Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP) Modbus register map

Updated 19 November 2026

Short answer

The Acromag BusWorks XT1211 (current) and XT1221 (voltage) are 8-channel differential analog input modules on Modbus TCP. The Modbus map is read-only: eight normalized channel values and a heartbeat counter.

This page lists 9 Modbus registers for the Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Acromag’s own free documentation (linked below) and checked against it.

Manufacturer
Acromag
Model
BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP)
Equipment type
Sensor (Ethernet analog input module)
Registers
9 (0 writable)
Transport
Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
XT1211-000, XT1221-000, XT1211, XT1221, BusWorks XT1211, BusWorks XT1221
Source document
BusWorks XT Series Model XT1211/XT1221-000 8 CH Differential Current/Voltage Input User's Manual · 8500951K · rev. 2022-11-18
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP)

Integration in brief

Read input registers 0-7 for the eight channels and convert counts to engineering units from the configured range (30000 = 100 %). Watch register 8 to confirm fresh data.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0CH 00 dataINT16Channel 0Read
IR 1CH 01 dataINT16Channel 1Read
IR 7CH 07 dataINT16Channel 7Read
IR 8Heart beatUINT16HeartbeatRead

Enable Modbus control & writes

Modbus TCP needs no enabling; set the IP address (default static 192.168.1.100) and channel ranges with the USB configuration software before connecting to the network.

Byte order & addressing

Network setup

Watch out for

Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

9 of 9 shown
Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001CH 00 dataNormalized count: ±30000 = ±100 % of the range (±20000 in legacy mode).INT16Read
IR1doc 30002CH 01 dataNormalized count: ±30000 = ±100 % of the range (±20000 in legacy mode).INT16Read
IR2doc 30003CH 02 dataNormalized count: ±30000 = ±100 % of the range (±20000 in legacy mode).INT16Read
IR3doc 30004CH 03 dataNormalized count: ±30000 = ±100 % of the range (±20000 in legacy mode).INT16Read
IR4doc 30005CH 04 dataNormalized count: ±30000 = ±100 % of the range (±20000 in legacy mode).INT16Read
IR5doc 30006CH 05 dataNormalized count: ±30000 = ±100 % of the range (±20000 in legacy mode).INT16Read
IR6doc 30007CH 06 dataNormalized count: ±30000 = ±100 % of the range (±20000 in legacy mode).INT16Read
IR7doc 30008CH 07 dataNormalized count: ±30000 = ±100 % of the range (±20000 in legacy mode).INT16Read
IR8doc 30009Heart beatCounts 0-65535 on each host transfer, then wraps.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP)

What Modbus registers does the Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP) have?

This map lists 9 registers: 9 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register map prints both the reference (00001, 10001, 30001, 40001) and the 0-based address column; the address column is what goes on the wire.

What are the minimum Modbus registers to integrate the Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP)?

Start with IR 0 CH 00 data (Channel 0); IR 1 CH 01 data (Channel 1); IR 7 CH 07 data (Channel 7); IR 8 Heart beat (Heartbeat).

How do I enable Modbus control of the Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP)?

Modbus TCP needs no enabling; set the IP address (default static 192.168.1.100) and channel ranges with the USB configuration software before connecting to the network.

Where is the official Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP) Modbus documentation?

The source is BusWorks XT Series Model XT1211/XT1221-000 8 CH Differential Current/Voltage Input User's Manual (8500951K), revision 2022-11-18, published free by Acromag at https://www.acromag.com/wp-content/uploads/2019/06/Acromag-XT1211-and-XT1221_951K-User-Manual.pdf.

More Acromag Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: BusWorks XT Series Model XT1211/XT1221-000 8 CH Differential Current/Voltage Input User's Manual · 8500951K · rev. 2022-11-18. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.