Sensor (remote I/O module) · Modbus register map
Moxa ioLogik R1214 RS-485 remote I/O Modbus register map
Updated 17 November 2026
The ioLogik R1214 is a Moxa RS-485 Modbus RTU remote I/O module with 6 digital inputs and 6 relay outputs with pulse mode and relay counters. It supports a repeater or dual RS-485 mode and a Modbus host-connection watchdog with safe-mode output states. This map covers the shared system registers (model, watchdog, serial settings) and the DI counters and relay outputs.
This page lists 162 Modbus registers for the Moxa ioLogik R1214 RS-485 remote I/O — 127 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Moxa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Moxa
- Model
- ioLogik R1214 RS-485 remote I/O
- Equipment type
- Sensor (remote I/O module)
- Registers
- 162 (127 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- ioLogik R1214, R1214, R1214-T
Integration notes: Moxa ioLogik R1214 RS-485 remote I/O
Poll the I/O block with the function code shown for each register (01/02 for bits, 03/04 for words). Enable the Modbus watchdog (0x7564, timeout 0x7565) so outputs and counters fall back to their safe-mode settings if the master stops polling.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 30000 | SYS_modelID | UINT16 | Model ID check | Read |
| HR 30052 | SYS_modbusWatchdogFuntion | UINT16 | Enable communication watchdog | Read/write |
| HR 30053 | SYS_modbusWatchdogTimeout | UINT16 | Watchdog timeout | Read/write |
| DI 0 | DI-00_status | BIT | First digital input | Read |
| IR 32 | DI-00_counterValue | UINT32 ABCD | First counter value | Read |
| CO 320 | RLY-00_status | BIT | First output on/off | Read/write |
Enable Modbus control & writes
Set the device ID (1-99) on the two rotary dials. Put the Initial/Run switch on Initial to configure the unit at 9600 baud, no parity, 8 data bits, 1 stop bit (with ioSearch or the SYS_port* registers), then switch back to Run.
Communication loss & watchdog
SYS_modbusWatchdogFuntion (0x7564) enables the host-connection watchdog, SYS_modbusWatchdogTimeout (0x7565) sets the timeout in seconds (factory default 10 s), SYS_modbusWatchdogStatus (0x7566) shows a timeout. It is disabled by default; safe-status settings only act when it is enabled.
Byte order & addressing
- System registers sit at 0x7530 and up (six-digit references 330001/430002).
- Write 404 to SYS_restartDevice or SYS_loadFactoryDefault to trigger them.
Network setup
- Device ID 1-99 on the rotary dials (x1 and x10).
- The Dual/Rep switch selects two separate RS-485 ports or repeater mode; SYS_rs485PortMode reports which is active.
- Baud rate codes: 1=1200 ... 4=9600, 5=19200 ... 9=921600.
Watch out for
- Factory defaults (reset button held 5 s, ioSearch, or SYS_loadFactoryDefault) return the serial settings to 9600 n 8 1 and disable the watchdog.
Moxa ioLogik R1214 RS-485 remote I/O Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0x0000 | DI-00_counterStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 1doc 0x0001 | DI-01_counterStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 2doc 0x0002 | DI-02_counterStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 3doc 0x0003 | DI-03_counterStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 4doc 0x0004 | DI-04_counterStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 5doc 0x0005 | DI-05_counterStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 32doc 0x0020 | DI-00_counterReset | BIT | Read/write | 1 = reset to initial value | ||||
| CO | 33doc 0x0021 | DI-01_counterReset | BIT | Read/write | 1 = reset to initial value | ||||
| CO | 34doc 0x0022 | DI-02_counterReset | BIT | Read/write | 1 = reset to initial value | ||||
| CO | 35doc 0x0023 | DI-03_counterReset | BIT | Read/write | 1 = reset to initial value | ||||
| CO | 36doc 0x0024 | DI-04_counterReset | BIT | Read/write | 1 = reset to initial value | ||||
| CO | 37doc 0x0025 | DI-05_counterReset | BIT | Read/write | 1 = reset to initial value | ||||
| CO | 64doc 0x0040 | DI-00_counterOverflowFlag | BIT | Read/write | 1 = clear overflow flag | ||||
| CO | 65doc 0x0041 | DI-01_counterOverflowFlag | BIT | Read/write | 1 = clear overflow flag | ||||
| CO | 66doc 0x0042 | DI-02_counterOverflowFlag | BIT | Read/write | 1 = clear overflow flag | ||||
| CO | 67doc 0x0043 | DI-03_counterOverflowFlag | BIT | Read/write | 1 = clear overflow flag | ||||
| CO | 68doc 0x0044 | DI-04_counterOverflowFlag | BIT | Read/write | 1 = clear overflow flag | ||||
| CO | 69doc 0x0045 | DI-05_counterOverflowFlag | BIT | Read/write | 1 = clear overflow flag | ||||
