRead
IR384doc 0x0180RLY-00_currentCountHigh word at this address, low word next.UINT32ABCDRead
IR386doc 0x0182RLY-01_currentCountHigh word at this address, low word next.UINT32ABCDRead
IR388doc 0x0184RLY-02_currentCountHigh word at this address, low word next.UINT32ABCDRead
IR390doc 0x0186RLY-03_currentCountHigh word at this address, low word next.UINT32ABCDRead
IR392doc 0x0188RLY-04_currentCountHigh word at this address, low word next.UINT32ABCDRead
IR394doc 0x018ARLY-05_currentCountHigh word at this address, low word next.UINT32ABCDRead
IR30000doc 0x7530SYS_modelIDUINT16Read
IR30025doc 0x7549SYS_vendorIDUINT16Read
IR30026doc 0x754ASYS_unitIDUINT16Read
IR30037doc 0x7555SYS_productNameSTRING[20]Read
IR30058doc 0x756ASYS_rs485PortModeUINT16Read0 = initial-repeater; 1 = initial-dual RS- 485; 2 = run-repeater; 3 = run-dual RS-485
HR0doc 0x0000DI-00_modeUINT16Read/write0 = DI; 1 = Counter
HR1doc 0x0001DI-01_modeUINT16Read/write0 = DI; 1 = Counter
HR2doc 0x0002DI-02_modeUINT16Read/write0 = DI; 1 = Counter
HR3doc 0x0003DI-03_modeUINT16Read/write0 = DI; 1 = Counter
HR4doc 0x0004DI-04_modeUINT16Read/write0 = DI; 1 = Counter
HR5doc 0x0005DI-05_modeUINT16Read/write0 = DI; 1 = Counter
HR32doc 0x0020DI-00_filterUINT16× 100µsRead/write
HR33doc 0x0021DI-01_filterUINT16× 100µsRead/write
HR34doc 0x0022DI-02_filterUINT16× 100µsRead/write
HR35doc 0x0023DI-03_filterUINT16× 100µsRead/write
HR36doc 0x0024DI-04_filterUINT16× 100µsRead/write
HR37doc 0x0025DI-05_filterUINT16× 100µsRead/write
HR64doc 0x0040DI-00_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR65doc 0x0041DI-01_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR66doc 0x0042DI-02_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR67doc 0x0043DI-03_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR68doc 0x0044DI-04_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR69doc 0x0045DI-05_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR320doc 0x0140RLY-00_statusUINT16Read/write0 = OFF; 1 = ON
HR321doc 0x0141RLY-01_statusUINT16Read/write0 = OFF; 1 = ON
HR322doc 0x0142RLY-02_statusUINT16Read/write0 = OFF; 1 = ON
HR323doc 0x0143RLY-03_statusUINT16Read/write0 = OFF; 1 = ON
HR324doc 0x0144RLY-04_statusUINT16Read/write0 = OFF; 1 = ON
HR325doc 0x0145RLY-05_statusUINT16Read/write0 = OFF; 1 = ON
HR352doc 0x0160RLY-00_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR354doc 0x0162RLY-01_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR356doc 0x0164RLY-02_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR358doc 0x0166RLY-03_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR360doc 0x0168RLY-04_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR362doc 0x016ARLY-05_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR480doc 0x01E0RLY-00_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR481doc 0x01E1RLY-01_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR482doc 0x01E2RLY-02_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR483doc 0x01E3RLY-03_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR484doc 0x01E4RLY-04_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR485doc 0x01E5RLY-05_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR486doc 0x01E6RLY-06_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR487doc 0x01E7RLY-07_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR544doc 0x0220RLY-00_PowerOnDelayUINT16sRead/write
HR545doc 0x0221RLY-01_PowerOnDelayUINT16sRead/write
HR546doc 0x0222RLY-02_PowerOnDelayUINT16sRead/write
HR547doc 0x0223RLY-03_PowerOnDelayUINT16sRead/write
HR548doc 0x0224RLY-04_PowerOnDelayUINT16sRead/write
HR549doc 0x0225RLY-05_PowerOnDelayUINT16sRead/write
HR30052doc 0x7564SYS_modbusWatchdogFuntionUINT16Read/write0 = Disable; 1 = Enable
HR30053doc 0x7565SYS_modbusWatchdogTimeoutUINT16sRead/write
HR30054doc 0x7566SYS_modbusWatchdogStatusUINT16Read/write0 = Normal; 1 = Timeout
HR30056doc 0x7568SYS_restartDeviceWrite 404 to trigger.UINT16Read/write
HR30057doc 0x7569SYS_loadFactoryDefaultWrite 404 to trigger.UINT16Read/write
HR30060doc 0x756CSYS_port0BaudrateUINT16Read/write1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 19200; 6 = 38400; 7 = 57600; 8 = 115200; 9 = 921600
HR30061doc 0x756DSYS_port1BaudrateUINT16Read/write1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 19200; 6 = 38400; 7 = 57600; 8 = 115200; 9 = 921600
HR30064doc 0x7570SYS_port0StopBitUINT16Read/write0 = 1; 1 = 2
HR30065doc 0x7571SYS_port1StopBitUINT16Read/write0 = 1; 1 = 2
HR30066doc 0x7572SYS_port0ParityUINT16Read/write0 = None; 1 = Even; 2 = Odd
HR30067doc 0x7573SYS_port1ParityUINT16Read/write0 = None; 1 = Even; 2 = Odd

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Moxa ioLogik R1214 RS-485 remote I/O

What Modbus registers does the Moxa ioLogik R1214 RS-485 remote I/O have?

This map lists 162 registers: 72 coils, 6 discrete inputs, 29 input registers, 55 holding registers. 127 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Moxa ioLogik R1214 RS-485 remote I/O Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints the hex protocol address and a 1-based reference number (0x0000 = 00001/10001/30001/40001). The hex address is sent on the wire; the table (coil, discrete input, input or holding) is set by the function code column.

What byte order does the Moxa ioLogik R1214 RS-485 remote I/O use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Moxa ioLogik R1214 RS-485 remote I/O?

Start with IR 30000 SYS_modelID (Model ID check); HR 30052 SYS_modbusWatchdogFuntion (Enable communication watchdog); HR 30053 SYS_modbusWatchdogTimeout (Watchdog timeout); DI 0 DI-00_status (First digital input); IR 32 DI-00_counterValue (First counter value); CO 320 RLY-00_status (First output on/off).

How do I enable Modbus control of the Moxa ioLogik R1214 RS-485 remote I/O?

Set the device ID (1-99) on the two rotary dials. Put the Initial/Run switch on Initial to configure the unit at 9600 baud, no parity, 8 data bits, 1 stop bit (with ioSearch or the SYS_port* registers), then switch back to Run.

What happens when the Moxa ioLogik R1214 RS-485 remote I/O loses Modbus communication?

SYS_modbusWatchdogFuntion (0x7564) enables the host-connection watchdog, SYS_modbusWatchdogTimeout (0x7565) sets the timeout in seconds (factory default 10 s), SYS_modbusWatchdogStatus (0x7566) shows a timeout. It is disabled by default; safe-status settings only act when it is enabled.

Where is the official Moxa ioLogik R1214 RS-485 remote I/O Modbus documentation?

The source is ioLogik R1200 Series User's Manual (Edition 3.4), revision 2021-04. Moxa doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn11.bigcommerce.com/s-hltjsp5jm3/content/pdfs/moxa-iologik-r1200-series-manual.pdf. It may be an older revision, so check it against the live unit.

More Moxa Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: ioLogik R1200 Series User's Manual · Edition 3.4 · rev. 2021-04 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.