Sensor (remote I/O module, digital inputs/outputs) · Modbus register map
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) Modbus register map
Updated 17 November 2026
The R-32DIDO is a Seneca R-series remote I/O with 32 digital channels that can each be set as input or output, each with a 32-bit counter. It serves Modbus TCP on Ethernet and Modbus RTU on RS-485. This map covers the two 16-bit I/O words, the 32 counters and the coil and discrete-input views of each channel.
This page lists 103 Modbus registers for the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) — 66 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seneca
- Model
- R-32DIDO Ethernet I/O (32 digital inputs/outputs)
- Equipment type
- Sensor (remote I/O module, digital inputs/outputs)
- Registers
- 103 (66 writable)
- Transport
- Modbus TCP, Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO
Integration notes: Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
Read holding registers 20-21 for all 32 channels as two bit words, or use coils 0-31 / discrete inputs 0-31. Counters are 32-bit MSW-first pairs from 100.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 20 | Digital I/O channels 1-16 | BITMAP16 | Channels 1-16 | Read/write |
| HR 21 | Digital I/O channels 17-32 | BITMAP16 | Channels 17-32 | Read/write |
| HR 100 | Counter 1 | UINT32 ABCD | Counter 1 | Read/write |
| HR 102 | Counter 2 | UINT32 ABCD | Counter 2 | Read/write |
Enable Modbus control & writes
Modbus TCP server and RTU slave are on by default; channel direction and counters are configured in the web server.
Communication loss & watchdog
Per the web-server chapter, each channel set as an output has an optional watchdog (default disabled, timeout default 100 s) triggered by no Modbus traffic or no output writes; the output then takes its configured watchdog state.
Byte order & addressing
- Offset is the wire address.
- Counters are MSW first on this model.
Network setup
- Factory IP is 192.168.90.101; change it before adding a second unit.
Watch out for
- Each channel is set as input or output in the configuration; check that before writing.
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 1 | Digital I/O 1 | BIT | Read/write | |||||
| CO | 1doc 2 | Digital I/O 2 | BIT | Read/write | |||||
| CO | 2doc 3 | Digital I/O 3 | BIT | Read/write | |||||
| CO | 3doc 4 | Digital I/O 4 | BIT | Read/write | |||||
| CO | 4doc 5 | Digital I/O 5 | BIT | Read/write | |||||
| CO | 5doc 6 | Digital I/O 6 | BIT | Read/write | |||||
| CO | 6doc 7 | Digital I/O 7 | BIT | Read/write | |||||
| CO | 7doc 8 | Digital I/O 8 | BIT | Read/write | |||||
| CO | 8doc 9 | Digital I/O 9 | BIT | Read/write | |||||
| CO | 9doc 10 | Digital I/O 10 | BIT | Read/write | |||||
| CO | 10doc 11 | Digital I/O 11 | BIT | Read/write | |||||
| CO | 11doc 12 | Digital I/O 12 | BIT | Read/write | |||||
| CO | 12doc 13 | Digital I/O 13 | BIT | Read/write | |||||
| CO | 13doc 14 | Digital I/O 14 | BIT | Read/write | |||||
| CO | 14doc 15 | Digital I/O 15 | BIT | Read/write | |||||
| CO | 15doc 16 | Digital I/O 16 | BIT | Read/write | |||||
| CO | 16doc 17 | Digital I/O 17 | BIT | Read/write | |||||
| CO | 17doc 18 | Digital I/O 18 | BIT | Read/write | |||||
| CO | 18doc 19 | Digital I/O 19 | BIT | Read/write | |||||
| CO | 19doc 20 | Digital I/O 20 | BIT | Read/write | |||||
| CO | 20doc 21 | Digital I/O 21 | BIT | Read/write | |||||
| CO | 21doc 22 | Digital I/O 22 | BIT | Read/write | |||||
| CO | 22doc 23 | Digital I/O 23 | BIT | Read/write | |||||
| CO | 23doc 24 | Digital I/O 24 | BIT | Read/write | |||||
| CO | 24doc 25 | Digital I/O 25 | BIT | Read/write | |||||
| CO | 25doc 26 | Digital I/O 26 | BIT | Read/write | |||||
| CO | 26doc 27 | Digital I/O 27 | BIT | Read/write | |||||
| CO | 27doc 28 | Digital I/O 28 | BIT | Read/write | |||||
| CO | 28doc 29 | Digital I/O 29 | BIT | Read/write | |||||
| CO | 29doc 30 | Digital I/O 30 | BIT | Read/write | |||||
| CO | 30doc 31 | Digital I/O 31 | BIT | Read/write | |||||
| CO | 31doc 32 | Digital I/O 32 | BIT | Read/write | |||||
| DI | 0doc 10001 | Digital I/O 1 state | BIT | Read | |||||
| DI | 1doc 10002 | Digital I/O 2 state | BIT | Read | |||||
| DI | 2doc 10003 | Digital I/O 3 state | BIT | Read | |||||
| DI | 3doc 10004 | Digital I/O 4 state | BIT | Read | |||||
| DI | 4doc 10005 | Digital I/O 5 state | BIT | Read | |||||
| DI | 5doc 10006 | Digital I/O 6 state | BIT | Read | |||||
| DI | 6doc 10007 | Digital I/O 7 state | BIT | Read | |||||
| DI | 7doc 10008 | Digital I/O 8 state | BIT | Read | |||||
| DI | 8doc 10009 | Digital I/O 9 state | BIT | Read | |||||
