- R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
Sensor (remote I/O module, digital inputs/outputs) · Modbus register map
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) Modbus register map
Updated 17 November 2026
The R-16DI-8DO is a Seneca R-series remote I/O with 16 digital inputs, each with a 32-bit counter and pulse timing, and 8 digital outputs. It serves Modbus TCP on two Ethernet ports and Modbus RTU on RS-485. This map covers the input and output words, counters and counter reset, low/high time and period floats, integer frequencies, and the coil/discrete-input views.
This page lists 125 Modbus registers for the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) — 42 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seneca
- Model
- R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
- Equipment type
- Sensor (remote I/O module, digital inputs/outputs)
- Registers
- 125 (42 writable)
- Transport
- Modbus TCP, Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO
Integration notes: Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
Read holding register 20 for all 16 inputs and write 22 for the 8 outputs (or use coils 32-39). Counters are 32-bit LSW-first pairs from 102; reset any of them through register 100 or coils 100-115.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 20 | Digital inputs | BITMAP16 | Digital inputs | Read |
| HR 22 | Digital outputs | BITMAP16 | Digital outputs | Read/write |
| HR 102 | Counter 1 | UINT32 CDAB | Counter 1 | Read/write |
| HR 100 | Counter reset | BITMAP16 | Counter reset bits | Read/write |
| HR 528 | Input 1 period | FLOAT32 CDAB | Input 1 period | Read |
Enable Modbus control & writes
Modbus TCP server and RTU slave are on by default; configure through the web server or Seneca Discovery Device.
Communication loss & watchdog
Per the web-server chapter, an optional digital-output watchdog (default disabled, timeout default 5 s) sends the outputs to their fail state when no Modbus, USB or P2P traffic arrives within the timeout.
Byte order & addressing
- Offset is the wire address.
- 32-bit values are LSW first on this model.
Network setup
- Factory IP is 192.168.90.101; change it before adding a second unit.
Watch out for
- Do not assume sibling R-series word order; this model's table is LSW first.
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 32doc 33 | Digital output 1 | BIT | Read/write | |||||
| CO | 33doc 34 | Digital output 2 | BIT | Read/write | |||||
| CO | 34doc 35 | Digital output 3 | BIT | Read/write | |||||
| CO | 35doc 36 | Digital output 4 | BIT | Read/write | |||||
| CO | 36doc 37 | Digital output 5 | BIT | Read/write | |||||
| CO | 37doc 38 | Digital output 6 | BIT | Read/write | |||||
| CO | 38doc 39 | Digital output 7 | BIT | Read/write | |||||
| CO | 39doc 40 | Digital output 8 | BIT | Read/write | |||||
| CO | 100doc 101 | Counter 1 reset | BIT | Read/write | |||||
| CO | 101doc 102 | Counter 2 reset | BIT | Read/write | |||||
| CO | 102doc 103 | Counter 3 reset | BIT | Read/write | |||||
| CO | 103doc 104 | Counter 4 reset | BIT | Read/write | |||||
| CO | 104doc 105 | Counter 5 reset | BIT | Read/write | |||||
| CO | 105doc 106 | Counter 6 reset | BIT | Read/write | |||||
| CO | 106doc 107 | Counter 7 reset | BIT | Read/write | |||||
| CO | 107doc 108 | Counter 8 reset | BIT | Read/write | |||||
| CO | 108doc 109 | Counter 9 reset | BIT | Read/write | |||||
| CO | 109doc 110 | Counter 10 reset | BIT | Read/write | |||||
| CO | 110doc 111 | Counter 11 reset | BIT | Read/write | |||||
| CO | 111doc 112 | Counter 12 reset | BIT | Read/write | |||||
| CO | 112doc 113 | Counter 13 reset | BIT | Read/write | |||||
| CO | 113doc 114 | Counter 14 reset | BIT | Read/write | |||||
| CO | 114doc 115 | Counter 15 reset | BIT | Read/write | |||||
| CO | 115doc 116 | Counter 16 reset | BIT | Read/write | |||||
| DI | 0doc 10001 | Digital input 1 | BIT | Read | |||||
| DI | 1doc 10002 | Digital input 2 | BIT | Read | |||||
| DI | 2doc 10003 | Digital input 3 | BIT | Read | |||||
| DI | 3doc 10004 | Digital input 4 | BIT | Read | |||||
| DI | 4doc 10005 | Digital input 5 | BIT | Read | |||||
| DI | 5doc 10006 | Digital input 6 | BIT | Read | |||||
| DI | 6doc 10007 | Digital input 7 | BIT | Read | |||||
| DI | 7doc 10008 | Digital input 8 | BIT | Read | |||||
| DI | 8doc 10009 | Digital input 9 | BIT | Read | |||||
| DI | 9doc 10010 | Digital input 10 | BIT | Read | |||||
| DI | 10doc 10011 | Digital input 11 | BIT | Read | |||||
| DI | 11doc 10012 | Digital input 12 | BIT | Read | |||||
| DI | 12doc 10013 | Digital input 13 | BIT | Read | |||||
| DI | 13doc 10014 | Digital input 14 | BIT | Read | |||||
| DI | 14doc 10015 | Digital input 15 | BIT | Read | |||||
| DI | 15doc 10016 | Digital input 16 | BIT | Read | |||||
| HR | 0doc 40001 | Machine ID | Device identification code. | UINT16 | Read | ||||
| HR | 1doc 40002 | Firmware revision | UINT16 | Read | |||||
| HR | 20doc 40021 | Digital inputs | Bit 0 = input 1 ... bit 15 = input 16. | BITMAP16 | Read | bit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4; bit 4 = Input 5; bit 5 = Input 6; bit 6 = Input 7; bit 7 = Input 8; bit 8 = Input 9; bit 9 = Input 10; bit 10 = Input 11; bit 11 = Input 12; bit 12 = Input 13; bit 13 = Input 14; bit 14 = Input 15; bit 15 = Input 16 | |||
