Easy Modbus
  1. Home
  2. Modbus register maps
  3. Seneca
  4. T203PM single-phase AC/DC power meter (Modbus RTU)

Power meter · Modbus register map

Seneca T203PM single-phase AC/DC power meter (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The T203PM is a DIN-rail transducer that measures true-RMS AC or DC voltage and current on one phase and works out power, energy, power factor, frequency and THD. It answers Modbus RTU on RS-485 (and on USB for setup). This map covers the float measurement block, min/max values, scaled integer copies, the 64-bit energy counters, the command register and the analog/digital output setup.

This page lists 61 Modbus registers for the Seneca T203PM single-phase AC/DC power meter (Modbus RTU) — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.

Manufacturer
Seneca
Model
T203PM single-phase AC/DC power meter (Modbus RTU)
Equipment type
Power meter
Registers
61 (23 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM
Source document
T203PM100-MU / T203PM300-MU / T203PM600-MU User Manual · MI00571-3-EN · rev. 2023-03-16
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Seneca T203PM single-phase AC/DC power meter (Modbus RTU)

Integration in brief

Read holding registers 104-125 (function 03) in one block for volts, amps, powers, energies, frequency, PF and THD as ABCD floats. Use the 64-bit counters at 181/185/189 when you need exact energy totals.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 104RMS voltageFLOAT32 ABCDRMS voltageRead
HR 106RMS currentFLOAT32 ABCDRMS currentRead
HR 108Active powerFLOAT32 ABCDActive powerRead
HR 114Active energyFLOAT32 ABCDActive energyRead
HR 120FrequencyFLOAT32 ABCDFrequencyRead
HR 122Power factorFLOAT32 ABCDPower factorRead
HR 181Active energy counterUINT64 ABCDActive energy counter, Wh/10Read/write

Enable Modbus control & writes

Modbus RTU slave is always on. Slave ID is register 2 and serial format register 81; the maker recommends its Easy Setup 2 software for configuration.

Byte order & addressing

Network setup

Watch out for

Seneca T203PM single-phase AC/DC power meter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