| DI | 9doc 10010 | Digital I/O 10 state | BIT | Read | |||||
| DI | 10doc 10011 | Digital I/O 11 state | BIT | Read | |||||
| DI | 11doc 10012 | Digital I/O 12 state | BIT | Read | |||||
| DI | 12doc 10013 | Digital I/O 13 state | BIT | Read | |||||
| DI | 13doc 10014 | Digital I/O 14 state | BIT | Read | |||||
| DI | 14doc 10015 | Digital I/O 15 state | BIT | Read | |||||
| DI | 15doc 10016 | Digital I/O 16 state | BIT | Read | |||||
| DI | 16doc 10017 | Digital I/O 17 state | BIT | Read | |||||
| DI | 17doc 10018 | Digital I/O 18 state | BIT | Read | |||||
| DI | 18doc 10019 | Digital I/O 19 state | BIT | Read | |||||
| DI | 19doc 10020 | Digital I/O 20 state | BIT | Read | |||||
| DI | 20doc 10021 | Digital I/O 21 state | BIT | Read | |||||
| DI | 21doc 10022 | Digital I/O 22 state | BIT | Read | |||||
| DI | 22doc 10023 | Digital I/O 23 state | BIT | Read | |||||
| DI | 23doc 10024 | Digital I/O 24 state | BIT | Read | |||||
| DI | 24doc 10025 | Digital I/O 25 state | BIT | Read | |||||
| DI | 25doc 10026 | Digital I/O 26 state | BIT | Read | |||||
| DI | 26doc 10027 | Digital I/O 27 state | BIT | Read | |||||
| DI | 27doc 10028 | Digital I/O 28 state | BIT | Read | |||||
| DI | 28doc 10029 | Digital I/O 29 state | BIT | Read | |||||
| DI | 29doc 10030 | Digital I/O 30 state | BIT | Read | |||||
| DI | 30doc 10031 | Digital I/O 31 state | BIT | Read | |||||
| DI | 31doc 10032 | Digital I/O 32 state | BIT | Read | |||||
| HR | 0doc 40001 | Machine ID | Device identification code. | UINT16 | Read | ||||
| HR | 1doc 40002 | Firmware revision (major/minor) | UINT16 | Read | |||||
| HR | 2doc 40003 | Firmware revision (fix/build) | UINT16 | Read | |||||
| HR | 3doc 40004 | Firmware code | UINT16 | Read | |||||
| HR | 6doc 40007 | Board ID | Hardware revision. | UINT16 | Read | ||||
| HR | 20doc 40021 | Digital I/O channels 1-16 | Bit 0 = channel 1 ... bit 15 = channel 16. | BITMAP16 | Read/write | bit 0 = Channel 1; bit 1 = Channel 2; bit 2 = Channel 3; bit 3 = Channel 4; bit 4 = Channel 5; bit 5 = Channel 6; bit 6 = Channel 7; bit 7 = Channel 8; bit 8 = Channel 9; bit 9 = Channel 10; bit 10 = Channel 11; bit 11 = Channel 12; bit 12 = Channel 13; bit 13 = Channel 14; bit 14 = Channel 15; bit 15 = Channel 16 | |||
| HR | 21doc 40022 | Digital I/O channels 17-32 | Bit 0 = channel 17 ... bit 15 = channel 32. | BITMAP16 | Read/write | bit 0 = Channel 17; bit 1 = Channel 18; bit 2 = Channel 19; bit 3 = Channel 20; bit 4 = Channel 21; bit 5 = Channel 22; bit 6 = Channel 23; bit 7 = Channel 24; bit 8 = Channel 25; bit 9 = Channel 26; bit 10 = Channel 27; bit 11 = Channel 28; bit 12 = Channel 29; bit 13 = Channel 30; bit 14 = Channel 31; bit 15 = Channel 32 | |||
| HR | 100doc 40101 | Counter 1 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 102doc 40103 | Counter 2 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 104doc 40105 | Counter 3 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 106doc 40107 | Counter 4 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 108doc 40109 | Counter 5 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 110doc 40111 | Counter 6 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 112doc 40113 | Counter 7 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 114doc 40115 | Counter 8 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 116doc 40117 | Counter 9 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 118doc 40119 | Counter 10 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 120doc 40121 | Counter 11 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 122doc 40123 | Counter 12 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 124doc 40125 | Counter 13 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 126doc 40127 | Counter 14 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 128doc 40129 | Counter 15 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 130doc 40131 | Counter 16 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 132doc 40133 | Counter 17 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 134doc 40135 | Counter 18 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 136doc 40137 | Counter 19 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 138doc 40139 | Counter 20 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 140doc 40141 | Counter 21 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 142doc 40143 | Counter 22 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 144doc 40145 | Counter 23 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 146doc 40147 | Counter 24 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 148doc 40149 | Counter 25 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 150doc 40151 | Counter 26 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 152doc 40153 | Counter 27 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 154doc 40155 | Counter 28 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 156doc 40157 | Counter 29 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 158doc 40159 | Counter 30 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 160doc 40161 | Counter 31 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write | |||
