Sensor (remote I/O module, digital inputs/outputs) · Modbus register map

Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) Modbus register map

Updated 17 November 2026

Short answer

The R-32DIDO is a Seneca R-series remote I/O with 32 digital channels that can each be set as input or output, each with a 32-bit counter. It serves Modbus TCP on Ethernet and Modbus RTU on RS-485. This map covers the two 16-bit I/O words, the 32 counters and the coil and discrete-input views of each channel.

This page lists 103 Modbus registers for the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) — 66 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.

Manufacturer
Seneca
Model
R-32DIDO Ethernet I/O (32 digital inputs/outputs)
Equipment type
Sensor (remote I/O module, digital inputs/outputs)
Registers
103 (66 writable)
Transport
Modbus TCP, Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8N1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO
Source document
Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)

Integration in brief

Read holding registers 20-21 for all 32 channels as two bit words, or use coils 0-31 / discrete inputs 0-31. Counters are 32-bit MSW-first pairs from 100.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 20Digital I/O channels 1-16BITMAP16Channels 1-16Read/write
HR 21Digital I/O channels 17-32BITMAP16Channels 17-32Read/write
HR 100Counter 1UINT32 ABCDCounter 1Read/write
HR 102Counter 2UINT32 ABCDCounter 2Read/write

Enable Modbus control & writes

Modbus TCP server and RTU slave are on by default; channel direction and counters are configured in the web server.

Communication loss & watchdog

Per the web-server chapter, each channel set as an output has an optional watchdog (default disabled, timeout default 100 s) triggered by no Modbus traffic or no output writes; the output then takes its configured watchdog state.

