Easy Modbus
  1. Home
  2. Modbus register maps
  3. Seneca
  4. R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)

Sensor (remote I/O module, digital inputs/outputs) · Modbus register map

Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) Modbus register map

Updated 17 November 2026

Short answer

The R-16DI-8DO is a Seneca R-series remote I/O with 16 digital inputs, each with a 32-bit counter and pulse timing, and 8 digital outputs. It serves Modbus TCP on two Ethernet ports and Modbus RTU on RS-485. This map covers the input and output words, counters and counter reset, low/high time and period floats, integer frequencies, and the coil/discrete-input views.

This page lists 125 Modbus registers for the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) — 42 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.

Manufacturer
Seneca
Model
R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
Equipment type
Sensor (remote I/O module, digital inputs/outputs)
Registers
125 (42 writable)
Transport
Modbus TCP, Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8N1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Also known as
R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO
Source document
Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)

Integration in brief

Read holding register 20 for all 16 inputs and write 22 for the 8 outputs (or use coils 32-39). Counters are 32-bit LSW-first pairs from 102; reset any of them through register 100 or coils 100-115.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 20Digital inputsBITMAP16Digital inputsRead
HR 22Digital outputsBITMAP16Digital outputsRead/write
HR 102Counter 1UINT32 CDABCounter 1Read/write
HR 100Counter resetBITMAP16Counter reset bitsRead/write
HR 528Input 1 periodFLOAT32 CDABInput 1 periodRead

Enable Modbus control & writes

Modbus TCP server and RTU slave are on by default; configure through the web server or Seneca Discovery Device.

Communication loss & watchdog

Per the web-server chapter, an optional digital-output watchdog (default disabled, timeout default 5 s) sends the outputs to their fail state when no Modbus, USB or P2P traffic arrives within the timeout.

