Sensor (remote I/O module) · Modbus register map
Unipi Technology Unipi Extension xS51 I/O module Modbus register map
Updated 19 November 2026
The Unipi Extension xS51 is an RS-485 Modbus RTU extension module with 4 digital inputs, 5 relay outputs, 4 analog outputs (0-10 V) and 4 configurable analog inputs (voltage, current or resistance). The map covers I/O states, analog values, counters, the master watchdog and configuration.
This page lists 54 Modbus registers for the Unipi Technology Unipi Extension xS51 I/O module — 38 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Unipi Technology’s own free documentation (linked below) and checked against it.
- Manufacturer
- Unipi Technology
- Model
- Unipi Extension xS51 I/O module
- Equipment type
- Sensor (remote I/O module)
- Registers
- 54 (38 writable)
- Transport
- Modbus RTU
- Default unit ID
- 15
- Default serial
- 19200 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- Unipi Extension xS51, xS51
- Source document
- Extension xS51 Modbus map · v2.0
Integration notes: Unipi Technology Unipi Extension xS51 I/O module
Read digital inputs and relays as bit words at registers 0 and 1 (or as coils), analog inputs as CDAB floats from register 6, and write analog outputs as 0-4000 counts at registers 2-5.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Digital Inputs | BITMAP16 | Digital input states | Read |
| HR 1 | Relay Outputs | BITMAP16 | Relay output states | Read/write |
| HR 6 | Analog Input 1 | FLOAT32 CDAB | Analog input 1 | Read |
| HR 2 | Analog Output 1 (0..4000 ~ 0..10V) | UINT16 | Analog output 1 | Read/write |
| CO 0 | Relay Output 1 | BIT | Relay 1 | Read/write |
| HR 15 | Counter of Digital Input 1 | UINT32 CDAB | DI 1 counter | Read/write |
Enable Modbus control & writes
Modbus RTU is the native interface; nothing needs enabling. Factory settings are address 15, 19200 bps, 8N1.
Communication loss & watchdog
Master watchdog (MWD): enable it with the MWD Enable bit of the MWD status register and set the timeout in register 1008 (default 5000 ms). A watchdog reboot is flagged by the MWD Reboot Detected bit and coil 1000; the map does not describe the timeout behaviour further.
Byte order & addressing
- 32-bit values (floats, counters and the PCB serial number) are low word first (CDAB).
- Changes to RS-485 settings and other configuration need the Save configuration coil to survive a power cycle.
Network setup
- Set the address register (1024) and the packed RS-485 configuration register (1023), then write 1 to the save coil (1003) so the settings are used on startup.
Unipi Technology Unipi Extension xS51 I/O module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0x0000 | Relay Output 1 | Relay output state. | BIT | Read/write | ||||
| CO | 1doc 0x0001 | Relay Output 2 | Relay output state. | BIT | Read/write | ||||
| CO | 2doc 0x0002 | Relay Output 3 | Relay output state. | BIT | Read/write | ||||
| CO | 3doc 0x0003 | Relay Output 4 | Relay output state. | BIT | Read/write | ||||
| CO | 4doc 0x0004 | Relay Output 5 | Relay output state. | BIT | Read/write | ||||
| CO | 5doc 0x0005 | Digital Input 1 | Digital input state (read with FC01). | BIT | Read | ||||
| CO | 6doc 0x0006 | Digital Input 2 | Digital input state (read with FC01). | BIT | Read | ||||
| CO | 7doc 0x0007 | Digital Input 3 | Digital input state (read with FC01). | BIT | Read | ||||
| CO | 8doc 0x0008 | Digital Input 4 | Digital input state (read with FC01). | BIT | Read | ||||
| CO | 9doc 0x0009 | User Programmable LED 1 | BIT | Read/write | |||||
| CO | 10doc 0x000A | User Programmable LED 2 | BIT | Read/write | |||||
| CO | 11doc 0x000B | User Programmable LED 3 | BIT | Read/write | |||||
| CO | 1000doc 0x03E8 | MWD reset indication | Set when the master watchdog has reset the module. | BIT | Read/write | ||||
| CO | 1002doc 0x03EA | Reset group MCU | Write 1 to reset the module processor. | BIT | Write | ||||
| CO | 1003doc 0x03EB | Save current configuration and use on startup | Write 1 to store the current settings as power-up defaults. | BIT | Write | ||||