Byte order & addressing

Network setup

Watch out for

Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

103 of 103 shown
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 1Digital I/O 1BITRead/write
CO1doc 2Digital I/O 2BITRead/write
CO2doc 3Digital I/O 3BITRead/write
CO3doc 4Digital I/O 4BITRead/write
CO4doc 5Digital I/O 5BITRead/write
CO5doc 6Digital I/O 6BITRead/write
CO6doc 7Digital I/O 7BITRead/write
CO7doc 8Digital I/O 8BITRead/write
CO8doc 9Digital I/O 9BITRead/write
CO9doc 10Digital I/O 10BITRead/write
CO10doc 11Digital I/O 11BITRead/write
CO11doc 12Digital I/O 12BITRead/write
CO12doc 13Digital I/O 13BITRead/write
CO13doc 14Digital I/O 14BITRead/write
CO14doc 15Digital I/O 15BITRead/write
CO15doc 16Digital I/O 16BITRead/write
CO16doc 17Digital I/O 17BITRead/write
CO17doc 18Digital I/O 18BITRead/write
CO18doc 19Digital I/O 19BITRead/write
CO19doc 20Digital I/O 20BITRead/write
CO20doc 21Digital I/O 21BITRead/write
CO21doc 22Digital I/O 22BITRead/write
CO22doc 23Digital I/O 23BITRead/write
CO23doc 24Digital I/O 24BITRead/write
CO24doc 25Digital I/O 25BITRead/write
CO25doc 26Digital I/O 26BITRead/write
CO26doc 27Digital I/O 27BITRead/write
CO27doc 28Digital I/O 28BITRead/write
CO28doc 29Digital I/O 29BITRead/write
CO29doc 30Digital I/O 30BITRead/write
CO30doc 31Digital I/O 31BITRead/write
CO31doc 32Digital I/O 32BITRead/write
DI0doc 10001Digital I/O 1 stateBITRead
DI1doc 10002Digital I/O 2 stateBITRead
DI2doc 10003Digital I/O 3 stateBITRead
DI3doc 10004Digital I/O 4 stateBITRead
DI4doc 10005Digital I/O 5 stateBITRead
DI5doc 10006Digital I/O 6 stateBITRead
DI6doc 10007Digital I/O 7 stateBITRead
DI7doc 10008Digital I/O 8 stateBITRead
DI8doc 10009Digital I/O 9 stateBITRead
DI9doc 10010Digital I/O 10 stateBITRead
DI10doc 10011Digital I/O 11 stateBITRead
DI11doc 10012Digital I/O 12 stateBITRead
DI12doc 10013Digital I/O 13 stateBITRead
DI13doc 10014Digital I/O 14 stateBITRead
DI14doc 10015Digital I/O 15 stateBITRead
DI15doc 10016Digital I/O 16 stateBITRead
DI16doc 10017Digital I/O 17 stateBITRead
DI17doc 10018Digital I/O 18 stateBITRead
DI18doc 10019Digital I/O 19 stateBITRead
DI19doc 10020Digital I/O 20 stateBITRead
DI20doc 10021Digital I/O 21 stateBITRead
DI21doc 10022Digital I/O 22 stateBITRead
DI22doc 10023Digital I/O 23 stateBITRead
DI23doc 10024Digital I/O 24 stateBITRead
DI24doc 10025Digital I/O 25 stateBITRead
DI25doc 10026Digital I/O 26 stateBITRead
DI26doc 10027Digital I/O 27 stateBITRead
DI27doc 10028Digital I/O 28 stateBITRead
DI28doc 10029Digital I/O 29 stateBITRead
DI29doc 10030Digital I/O 30 stateBITRead
DI30doc 10031Digital I/O 31 stateBITRead
DI31doc 10032Digital I/O 32 stateBITRead
HR0doc 40001Machine IDDevice identification code.UINT16Read
HR1doc 40002Firmware revision (major/minor)UINT16Read
HR2doc 40003Firmware revision (fix/build)UINT16Read
HR3doc 40004Firmware codeUINT16Read
HR6doc 40007Board IDHardware revision.UINT16Read
HR20doc 40021Digital I/O channels 1-16Bit 0 = channel 1 ... bit 15 = channel 16.BITMAP16Read/writebit 0 = Channel 1; bit 1 = Channel 2; bit 2 = Channel 3; bit 3 = Channel 4; bit 4 = Channel 5; bit 5 = Channel 6; bit 6 = Channel 7; bit 7 = Channel 8; bit 8 = Channel 9; bit 9 = Channel 10; bit 10 = Channel 11; bit 11 = Channel 12; bit 12 = Channel 13; bit 13 = Channel 14; bit 14 = Channel 15; bit 15 = Channel 16
HR21doc 40022Digital I/O channels 17-32Bit 0 = channel 17 ... bit 15 = channel 32.BITMAP16Read/writebit 0 = Channel 17; bit 1 = Channel 18; bit 2 = Channel 19; bit 3 = Channel 20; bit 4 = Channel 21; bit 5 = Channel 22; bit 6 = Channel 23; bit 7 = Channel 24; bit 8 = Channel 25; bit 9 = Channel 26; bit 10 = Channel 27; bit 11 = Channel 28; bit 12 = Channel 29; bit 13 = Channel 30; bit 14 = Channel 31; bit 15 = Channel 32
HR100doc 40101Counter 1Digital input counter, MSW first.UINT32ABCDRead/write
HR102doc 40103Counter 2Digital input counter, MSW first.UINT32ABCDRead/write
HR104doc 40105Counter 3Digital input counter, MSW first.UINT32ABCDRead/write
HR106doc 40107Counter 4Digital input counter, MSW first.UINT32ABCDRead/write
HR108doc 40109Counter 5Digital input counter, MSW first.UINT32ABCDRead/write
HR110doc 40111Counter 6Digital input counter, MSW first.UINT32ABCDRead/write
HR112doc 40113Counter 7Digital input counter, MSW first.UINT32ABCDRead/write
HR114doc 40115Counter 8Digital input counter, MSW first.UINT32ABCDRead/write
HR116doc 40117Counter 9Digital input counter, MSW first.UINT32ABCDRead/write
HR118doc 40119Counter 10Digital input counter, MSW first.UINT32ABCDRead/write
HR120doc 40121Counter 11Digital input counter, MSW first.UINT32ABCDRead/write
HR122doc 40123Counter 12Digital input counter, MSW first.UINT32ABCDRead/write
HR124doc 40125Counter 13Digital input counter, MSW first.UINT32ABCDRead/write
HR126doc 40127Counter 14Digital input counter, MSW first.UINT32ABCDRead/write
HR128doc 40129Counter 15Digital input counter, MSW first.UINT32ABCDRead/write
HR130doc 40131Counter 16Digital input counter, MSW first.UINT32ABCDRead/write
HR132doc 40133Counter 17Digital input counter, MSW first.UINT32ABCDRead/write
HR134doc 40135Counter 18Digital input counter, MSW first.UINT32ABCDRead/write
HR136doc 40137Counter 19Digital input counter, MSW first.UINT32ABCDRead/write
HR138doc 40139Counter 20Digital input counter, MSW first.UINT32ABCDRead/write
HR140doc 40141Counter 21Digital input counter, MSW first.UINT32ABCDRead/write
HR142doc 40143Counter 22Digital input counter, MSW first.UINT32ABCDRead/write
HR144doc 40145Counter 23Digital input counter, MSW first.UINT32ABCDRead/write
HR146doc 40147Counter 24Digital input counter, MSW first.UINT32ABCDRead/write
HR148doc 40149Counter 25Digital input counter, MSW first.UINT32ABCDRead/write
HR150doc 40151Counter 26Digital input counter, MSW first.UINT32ABCDRead/write
HR152doc 40153Counter 27Digital input counter, MSW first.UINT32ABCDRead/write
HR154doc 40155Counter 28Digital input counter, MSW first.UINT32ABCDRead/write
HR156doc 40157Counter 29Digital input counter, MSW first.UINT32ABCDRead/write
HR158doc 40159Counter 30Digital input counter, MSW first.UINT32ABCDRead/write
HR160doc 40161Counter 31Digital input counter, MSW first.UINT32ABCDRead/write
HR162doc 40163Counter 32Digital input counter, MSW first.UINT32ABCDRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)

What Modbus registers does the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) have?

This map lists 103 registers: 32 coils, 32 discrete inputs, 39 holding registers. 66 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Holding-register tables print the 4x number (40001) and the 0-based offset (0); coils print 1 / offset 0 and discrete inputs 10001 / offset 0. The offset is the wire address.

What byte order does the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)?

Start with HR 20 Digital I/O channels 1-16 (Channels 1-16); HR 21 Digital I/O channels 17-32 (Channels 17-32); HR 100 Counter 1 (Counter 1); HR 102 Counter 2 (Counter 2).

How do I enable Modbus control of the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)?

Modbus TCP server and RTU slave are on by default; channel direction and counters are configured in the web server.

What happens when the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) loses Modbus communication?

Per the web-server chapter, each channel set as an output has an optional watchdog (default disabled, timeout default 100 s) triggered by no Modbus traffic or no output writes; the output then takes its configured watchdog state.

Where is the official Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) Modbus documentation?

The source is Series R I/O with protocol - User Manual (MI-00604-29-EN), revision 2026-09-03, published free by Seneca at https://www.seneca.it/media/6848135/mi00604-29-en.pdf.

More Seneca Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.