| HR | 22doc 40023 | Digital outputs | Bit 0 = output 1 ... bit 7 = output 8. | BITMAP16 | Read/write | bit 0 = Output 1; bit 1 = Output 2; bit 2 = Output 3; bit 3 = Output 4; bit 4 = Output 5; bit 5 = Output 6; bit 6 = Output 7; bit 7 = Output 8 | |||
| HR | 100doc 40101 | Counter reset | Write a 1 in bit n-1 to reset counter n. | BITMAP16 | Read/write | bit 0 = Reset counter 1; bit 1 = Reset counter 2; bit 2 = Reset counter 3; bit 3 = Reset counter 4; bit 4 = Reset counter 5; bit 5 = Reset counter 6; bit 6 = Reset counter 7; bit 7 = Reset counter 8; bit 8 = Reset counter 9; bit 9 = Reset counter 10; bit 10 = Reset counter 11; bit 11 = Reset counter 12; bit 12 = Reset counter 13; bit 13 = Reset counter 14; bit 14 = Reset counter 15; bit 15 = Reset counter 16 | |||
| HR | 102doc 40103 | Counter 1 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 104doc 40105 | Counter 2 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 106doc 40107 | Counter 3 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 108doc 40109 | Counter 4 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 110doc 40111 | Counter 5 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 112doc 40113 | Counter 6 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 114doc 40115 | Counter 7 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 116doc 40117 | Counter 8 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 118doc 40119 | Counter 9 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 120doc 40121 | Counter 10 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 122doc 40123 | Counter 11 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 124doc 40125 | Counter 12 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 126doc 40127 | Counter 13 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 128doc 40129 | Counter 14 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 130doc 40131 | Counter 15 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 132doc 40133 | Counter 16 | Digital input counter, LSW first. | UINT32 | CDAB | Read/write | |||
| HR | 296doc 40297 | Input 1 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 297doc 40298 | Input 2 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 298doc 40299 | Input 3 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 299doc 40300 | Input 4 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 300doc 40301 | Input 5 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 301doc 40302 | Input 6 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 302doc 40303 | Input 7 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 303doc 40304 | Input 8 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 304doc 40305 | Input 9 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 305doc 40306 | Input 10 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 306doc 40307 | Input 11 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 307doc 40308 | Input 12 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 308doc 40309 | Input 13 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 309doc 40310 | Input 14 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 310doc 40311 | Input 15 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 311doc 40312 | Input 16 frequency (integer) | UINT16 | Hz | Read | ||||
| HR | 400doc 40401 | Input 1 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 402doc 40403 | Input 2 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 404doc 40405 | Input 3 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 406doc 40407 | Input 4 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 408doc 40409 | Input 5 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 410doc 40411 | Input 6 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 412doc 40413 | Input 7 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 414doc 40415 | Input 8 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 416doc 40417 | Input 9 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 418doc 40419 | Input 10 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 420doc 40421 | Input 11 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 422doc 40423 | Input 12 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 424doc 40425 | Input 13 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 426doc 40427 | Input 14 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 428doc 40429 | Input 15 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 430doc 40431 | Input 16 low time | FLOAT32 | CDAB | ms | Read | |||
| HR | 464doc 40465 | Input 1 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 466doc 40467 | Input 2 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 468doc 40469 | Input 3 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 470doc 40471 | Input 4 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 472doc 40473 | Input 5 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 474doc 40475 | Input 6 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 476doc 40477 | Input 7 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 478doc 40479 | Input 8 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 480doc 40481 | Input 9 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 482doc 40483 | Input 10 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 484doc 40485 | Input 11 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 486doc 40487 | Input 12 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 488doc 40489 | Input 13 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 490doc 40491 | Input 14 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 492doc 40493 | Input 15 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 494doc 40495 | Input 16 high time | FLOAT32 | CDAB | ms | Read | |||