| HR | 0doc 0x0000 | Digital Inputs | BITMAP16 | Read | bit 0 = Digital Input 1; bit 1 = Digital Input 2; bit 2 = Digital Input 3; bit 3 = Digital Input 4 | ||||
| HR | 1doc 0x0001 | Relay Outputs | BITMAP16 | Read/write | bit 0 = Relay Output 1; bit 1 = Relay Output 2; bit 2 = Relay Output 3; bit 3 = Relay Output 4; bit 4 = Relay Output 5 | ||||
| HR | 2doc 0x0002 | Analog Output 1 (0..4000 ~ 0..10V) | Analog output, 0-4000 counts = 0-10 V. | UINT16 | × 0.0025 | V | Read/write | ||
| HR | 3doc 0x0003 | Analog Output 2 (0..4000 ~ 0..10V) | Analog output, 0-4000 counts = 0-10 V. | UINT16 | × 0.0025 | V | Read/write | ||
| HR | 4doc 0x0004 | Analog Output 3 (0..4000 ~ 0..10V) | Analog output, 0-4000 counts = 0-10 V. | UINT16 | × 0.0025 | V | Read/write | ||
| HR | 5doc 0x0005 | Analog Output 4 (0..4000 ~ 0..10V) | Analog output, 0-4000 counts = 0-10 V. | UINT16 | × 0.0025 | V | Read/write | ||
| HR | 6doc 0x0006 | Analog Input 1 | Analog input reading (float); unit not stated in the map. | FLOAT32 | CDAB | Read | |||
| HR | 8doc 0x0008 | Analog Input 2 | Analog input reading (float); unit not stated in the map. | FLOAT32 | CDAB | Read | |||
| HR | 10doc 0x000A | Analog Input 3 | Analog input reading (float); unit not stated in the map. | FLOAT32 | CDAB | Read | |||
| HR | 12doc 0x000C | Analog Input 4 | Analog input reading (float); unit not stated in the map. | FLOAT32 | CDAB | Read | |||
| HR | 14doc 0x000E | Group MasterWatchDog (MWD) Status | BITMAP16 | Read/write | bit 0 = MWD Enable; bit 1 = MWD Reboot Detected | ||||
| HR | 15doc 0x000F | Counter of Digital Input 1 | Pulse counter for this input; writable to preset. | UINT32 | CDAB | Read/write | |||
| HR | 17doc 0x0011 | Counter of Digital Input 2 | Pulse counter for this input; writable to preset. | UINT32 | CDAB | Read/write | |||
| HR | 19doc 0x0013 | Counter of Digital Input 3 | Pulse counter for this input; writable to preset. | UINT32 | CDAB | Read/write | |||
| HR | 21doc 0x0015 | Counter of Digital Input 4 | Pulse counter for this input; writable to preset. | UINT32 | CDAB | Read/write | |||
| HR | 27doc 0x001B | User-programmable LED states | BITMAP16 | Read/write | bit 0 = User LED 1; bit 1 = User LED 2; bit 2 = User LED 3 | ||||
| HR | 28doc 0x001C | Synchronised Relay Outputs | BITMAP16 | Read/write | bit 0 = Synchronised RO 1; bit 1 = Synchronised RO 2; bit 2 = Synchronised RO 3; bit 3 = Synchronised RO 4; bit 4 = Synchronised RO 5 | ||||
| HR | 29doc 0x001D | Synchronised Relay Output Locks | BITMAP16 | Read/write | bit 0 = Synchronised RO Lock 1; bit 1 = Synchronised RO Lock 2; bit 2 = Synchronised RO Lock 3; bit 3 = Synchronised RO Lock 4; bit 4 = Synchronised RO Lock 5 | ||||
| HR | 1000doc 0x03E8 | Firmware Version | UINT16 | Read | |||||
| HR | 1001doc 0x03E9 | Number of I/Os | Packed counts: bits 0-7 DOs, bits 8-15 DIs. | UINT16 | Read | ||||
| HR | 1002doc 0x03EA | Number of peripherals | Packed counts: bits 0-3 RS485 lines, bits 4-7 AOs, bits 8-15 AIs. | UINT16 | Read | ||||
| HR | 1003doc 0x03EB | Firmware ID | UINT16 | Read | |||||
| HR | 1004doc 0x03EC | Hardware ID | UINT16 | Read | |||||
| HR | 1005doc 0x03ED | PCB Serial Number | UINT32 | CDAB | Read | ||||
| HR | 1008doc 0x03F0 | MasterWatchDog (MWD) Timeout (in 1ms) | Master watchdog timeout; default 5000 ms. | UINT16 | ms | Read/write | |||
| HR | 1009doc 0x03F1 | VRef of MCU | UINT16 | Read | |||||
| HR | 1010doc 0x03F2 | Debounce time (in 100us) for DI 1 | Input debounce time in 100 us steps. | UINT16 | × 0.1 | ms | Read/write | ||
| HR | 1011doc 0x03F3 | Debounce time (in 100us) for DI 2 | Input debounce time in 100 us steps. | UINT16 | × 0.1 | ms | Read/write | ||
| HR | 1012doc 0x03F4 | Debounce time (in 100us) for DI 3 | Input debounce time in 100 us steps. | UINT16 | × 0.1 | ms | Read/write | ||
| HR | 1013doc 0x03F5 | Debounce time (in 100us) for DI 4 | Input debounce time in 100 us steps. | UINT16 | × 0.1 | ms | Read/write | ||