| CO | 96doc 0x0060 | DI-00_counterPowerOnStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 97doc 0x0061 | DI-01_counterPowerOnStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 98doc 0x0062 | DI-02_counterPowerOnStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 99doc 0x0063 | DI-03_counterPowerOnStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 100doc 0x0064 | DI-04_counterPowerOnStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 101doc 0x0065 | DI-05_counterPowerOnStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 128doc 0x0080 | DI-00_counterSafeModeStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 129doc 0x0081 | DI-01_counterSafeModeStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 130doc 0x0082 | DI-02_counterSafeModeStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 131doc 0x0083 | DI-03_counterSafeModeStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 132doc 0x0084 | DI-04_counterSafeModeStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 133doc 0x0085 | DI-05_counterSafeModeStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 160doc 0x00A0 | DI-00_counterPowerOffStorage | BIT | Read/write | 0 = Disable; 1 = Enable | ||||
| CO | 161doc 0x00A1 | DI-01_counterPowerOffStorage | BIT | Read/write | 0 = Disable; 1 = Enable | ||||
| CO | 162doc 0x00A2 | DI-02_counterPowerOffStorage | BIT | Read/write | 0 = Disable; 1 = Enable | ||||
| CO | 163doc 0x00A3 | DI-03_counterPowerOffStorage | BIT | Read/write | 0 = Disable; 1 = Enable | ||||
| CO | 164doc 0x00A4 | DI-04_counterPowerOffStorage | BIT | Read/write | 0 = Disable; 1 = Enable | ||||
| CO | 165doc 0x00A5 | DI-05_counterPowerOffStorage | BIT | Read/write | 0 = Disable; 1 = Enable | ||||
| CO | 320doc 0x0140 | RLY-00_status | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 321doc 0x0141 | RLY-01_status | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 322doc 0x0142 | RLY-02_status | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 323doc 0x0143 | RLY-03_status | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 324doc 0x0144 | RLY-04_status | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 325doc 0x0145 | RLY-05_status | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 352doc 0x0160 | RLY-00_powerOnStatus | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 353doc 0x0161 | RLY-01_powerOnStatus | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 354doc 0x0162 | RLY-02_powerOnStatus | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 355doc 0x0163 | RLY-03_powerOnStatus | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 356doc 0x0164 | RLY-04_powerOnStatus | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 357doc 0x0165 | RLY-05_powerOnStatus | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 384doc 0x0180 | RLY-00_pulseStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 385doc 0x0181 | RLY-01_pulseStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 386doc 0x0182 | RLY-02_pulseStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 387doc 0x0183 | RLY-03_pulseStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 388doc 0x0184 | RLY-04_pulseStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 389doc 0x0185 | RLY-05_pulseStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 416doc 0x01A0 | RLY-00_pulsePowerOnStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 417doc 0x01A1 | RLY-01_pulsePowerOnStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 418doc 0x01A2 | RLY-02_pulsePowerOnStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 419doc 0x01A3 | RLY-03_pulsePowerOnStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 420doc 0x01A4 | RLY-04_pulsePowerOnStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 421doc 0x01A5 | RLY-05_pulsePowerOnStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 448doc 0x01C0 | RLY-00_pulseSafeModeStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 449doc 0x01C1 | RLY-01_pulseSafeModeStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 450doc 0x01C2 | RLY-02_pulseSafeModeStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 451doc 0x01C3 | RLY-03_pulseSafeModeStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 452doc 0x01C4 | RLY-04_pulseSafeModeStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 453doc 0x01C5 | RLY-05_pulseSafeModeStatus | BIT | Read/write | 0 = STOP; 1 = START | ||||
| CO | 479doc 0x01DF | RLY-00_pulseReset | BIT | Read/write | 1 = reset pulse count | ||||