| HR | 528doc 40529 | Input 1 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 530doc 40531 | Input 2 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 532doc 40533 | Input 3 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 534doc 40535 | Input 4 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 536doc 40537 | Input 5 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 538doc 40539 | Input 6 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 540doc 40541 | Input 7 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 542doc 40543 | Input 8 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 544doc 40545 | Input 9 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 546doc 40547 | Input 10 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 548doc 40549 | Input 11 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 550doc 40551 | Input 12 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 552doc 40553 | Input 13 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 554doc 40555 | Input 14 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 556doc 40557 | Input 15 period | FLOAT32 | CDAB | ms | Read | |||
| HR | 558doc 40559 | Input 16 period | FLOAT32 | CDAB | ms | Read |
Notes on this map
- The protocol page lists function codes 01, 03, 05, 06, 15 and 16; the tables also give the digital inputs as 1x input status read with function 02. Modbus RTU runs on RS-485 and Modbus TCP serves up to 8 clients.
- Unlike some sibling R-series products, this table marks every 32-bit pair LSW first (counter 1 LSW at 40103, MSW at 40104), so counters and floats are CDAB.
- Factory settings from the manual: static IP 192.168.90.101/24, gateway 192.168.90.1, Modbus TCP port 502, station address 1; RS-485 38400 baud, 8 data bits, no parity, 1 stop bit, address 1.
- Left out: the command register 40017 (codes not listed for this product); the 32-bit integer low/high/period copies at 40201-40296, whose unit is printed as [ms*10] and is unclear; the consecutive copy block from 48001 (it repeats the values with integer timing in 50 us steps); float frequencies at 48331+.
- Coils 1-16 in the coil table mirror the inputs read-only and are not listed; use discrete inputs 10001-10016.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
What Modbus registers does the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) have?
This map lists 125 registers: 24 coils, 16 discrete inputs, 85 holding registers. 42 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Holding-register tables print the 4x number (40001) and the 0-based offset (0); coils print 1 / offset 0 and discrete inputs 10001 / offset 0. The offset is the wire address.
What byte order does the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)?
Start with HR 20 Digital inputs (Digital inputs); HR 22 Digital outputs (Digital outputs); HR 102 Counter 1 (Counter 1); HR 100 Counter reset (Counter reset bits); HR 528 Input 1 period (Input 1 period).
How do I enable Modbus control of the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)?
Modbus TCP server and RTU slave are on by default; configure through the web server or Seneca Discovery Device.
What happens when the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) loses Modbus communication?
Per the web-server chapter, an optional digital-output watchdog (default disabled, timeout default 5 s) sends the outputs to their fail state when no Modbus, USB or P2P traffic arrives within the timeout.
Where is the official Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) Modbus documentation?
The source is Series R I/O with protocol - User Manual (MI-00604-29-EN), revision 2026-09-03, published free by Seneca at https://www.seneca.it/media/6848135/mi00604-29-en.pdf.
More Seneca Modbus register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2 - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN
Other remote i/o modules register maps
- Sensor (remote I/O module)
Unipi Technology Unipi Extension xS51 I/O module
Unipi Extension xS51 RS-485 module per the Unipi Extension xS51 Modbus map v2.0.
Also known as: Unipi Extension xS51, xS51 - Sensor / remote I/O module
Brainboxes ED-538 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-538 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-538, ED538 - Sensor (remote I/O module)
Moxa ioLogik R1212 RS-485 remote I/O
ioLogik R1212 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1212, R1212, R1212-T - Sensor (Ethernet data logger / I/O module)
Teracom TCW220 Ethernet data logger
TCW220 per the Teracom TCW220 user manual Revision R4.24, firmware V2.012 or later.
Also known as: TCW220 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS54 universal analog input module
Unipi Extension xS54 RS-485 module per the Unipi Extension xS54 Modbus map v2.0.
Also known as: Unipi Extension xS54, xS54 - Sensor (counter/frequency input module)
ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
ICP DAS M-7080 and M-7080B two-channel 32-bit counter/frequency modules with two digital outputs, in Modbus RTU mode.
Also known as: M-7080, M-7080B, M7080, M7080B
All remote i/o modules Modbus register maps →
Source: Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.