61 of 61 shown
Seneca T203PM single-phase AC/DC power meter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 40002Firmware revisionUINT16Read
HR2doc 40003Modbus slave IDFlash register; limit writes to about 10,000.UINT16Read/write
HR4doc 40005Command registerWrite a command code; table prints RO but the manual writes commands here.UINT16Read/write45505 = Clear energies; 49568 = Reboot; 49600 = Write to flash; 49612 = Clear min/max; 49616 = Enable write custom energies; 49617 = Write custom energies and reboot
HR71doc 40072Voltage multiplierMust be > 0.FLOAT32ABCDRead/write
HR73doc 40074Current multiplierMust be > 0.FLOAT32ABCDRead/write
HR75doc 40076Voltage transformation ratioMust be > 0.FLOAT32ABCDRead/write
HR77doc 40078Current cut-off0 = disabled.FLOAT32ABCDARead/write
HR79doc 40080Voltage cut-off0 = disabled.FLOAT32ABCDVRead/write
HR81doc 40082Serial settings (stop bits / parity / baud)Bit 12 stop bits, bits 8-9 parity, bits 0-7 baud code.BITMAP16Read/writebit 12 = Stop bits: 0 = 1, 1 = 2; bit 0-7 = Baud: 0=2400 1=4800 2=9600 3=19200 4=38400 5=57600 6=115200; bit 8-9 = Parity: 0 none, 1 even, 2 odd
HR82doc 40083Measure typeUINT16Read/write0 = AC; 1 = DC
HR83doc 40084AO / DO measure selectionHigh byte = analog output source, low byte = digital output source.UINT16Read/writebit 0-7 = DO measure: same codes; bit 8-15 = AO measure: 0 none,1 V,2 A,3 P,4 Q,5 S,6 Hz,7 PF,8 THD
HR84doc 40085Digital output behaviourUINT16Read/write0 = None; 1 = Max alarm; 2 = Min alarm; 3 = Inside window; 4 = Outside window; 5 = 1000 pulses/kWh; 6 = 100 pulses/kWh; 7 = 10 pulses/kWh; 8 = 1 pulse/kWh; 9 = 100 pulses/MWh; 10 = 10 pulses/MWh; 11 = 1 pulse/MWh
HR85doc 40086AO input scale startFLOAT32ABCDRead/write
HR87doc 40088AO input scale endFLOAT32ABCDRead/write
HR89doc 40090AO output voltage minimumFLOAT32ABCDVRead/write
HR91doc 40092AO output voltage maximumFLOAT32ABCDVRead/write
HR93doc 40094AO output voltage presentFLOAT32ABCDVRead
HR95doc 40096DO normally highUINT16Read/write0 = Normally low; 1 = Normally high
HR96doc 40097DO low alarm thresholdFLOAT32ABCDRead/write
HR98doc 40099DO high alarm thresholdFLOAT32ABCDRead/write
HR100doc 40101DO alarm hysteresisFLOAT32ABCDRead/write
HR102doc 40103DO alarm delayCounts of 10 ms.UINT16× 10msRead/write
HR103doc 40104DO alarm statusUINT16Read0 = None; 1 = Max pre-alarm; 2 = Min pre-alarm; 4 = Inside window pre-alarm; 8 = Outside window pre-alarm; 256 = Max alarm; 512 = Min alarm; 1024 = Inside window alarm; 2048 = Outside window alarm
HR104doc 40105RMS voltageFLOAT32ABCDVRead
HR106doc 40107RMS currentSigned in DC mode.FLOAT32ABCDARead
HR108doc 40109Active powerFLOAT32ABCDWRead
HR110doc 40111Reactive powerFLOAT32ABCDvarRead
HR112doc 40113Apparent powerFLOAT32ABCDVARead
HR114doc 40115Active energyFLOAT32ABCDWhRead
HR116doc 40117Reactive energyFLOAT32ABCDvarhRead
HR118doc 40119Apparent energyFLOAT32ABCDVAhRead
HR120doc 40121FrequencyFLOAT32ABCDHzRead
HR122doc 40123Power factorFLOAT32ABCDRead
HR124doc 40125THDMeasured on current.FLOAT32ABCD%Read
HR139doc 40140Minimum RMS voltageFLOAT32ABCDVRead
HR141doc 40142Maximum RMS voltageFLOAT32ABCDVRead
HR143doc 40144Minimum RMS currentFLOAT32ABCDARead
HR145doc 40146Maximum RMS currentFLOAT32ABCDARead
HR147doc 40148Minimum active powerFLOAT32ABCDWRead
HR149doc 40150Maximum active powerFLOAT32ABCDWRead
HR151doc 40152Minimum reactive powerFLOAT32ABCDvarRead
HR153doc 40154Maximum reactive powerFLOAT32ABCDvarRead
HR155doc 40156Minimum apparent powerFLOAT32ABCDVARead
HR157doc 40158Maximum apparent powerTable text says minimum; register name is the maximum.FLOAT32ABCDVARead
HR159doc 40160Minimum frequencyFLOAT32ABCDHzRead
HR161doc 40162Maximum frequencyFLOAT32ABCDHzRead
HR163doc 40164Minimum power factorFLOAT32ABCDRead
HR165doc 40166Maximum power factorFLOAT32ABCDRead
HR167doc 40168Minimum THDFLOAT32ABCD%Read
HR169doc 40170Maximum THDFLOAT32ABCD%Read
HR173doc 40174RMS voltage (integer)INT16× 0.1VRead
HR174doc 40175RMS current (integer)INT16× 0.1ARead
HR175doc 40176Active power (integer)INT32ABCD× 0.1WRead
HR177doc 40178Reactive power (integer)INT32ABCD× 0.1varRead
HR179doc 40180Apparent power (integer)INT32ABCD× 0.1VARead
HR181doc 40182Active energy counterWritable only after the enable-custom-energies command.UINT64ABCD× 0.1WhRead/write
HR185doc 40186Reactive energy counterWritable only after the enable-custom-energies command.UINT64ABCD× 0.1varhRead/write
HR189doc 40190Apparent energy counterWritable only after the enable-custom-energies command.UINT64ABCD× 0.1VAhRead/write
HR193doc 40194Frequency (integer)UINT16× 0.1HzRead
HR194doc 40195Power factor (integer)INT16× 0.001Read
HR195doc 40196THD (integer)INT16× 0.1%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Seneca T203PM single-phase AC/DC power meter (Modbus RTU)

What Modbus registers does the Seneca T203PM single-phase AC/DC power meter (Modbus RTU) have?

This map lists 61 registers: 61 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Seneca T203PM single-phase AC/DC power meter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints both the 4x number (40002) and the 0-based offset (1). The offset is the wire address: 40002 is sent as 1.

What byte order does the Seneca T203PM single-phase AC/DC power meter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Seneca T203PM single-phase AC/DC power meter (Modbus RTU)?

Start with HR 104 RMS voltage (RMS voltage); HR 106 RMS current (RMS current); HR 108 Active power (Active power); HR 114 Active energy (Active energy); HR 120 Frequency (Frequency); HR 122 Power factor (Power factor); HR 181 Active energy counter (Active energy counter, Wh/10).

How do I enable Modbus control of the Seneca T203PM single-phase AC/DC power meter (Modbus RTU)?

Modbus RTU slave is always on. Slave ID is register 2 and serial format register 81; the maker recommends its Easy Setup 2 software for configuration.

Where is the official Seneca T203PM single-phase AC/DC power meter (Modbus RTU) Modbus documentation?

The source is T203PM100-MU / T203PM300-MU / T203PM600-MU User Manual (MI00571-3-EN), revision 2023-03-16, published free by Seneca at https://www.seneca.it/media/6849089/mi00571-3-en.pdf.

More Seneca Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: T203PM100-MU / T203PM300-MU / T203PM600-MU User Manual · MI00571-3-EN · rev. 2023-03-16. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.