| CO | 480doc 0x01E0 | RLY-01_pulseReset | BIT | Read/write | 1 = reset pulse count | ||||
| CO | 481doc 0x01E1 | RLY-02_pulseReset | BIT | Read/write | 1 = reset pulse count | ||||
| CO | 482doc 0x01E2 | RLY-03_pulseReset | BIT | Read/write | 1 = reset pulse count | ||||
| CO | 483doc 0x01E3 | RLY-04_pulseReset | BIT | Read/write | 1 = reset pulse count | ||||
| CO | 484doc 0x01E4 | RLY-05_pulseReset | BIT | Read/write | 1 = reset pulse count | ||||
| DI | 0doc 0x0000 | DI-00_status | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 1doc 0x0001 | DI-01_status | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 2doc 0x0002 | DI-02_status | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 3doc 0x0003 | DI-03_status | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 4doc 0x0004 | DI-04_status | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 5doc 0x0005 | DI-05_status | BIT | Read | 0 = OFF; 1 = ON | ||||
| IR | 0doc 0x0000 | DI-00_status | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| IR | 1doc 0x0001 | DI-01_status | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| IR | 2doc 0x0002 | DI-02_status | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| IR | 3doc 0x0003 | DI-03_status | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| IR | 4doc 0x0004 | DI-04_status | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| IR | 5doc 0x0005 | DI-05_status | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| IR | 32doc 0x0020 | DI-00_counterValue | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 34doc 0x0022 | DI-01_counterValue | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 36doc 0x0024 | DI-02_counterValue | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 38doc 0x0026 | DI-03_counterValue | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 40doc 0x0028 | DI-04_counterValue | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 42doc 0x002A | DI-05_counterValue | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 320doc 0x0140 | RLY-00_totalCount | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 322doc 0x0142 | RLY-01_totalCount | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 324doc 0x0144 | RLY-02_totalCount | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 326doc 0x0146 | RLY-03_totalCount | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 328doc 0x0148 | RLY-04_totalCount | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 330doc 0x014A | RLY-05_totalCount | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 384doc 0x0180 | RLY-00_currentCount | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 386doc 0x0182 | RLY-01_currentCount | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 388doc 0x0184 | RLY-02_currentCount | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 390doc 0x0186 | RLY-03_currentCount | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 392doc 0x0188 | RLY-04_currentCount | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 394doc 0x018A | RLY-05_currentCount | High word at this address, low word next. | UINT32 | ABCD | Read | |||
| IR | 30000doc 0x7530 | SYS_modelID | UINT16 | Read | |||||
| IR | 30025doc 0x7549 | SYS_vendorID | UINT16 | Read | |||||
| IR | 30026doc 0x754A | SYS_unitID | UINT16 | Read | |||||
| IR | 30037doc 0x7555 | SYS_productName | STRING[20] | Read | |||||
| IR | 30058doc 0x756A | SYS_rs485PortMode | UINT16 | Read | 0 = initial-repeater; 1 = initial-dual RS- 485; 2 = run-repeater; 3 = run-dual RS-485 | ||||
| HR | 0doc 0x0000 | DI-00_mode | UINT16 | Read/write | 0 = DI; 1 = Counter | ||||
| HR | 1doc 0x0001 | DI-01_mode | UINT16 | Read/write | 0 = DI; 1 = Counter | ||||
| HR | 2doc 0x0002 | DI-02_mode | UINT16 | Read/write | 0 = DI; 1 = Counter | ||||
| HR | 3doc 0x0003 | DI-03_mode | UINT16 | Read/write | 0 = DI; 1 = Counter | ||||
| HR | 4doc 0x0004 | DI-04_mode | UINT16 | Read/write | 0 = DI; 1 = Counter | ||||
| HR | 5doc 0x0005 | DI-05_mode | UINT16 | Read/write | 0 = DI; 1 = Counter | ||||
| HR | 32doc 0x0020 | DI-00_filter | UINT16 | × 100 | µs | Read/write | |||
| HR | 33doc 0x0021 | DI-01_filter | UINT16 | × 100 | µs | Read/write | |||
| HR | 34doc 0x0022 | DI-02_filter | UINT16 | × 100 | µs | Read/write | |||
| HR | 35doc 0x0023 | DI-03_filter | UINT16 | × 100 | µs | Read/write | |||
| HR | 36doc 0x0024 | DI-04_filter | UINT16 | × 100 | µs | Read/write | |||
| HR | 37doc 0x0025 | DI-05_filter | UINT16 | × 100 | µs | Read/write | |||
| HR | 64doc 0x0040 | DI-00_counterEvent | UINT16 | Read/write | 0 = Rising Edge; 1 = Falling Edge; 2 = Both | ||||