Byte order & addressing

Network setup

Watch out for

Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

125 of 125 shown
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO32doc 33Digital output 1BITRead/write
CO33doc 34Digital output 2BITRead/write
CO34doc 35Digital output 3BITRead/write
CO35doc 36Digital output 4BITRead/write
CO36doc 37Digital output 5BITRead/write
CO37doc 38Digital output 6BITRead/write
CO38doc 39Digital output 7BITRead/write
CO39doc 40Digital output 8BITRead/write
CO100doc 101Counter 1 resetBITRead/write
CO101doc 102Counter 2 resetBITRead/write
CO102doc 103Counter 3 resetBITRead/write
CO103doc 104Counter 4 resetBITRead/write
CO104doc 105Counter 5 resetBITRead/write
CO105doc 106Counter 6 resetBITRead/write
CO106doc 107Counter 7 resetBITRead/write
CO107doc 108Counter 8 resetBITRead/write
CO108doc 109Counter 9 resetBITRead/write
CO109doc 110Counter 10 resetBITRead/write
CO110doc 111Counter 11 resetBITRead/write
CO111doc 112Counter 12 resetBITRead/write
CO112doc 113Counter 13 resetBITRead/write
CO113doc 114Counter 14 resetBITRead/write
CO114doc 115Counter 15 resetBITRead/write
CO115doc 116Counter 16 resetBITRead/write
DI0doc 10001Digital input 1BITRead
DI1doc 10002Digital input 2BITRead
DI2doc 10003Digital input 3BITRead
DI3doc 10004Digital input 4BITRead
DI4doc 10005Digital input 5BITRead
DI5doc 10006Digital input 6BITRead
DI6doc 10007Digital input 7BITRead
DI7doc 10008Digital input 8BITRead
DI8doc 10009Digital input 9BITRead
DI9doc 10010Digital input 10BITRead
DI10doc 10011Digital input 11BITRead
DI11doc 10012Digital input 12BITRead
DI12doc 10013Digital input 13BITRead
DI13doc 10014Digital input 14BITRead
DI14doc 10015Digital input 15BITRead
DI15doc 10016Digital input 16BITRead
HR0doc 40001Machine IDDevice identification code.UINT16Read
HR1doc 40002Firmware revisionUINT16Read
HR20doc 40021Digital inputsBit 0 = input 1 ... bit 15 = input 16.BITMAP16Readbit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4; bit 4 = Input 5; bit 5 = Input 6; bit 6 = Input 7; bit 7 = Input 8; bit 8 = Input 9; bit 9 = Input 10; bit 10 = Input 11; bit 11 = Input 12; bit 12 = Input 13; bit 13 = Input 14; bit 14 = Input 15; bit 15 = Input 16
HR22doc 40023Digital outputsBit 0 = output 1 ... bit 7 = output 8.BITMAP16Read/writebit 0 = Output 1; bit 1 = Output 2; bit 2 = Output 3; bit 3 = Output 4; bit 4 = Output 5; bit 5 = Output 6; bit 6 = Output 7; bit 7 = Output 8
HR100doc 40101Counter resetWrite a 1 in bit n-1 to reset counter n.BITMAP16Read/writebit 0 = Reset counter 1; bit 1 = Reset counter 2; bit 2 = Reset counter 3; bit 3 = Reset counter 4; bit 4 = Reset counter 5; bit 5 = Reset counter 6; bit 6 = Reset counter 7; bit 7 = Reset counter 8; bit 8 = Reset counter 9; bit 9 = Reset counter 10; bit 10 = Reset counter 11; bit 11 = Reset counter 12; bit 12 = Reset counter 13; bit 13 = Reset counter 14; bit 14 = Reset counter 15; bit 15 = Reset counter 16
HR102doc 40103Counter 1Digital input counter, LSW first.UINT32CDABRead/write
HR104doc 40105Counter 2Digital input counter, LSW first.UINT32CDABRead/write
HR106doc 40107Counter 3Digital input counter, LSW first.UINT32CDABRead/write
HR108doc 40109Counter 4Digital input counter, LSW first.UINT32CDABRead/write
HR110doc 40111Counter 5Digital input counter, LSW first.UINT32CDABRead/write
HR112doc 40113Counter 6Digital input counter, LSW first.UINT32CDABRead/write
HR114doc 40115Counter 7Digital input counter, LSW first.UINT32CDABRead/write
HR116doc 40117Counter 8Digital input counter, LSW first.UINT32CDABRead/write
HR118doc 40119Counter 9Digital input counter, LSW first.UINT32CDABRead/write
HR120doc 40121Counter 10Digital input counter, LSW first.UINT32CDABRead/write
HR122doc 40123Counter 11Digital input counter, LSW first.UINT32CDABRead/write
HR124doc 40125Counter 12Digital input counter, LSW first.UINT32CDABRead/write
HR126doc 40127Counter 13Digital input counter, LSW first.UINT32CDABRead/write
HR128doc 40129Counter 14Digital input counter, LSW first.UINT32CDABRead/write
HR130doc 40131Counter 15Digital input counter, LSW first.UINT32CDABRead/write
HR132doc 40133Counter 16Digital input counter, LSW first.UINT32CDABRead/write
HR296doc 40297Input 1 frequency (integer)UINT16HzRead
HR297doc 40298Input 2 frequency (integer)UINT16HzRead
HR298doc 40299Input 3 frequency (integer)UINT16HzRead
HR299doc 40300Input 4 frequency (integer)UINT16HzRead
HR300doc 40301Input 5 frequency (integer)UINT16HzRead
HR301doc 40302Input 6 frequency (integer)UINT16HzRead
