  4. BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP)

Sensor (Ethernet digital I/O module) · Modbus register map

Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP) Modbus register map

Updated 19 November 2026

Short answer

The Acromag BusWorks XT1121-000 is a Modbus TCP Ethernet module with 16 active-high inputs paired with 16 high-side (sourcing) outputs. Its Modbus map is I/O only: four input-state words, a heartbeat counter and four output-command words; all setup is done over USB.

This page lists 9 Modbus registers for the Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Acromag’s own free documentation (linked below) and checked against it.

Manufacturer
Acromag
Model
BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP)
Equipment type
Sensor (Ethernet digital I/O module)
Registers
9 (4 writable)
Transport
Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
XT1121-000, XT1121, BusWorks XT1121
Source document
BusWorks XT Series Model XT1121-000 16-Channel Sourcing Digital I/O User's Manual · 8500950P · rev. 2022-11-18
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP)

Integration in brief

Read input registers 0-3 for input states and write holding registers 0-3 to drive the outputs, four channels per word. Watch input register 4 to confirm the module is updating.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Input State Group 0 (CH0-3)BITMAP16Inputs CH0-3Read
IR 1Input State Group 1 (CH4-7)BITMAP16Inputs CH4-7Read
IR 4Heart BeatUINT16HeartbeatRead
HR 0Set Output State Group 0 (CH0-3)BITMAP16Outputs CH0-3Read/write
HR 1Set Output State Group 1 (CH4-7)BITMAP16Outputs CH4-7Read/write

Enable Modbus control & writes

Modbus TCP needs no enabling; set the IP address (default static 192.168.1.100) with the USB configuration software before connecting to the network. The manual does not print the TCP port number.

Communication loss & watchdog

Per-channel watchdog (5-65534 s, 0 or 65535 = off) set in the USB software: with no read/write activity for that time the output goes to its chosen watchdog state and stays there until written again.

Byte order & addressing

Network setup

Watch out for

Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

9 of 9 shown
Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Input State Group 0 (CH0-3)Input states, bit 0 = lowest channel; 1 = high (no invert).BITMAP16Readbit 0 = CH0; bit 1 = CH1; bit 2 = CH2; bit 3 = CH3
IR1doc 30002Input State Group 1 (CH4-7)Input states, bit 0 = lowest channel; 1 = high (no invert).BITMAP16Readbit 0 = CH4; bit 1 = CH5; bit 2 = CH6; bit 3 = CH7
IR2doc 30003Input State Group 2 (CH8-11)Input states, bit 0 = lowest channel; 1 = high (no invert).BITMAP16Readbit 0 = CH8; bit 1 = CH9; bit 2 = CH10; bit 3 = CH11
IR3doc 30004Input State Group 3 (CH12-15)Input states, bit 0 = lowest channel; 1 = high (no invert).BITMAP16Readbit 0 = CH12; bit 1 = CH13; bit 2 = CH14; bit 3 = CH15
IR4doc 30005Heart BeatCounter that rises by 1 per transfer and wraps at 65535.UINT16Read
HR0doc 40001Set Output State Group 0 (CH0-3)Output commands, bit 0 = lowest channel; 1 = on (sourcing).BITMAP16Read/writebit 0 = CH0; bit 1 = CH1; bit 2 = CH2; bit 3 = CH3
HR1doc 40002Set Output State Group 1 (CH4-7)Output commands, bit 0 = lowest channel; 1 = on (sourcing).BITMAP16Read/writebit 0 = CH4; bit 1 = CH5; bit 2 = CH6; bit 3 = CH7
HR2doc 40003Set Output State Group 2 (CH8-11)Output commands, bit 0 = lowest channel; 1 = on (sourcing).BITMAP16Read/writebit 0 = CH8; bit 1 = CH9; bit 2 = CH10; bit 3 = CH11
HR3doc 40004Set Output State Group 3 (CH12-15)Output commands, bit 0 = lowest channel; 1 = on (sourcing).BITMAP16Read/writebit 0 = CH12; bit 1 = CH13; bit 2 = CH14; bit 3 = CH15

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP)

What Modbus registers does the Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP) have?

This map lists 9 registers: 5 input registers, 4 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register map prints both the reference (30001, 40001) and the 0-based address column (0, 1, 2...); the address column is what goes on the wire.

What are the minimum Modbus registers to integrate the Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP)?

Start with IR 0 Input State Group 0 (CH0-3) (Inputs CH0-3); IR 1 Input State Group 1 (CH4-7) (Inputs CH4-7); IR 4 Heart Beat (Heartbeat); HR 0 Set Output State Group 0 (CH0-3) (Outputs CH0-3); HR 1 Set Output State Group 1 (CH4-7) (Outputs CH4-7).

How do I enable Modbus control of the Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP)?

Modbus TCP needs no enabling; set the IP address (default static 192.168.1.100) with the USB configuration software before connecting to the network. The manual does not print the TCP port number.

What happens when the Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP) loses Modbus communication?

Per-channel watchdog (5-65534 s, 0 or 65535 = off) set in the USB software: with no read/write activity for that time the output goes to its chosen watchdog state and stays there until written again.

Where is the official Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP) Modbus documentation?

The source is BusWorks XT Series Model XT1121-000 16-Channel Sourcing Digital I/O User's Manual (8500950P), revision 2022-11-18, published free by Acromag at https://www.acromag.com/wp-content/uploads/2019/06/Acromag-XT1121_950P-User-Manual.pdf.

More Acromag Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: BusWorks XT Series Model XT1121-000 16-Channel Sourcing Digital I/O User's Manual · 8500950P · rev. 2022-11-18. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.