| HR | 65doc 0x0041 | DI-01_counterEvent | UINT16 | Read/write | 0 = Rising Edge; 1 = Falling Edge; 2 = Both | ||||
| HR | 66doc 0x0042 | DI-02_counterEvent | UINT16 | Read/write | 0 = Rising Edge; 1 = Falling Edge; 2 = Both | ||||
| HR | 67doc 0x0043 | DI-03_counterEvent | UINT16 | Read/write | 0 = Rising Edge; 1 = Falling Edge; 2 = Both | ||||
| HR | 68doc 0x0044 | DI-04_counterEvent | UINT16 | Read/write | 0 = Rising Edge; 1 = Falling Edge; 2 = Both | ||||
| HR | 69doc 0x0045 | DI-05_counterEvent | UINT16 | Read/write | 0 = Rising Edge; 1 = Falling Edge; 2 = Both | ||||
| HR | 320doc 0x0140 | RLY-00_status | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 321doc 0x0141 | RLY-01_status | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 322doc 0x0142 | RLY-02_status | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 323doc 0x0143 | RLY-03_status | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 324doc 0x0144 | RLY-04_status | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 325doc 0x0145 | RLY-05_status | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 352doc 0x0160 | RLY-00_pulseCount | High word at this address, low word next. | UINT32 | ABCD | Read/write | |||
| HR | 354doc 0x0162 | RLY-01_pulseCount | High word at this address, low word next. | UINT32 | ABCD | Read/write | |||
| HR | 356doc 0x0164 | RLY-02_pulseCount | High word at this address, low word next. | UINT32 | ABCD | Read/write | |||
| HR | 358doc 0x0166 | RLY-03_pulseCount | High word at this address, low word next. | UINT32 | ABCD | Read/write | |||
| HR | 360doc 0x0168 | RLY-04_pulseCount | High word at this address, low word next. | UINT32 | ABCD | Read/write | |||
| HR | 362doc 0x016A | RLY-05_pulseCount | High word at this address, low word next. | UINT32 | ABCD | Read/write | |||
| HR | 480doc 0x01E0 | RLY-00_safeModeStatus | UINT16 | Read/write | 0 = OFF; 1 = ON; 2 = Hold Last | ||||
| HR | 481doc 0x01E1 | RLY-01_safeModeStatus | UINT16 | Read/write | 0 = OFF; 1 = ON; 2 = Hold Last | ||||
| HR | 482doc 0x01E2 | RLY-02_safeModeStatus | UINT16 | Read/write | 0 = OFF; 1 = ON; 2 = Hold Last | ||||
| HR | 483doc 0x01E3 | RLY-03_safeModeStatus | UINT16 | Read/write | 0 = OFF; 1 = ON; 2 = Hold Last | ||||
| HR | 484doc 0x01E4 | RLY-04_safeModeStatus | UINT16 | Read/write | 0 = OFF; 1 = ON; 2 = Hold Last | ||||
| HR | 485doc 0x01E5 | RLY-05_safeModeStatus | UINT16 | Read/write | 0 = OFF; 1 = ON; 2 = Hold Last | ||||
| HR | 486doc 0x01E6 | RLY-06_safeModeStatus | UINT16 | Read/write | 0 = OFF; 1 = ON; 2 = Hold Last | ||||
| HR | 487doc 0x01E7 | RLY-07_safeModeStatus | UINT16 | Read/write | 0 = OFF; 1 = ON; 2 = Hold Last | ||||
| HR | 544doc 0x0220 | RLY-00_PowerOnDelay | UINT16 | s | Read/write | ||||
| HR | 545doc 0x0221 | RLY-01_PowerOnDelay | UINT16 | s | Read/write | ||||
| HR | 546doc 0x0222 | RLY-02_PowerOnDelay | UINT16 | s | Read/write | ||||
| HR | 547doc 0x0223 | RLY-03_PowerOnDelay | UINT16 | s | Read/write | ||||
| HR | 548doc 0x0224 | RLY-04_PowerOnDelay | UINT16 | s | Read/write | ||||
| HR | 549doc 0x0225 | RLY-05_PowerOnDelay | UINT16 | s | Read/write | ||||
| HR | 30052doc 0x7564 | SYS_modbusWatchdogFuntion | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 30053doc 0x7565 | SYS_modbusWatchdogTimeout | UINT16 | s | Read/write | ||||
| HR | 30054doc 0x7566 | SYS_modbusWatchdogStatus | UINT16 | Read/write | 0 = Normal; 1 = Timeout | ||||
| HR | 30056doc 0x7568 | SYS_restartDevice | Write 404 to trigger. | UINT16 | Read/write | ||||
| HR | 30057doc 0x7569 | SYS_loadFactoryDefault | Write 404 to trigger. | UINT16 | Read/write | ||||
| HR | 30060doc 0x756C | SYS_port0Baudrate | UINT16 | Read/write | 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 19200; 6 = 38400; 7 = 57600; 8 = 115200; 9 = 921600 | ||||
| HR | 30061doc 0x756D | SYS_port1Baudrate | UINT16 | Read/write | 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 19200; 6 = 38400; 7 = 57600; 8 = 115200; 9 = 921600 | ||||
| HR | 30064doc 0x7570 | SYS_port0StopBit | UINT16 | Read/write | 0 = 1; 1 = 2 | ||||
| HR | 30065doc 0x7571 | SYS_port1StopBit | UINT16 | Read/write | 0 = 1; 1 = 2 | ||||
| HR | 30066doc 0x7572 | SYS_port0Parity | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | ||||
| HR | 30067doc 0x7573 | SYS_port1Parity | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd |
Notes on this map
- Moxa does not appear to offer this manual on a public URL found in this pass; the link is an unaltered copy of the Moxa user's manual on a reseller's file host.