| HR | 162doc 40163 | Counter 32 | Digital input counter, MSW first. | UINT32 | ABCD | Read/write |
Notes on this map
- The protocol page lists function codes 01, 03, 05, 06, 15 and 16; the tables also give the digital inputs as 1x input status read with function 02. Modbus RTU runs on RS-485 and Modbus TCP serves up to 8 clients.
- Counters are printed MSW at the lower address (counter 1 MSW 40101, LSW 40102), so they are ABCD.
- Factory settings from the manual: static IP 192.168.90.101/24, gateway 192.168.90.1, Modbus TCP port 502, station address 1; RS-485 38400 baud, 8 data bits, no parity, 1 stop bit, address 1.
- Left out: period and frequency floats (40165-40292), because their rows do not mark which word is MSW and a sibling product in the same manual uses LSW first; the command and status registers, whose codes are not listed for this product; the large configuration and P2P rule block from 45001.
- The discrete-input table prints its rows as RW; discrete inputs are read-only by protocol and are listed as R.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
What Modbus registers does the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) have?
This map lists 103 registers: 32 coils, 32 discrete inputs, 39 holding registers. 66 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Holding-register tables print the 4x number (40001) and the 0-based offset (0); coils print 1 / offset 0 and discrete inputs 10001 / offset 0. The offset is the wire address.
What byte order does the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)?
Start with HR 20 Digital I/O channels 1-16 (Channels 1-16); HR 21 Digital I/O channels 17-32 (Channels 17-32); HR 100 Counter 1 (Counter 1); HR 102 Counter 2 (Counter 2).
How do I enable Modbus control of the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)?
Modbus TCP server and RTU slave are on by default; channel direction and counters are configured in the web server.
What happens when the Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) loses Modbus communication?
Per the web-server chapter, each channel set as an output has an optional watchdog (default disabled, timeout default 100 s) triggered by no Modbus traffic or no output writes; the output then takes its configured watchdog state.
Where is the official Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs) Modbus documentation?
The source is Series R I/O with protocol - User Manual (MI-00604-29-EN), revision 2026-09-03, published free by Seneca at https://www.seneca.it/media/6848135/mi00604-29-en.pdf.
More Seneca Modbus register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2 - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN
Other remote i/o modules register maps
- Sensor (remote I/O module)
Unipi Technology Unipi Extension xS52 resistance input module
Unipi Extension xS52 RS-485 module per the Unipi Extension xS52 Modbus map v2.0.
Also known as: Unipi Extension xS52, xS52 - Sensor / remote I/O module
Brainboxes ED-588 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-588 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-588, ED588 - Sensor (remote I/O module)
Moxa ioLogik R1214 RS-485 remote I/O
ioLogik R1214 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1214, R1214, R1214-T - Sensor (Ethernet I/O module)
Teracom TCW241 Ethernet I/O module
TCW241 per the Teracom TCW241 user manual Revision R4.30, firmware v2.012 or later.
Also known as: TCW241 - Sensor (Ethernet digital I/O module)
Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP)
BusWorks XT1121-000 per user's manual 8500950P (revision P, 18 Nov 2022).
Also known as: XT1121-000, XT1121, BusWorks XT1121 - Sensor (PWM output and counter input module)
ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)
ICP DAS M-7088 eight-channel PWM output module with eight digital inputs and counters, Modbus RTU firmware.
Also known as: M-7088, M7088
All remote i/o modules Modbus register maps →
Source: Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.