HR302doc 40303Input 7 frequency (integer)UINT16HzRead
HR303doc 40304Input 8 frequency (integer)UINT16HzRead
HR304doc 40305Input 9 frequency (integer)UINT16HzRead
HR305doc 40306Input 10 frequency (integer)UINT16HzRead
HR306doc 40307Input 11 frequency (integer)UINT16HzRead
HR307doc 40308Input 12 frequency (integer)UINT16HzRead
HR308doc 40309Input 13 frequency (integer)UINT16HzRead
HR309doc 40310Input 14 frequency (integer)UINT16HzRead
HR310doc 40311Input 15 frequency (integer)UINT16HzRead
HR311doc 40312Input 16 frequency (integer)UINT16HzRead
HR400doc 40401Input 1 low timeFLOAT32CDABmsRead
HR402doc 40403Input 2 low timeFLOAT32CDABmsRead
HR404doc 40405Input 3 low timeFLOAT32CDABmsRead
HR406doc 40407Input 4 low timeFLOAT32CDABmsRead
HR408doc 40409Input 5 low timeFLOAT32CDABmsRead
HR410doc 40411Input 6 low timeFLOAT32CDABmsRead
HR412doc 40413Input 7 low timeFLOAT32CDABmsRead
HR414doc 40415Input 8 low timeFLOAT32CDABmsRead
HR416doc 40417Input 9 low timeFLOAT32CDABmsRead
HR418doc 40419Input 10 low timeFLOAT32CDABmsRead
HR420doc 40421Input 11 low timeFLOAT32CDABmsRead
HR422doc 40423Input 12 low timeFLOAT32CDABmsRead
HR424doc 40425Input 13 low timeFLOAT32CDABmsRead
HR426doc 40427Input 14 low timeFLOAT32CDABmsRead
HR428doc 40429Input 15 low timeFLOAT32CDABmsRead
HR430doc 40431Input 16 low timeFLOAT32CDABmsRead
HR464doc 40465Input 1 high timeFLOAT32CDABmsRead
HR466doc 40467Input 2 high timeFLOAT32CDABmsRead
HR468doc 40469Input 3 high timeFLOAT32CDABmsRead
HR470doc 40471Input 4 high timeFLOAT32CDABmsRead
HR472doc 40473Input 5 high timeFLOAT32CDABmsRead
HR474doc 40475Input 6 high timeFLOAT32CDABmsRead
HR476doc 40477Input 7 high timeFLOAT32CDABmsRead
HR478doc 40479Input 8 high timeFLOAT32CDABmsRead
HR480doc 40481Input 9 high timeFLOAT32CDABmsRead
HR482doc 40483Input 10 high timeFLOAT32CDABmsRead
HR484doc 40485Input 11 high timeFLOAT32CDABmsRead
HR486doc 40487Input 12 high timeFLOAT32CDABmsRead
HR488doc 40489Input 13 high timeFLOAT32CDABmsRead
HR490doc 40491Input 14 high timeFLOAT32CDABmsRead
HR492doc 40493Input 15 high timeFLOAT32CDABmsRead
HR494doc 40495Input 16 high timeFLOAT32CDABmsRead
HR528doc 40529Input 1 periodFLOAT32CDABmsRead
HR530doc 40531Input 2 periodFLOAT32CDABmsRead
HR532doc 40533Input 3 periodFLOAT32CDABmsRead
HR534doc 40535Input 4 periodFLOAT32CDABmsRead
HR536doc 40537Input 5 periodFLOAT32CDABmsRead
HR538doc 40539Input 6 periodFLOAT32CDABmsRead
HR540doc 40541Input 7 periodFLOAT32CDABmsRead
HR542doc 40543Input 8 periodFLOAT32CDABmsRead
HR544doc 40545Input 9 periodFLOAT32CDABmsRead
HR546doc 40547Input 10 periodFLOAT32CDABmsRead
HR548doc 40549Input 11 periodFLOAT32CDABmsRead
HR550doc 40551Input 12 periodFLOAT32CDABmsRead
HR552doc 40553Input 13 periodFLOAT32CDABmsRead
HR554doc 40555Input 14 periodFLOAT32CDABmsRead
HR556doc 40557Input 15 periodFLOAT32CDABmsRead
HR558doc 40559Input 16 periodFLOAT32CDABmsRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)

What Modbus registers does the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) have?

This map lists 125 registers: 24 coils, 16 discrete inputs, 85 holding registers. 42 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Holding-register tables print the 4x number (40001) and the 0-based offset (0); coils print 1 / offset 0 and discrete inputs 10001 / offset 0. The offset is the wire address.

What byte order does the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)?

Start with HR 20 Digital inputs (Digital inputs); HR 22 Digital outputs (Digital outputs); HR 102 Counter 1 (Counter 1); HR 100 Counter reset (Counter reset bits); HR 528 Input 1 period (Input 1 period).

How do I enable Modbus control of the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)?

Modbus TCP server and RTU slave are on by default; configure through the web server or Seneca Discovery Device.

What happens when the Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) loses Modbus communication?

Per the web-server chapter, an optional digital-output watchdog (default disabled, timeout default 5 s) sends the outputs to their fail state when no Modbus, USB or P2P traffic arrives within the timeout.

Where is the official Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs) Modbus documentation?

The source is Series R I/O with protocol - User Manual (MI-00604-29-EN), revision 2026-09-03, published free by Seneca at https://www.seneca.it/media/6848135/mi00604-29-en.pdf.

More Seneca Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.