- Each table row gives the hex wire address, the 1-based decimal reference (e.g. 0x0000 = 40001; system registers use six digits, 0x7530 = 330001), access, size and function code.
- 32-bit counters are listed as ...High and ...Low word registers with the high word at the lower address; they are combined here as UINT32 high word first (ABCD).
- Left out: system strings and multi-word values whose format is not described (firmware version and release date, serial number, server name/location, password, vendor name).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Moxa ioLogik R1214 RS-485 remote I/O
What Modbus registers does the Moxa ioLogik R1214 RS-485 remote I/O have?
This map lists 162 registers: 72 coils, 6 discrete inputs, 29 input registers, 55 holding registers. 127 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Moxa ioLogik R1214 RS-485 remote I/O Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints the hex protocol address and a 1-based reference number (0x0000 = 00001/10001/30001/40001). The hex address is sent on the wire; the table (coil, discrete input, input or holding) is set by the function code column.
What byte order does the Moxa ioLogik R1214 RS-485 remote I/O use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Moxa ioLogik R1214 RS-485 remote I/O?
Start with IR 30000 SYS_modelID (Model ID check); HR 30052 SYS_modbusWatchdogFuntion (Enable communication watchdog); HR 30053 SYS_modbusWatchdogTimeout (Watchdog timeout); DI 0 DI-00_status (First digital input); IR 32 DI-00_counterValue (First counter value); CO 320 RLY-00_status (First output on/off).
How do I enable Modbus control of the Moxa ioLogik R1214 RS-485 remote I/O?
Set the device ID (1-99) on the two rotary dials. Put the Initial/Run switch on Initial to configure the unit at 9600 baud, no parity, 8 data bits, 1 stop bit (with ioSearch or the SYS_port* registers), then switch back to Run.
What happens when the Moxa ioLogik R1214 RS-485 remote I/O loses Modbus communication?
SYS_modbusWatchdogFuntion (0x7564) enables the host-connection watchdog, SYS_modbusWatchdogTimeout (0x7565) sets the timeout in seconds (factory default 10 s), SYS_modbusWatchdogStatus (0x7566) shows a timeout. It is disabled by default; safe-status settings only act when it is enabled.
Where is the official Moxa ioLogik R1214 RS-485 remote I/O Modbus documentation?
The source is ioLogik R1200 Series User's Manual (Edition 3.4), revision 2021-04. Moxa doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn11.bigcommerce.com/s-hltjsp5jm3/content/pdfs/moxa-iologik-r1200-series-manual.pdf. It may be an older revision, so check it against the live unit.
More Moxa Modbus register maps
- Sensor (remote I/O module)
Moxa ioLogik R1210 RS-485 remote I/O
ioLogik R1210 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1210, R1210, R1210-T - Sensor (remote I/O module)
Moxa ioLogik R1212 RS-485 remote I/O
ioLogik R1212 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1212, R1212, R1212-T - Sensor (remote I/O module)
Moxa ioLogik R1240 RS-485 remote I/O
ioLogik R1240 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1240, R1240, R1240-T - Sensor (remote I/O module)
Moxa ioLogik R1241 RS-485 remote I/O
ioLogik R1241 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1241, R1241, R1241-T
Other remote i/o modules register maps
- Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2 - Sensor (Ethernet I/O module)
Teracom TCW241 Ethernet I/O module
TCW241 per the Teracom TCW241 user manual Revision R4.30, firmware v2.012 or later.
Also known as: TCW241 - Sensor (Ethernet digital I/O module)
Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP)
BusWorks XT1121-000 per user's manual 8500950P (revision P, 18 Nov 2022).
Also known as: XT1121-000, XT1121, BusWorks XT1121 - Sensor (PWM output and counter input module)
ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)
ICP DAS M-7088 eight-channel PWM output module with eight digital inputs and counters, Modbus RTU firmware.
Also known as: M-7088, M7088 - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC
All remote i/o modules Modbus register maps →
Source: ioLogik R1200 Series User's Manual · Edition 3.4 · rev. 2021-04 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.