| HR | 1014doc 0x03F6 | Enable DirectSwitch functionality | BITMAP16 | Read/write | bit 0 = Enable DirectSwitch on DI 1; bit 1 = Enable DirectSwitch on DI 2; bit 2 = Enable DirectSwitch on DI 3; bit 3 = Enable DirectSwitch on DI 4 | ||||
| HR | 1015doc 0x03F7 | Invert DirectSwitch Polarity | BITMAP16 | Read/write | bit 0 = Invert DirectSwitch Polarity on DI 1; bit 1 = Invert DirectSwitch Polarity on DI 2; bit 2 = Invert DirectSwitch Polarity on DI 3; bit 3 = Invert DirectSwitch Polarity on DI 4 | ||||
| HR | 1016doc 0x03F8 | Enabled DirectSwitch Toggle | BITMAP16 | Read/write | bit 0 = Enable DirectSwitch Toggle on DI 1; bit 1 = Enable DirectSwitch Toggle on DI 2; bit 2 = Enable DirectSwitch Toggle on DI 3; bit 3 = Enable DirectSwitch Toggle on DI 4 | ||||
| HR | 1019doc 0x03FB | Configuration(U/I/R) of Analog Input 1 | Measurement type for this analog input. | UINT16 | Read/write | 0 = OFF; 1 = Voltage 0-10 V; 2 = Voltage 0-2.5 V; 3 = Current 0-20 mA; 4 = Resistance 0-1960 ohm; 5 = Resistance 0-100 kohm | |||
| HR | 1020doc 0x03FC | Configuration(U/I/R) of Analog Input 2 | Measurement type for this analog input. | UINT16 | Read/write | 0 = OFF; 1 = Voltage 0-10 V; 2 = Voltage 0-2.5 V; 3 = Current 0-20 mA; 4 = Resistance 0-1960 ohm; 5 = Resistance 0-100 kohm | |||
| HR | 1021doc 0x03FD | Configuration(U/I/R) of Analog Input 3 | Measurement type for this analog input. | UINT16 | Read/write | 0 = OFF; 1 = Voltage 0-10 V; 2 = Voltage 0-2.5 V; 3 = Current 0-20 mA; 4 = Resistance 0-1960 ohm; 5 = Resistance 0-100 kohm | |||
| HR | 1022doc 0x03FE | Configuration(U/I/R) of Analog Input 4 | Measurement type for this analog input. | UINT16 | Read/write | 0 = OFF; 1 = Voltage 0-10 V; 2 = Voltage 0-2.5 V; 3 = Current 0-20 mA; 4 = Resistance 0-1960 ohm; 5 = Resistance 0-100 kohm | |||
| HR | 1023doc 0x03FF | RS485 Configuration - see Description sheet | Bits 0-12 baud code, bit 13 parity on, bit 14 odd parity; default 14 (19200 8N1). | UINT16 | Read/write | ||||
| HR | 1024doc 0x0400 | Modbus Address Configuration (1-254) | Modbus RTU slave address (default 15). | UINT16 | Read/write |
Notes on this map
- Word order: the description sheet states 16-bit values are big endian (AB) and 32-bit values are mid-little endian (CDAB, low word first).
- Registers marked Reserved - Do Not Use are left out.
- Baud codes for the RS-485 configuration register: 11 = 2400, 12 = 4800, 13 = 9600, 14 = 19200, 15 = 38400, 4097 = 57600, 4098 = 115200 bps.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Unipi Technology Unipi Extension xS51 I/O module
What Modbus registers does the Unipi Technology Unipi Extension xS51 I/O module have?
This map lists 54 registers: 15 coils, 39 holding registers. 38 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Unipi Technology Unipi Extension xS51 I/O module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map lists each register in decimal and hex starting at 0; the number is the wire address.
What byte order does the Unipi Technology Unipi Extension xS51 I/O module use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Unipi Technology Unipi Extension xS51 I/O module?
Start with HR 0 Digital Inputs (Digital input states); HR 1 Relay Outputs (Relay output states); HR 6 Analog Input 1 (Analog input 1); HR 2 Analog Output 1 (0..4000 ~ 0..10V) (Analog output 1); CO 0 Relay Output 1 (Relay 1); HR 15 Counter of Digital Input 1 (DI 1 counter).
How do I enable Modbus control of the Unipi Technology Unipi Extension xS51 I/O module?
Modbus RTU is the native interface; nothing needs enabling. Factory settings are address 15, 19200 bps, 8N1.
What happens when the Unipi Technology Unipi Extension xS51 I/O module loses Modbus communication?
Master watchdog (MWD): enable it with the MWD Enable bit of the MWD status register and set the timeout in register 1008 (default 5000 ms). A watchdog reboot is flagged by the MWD Reboot Detected bit and coil 1000; the map does not describe the timeout behaviour further.
Where is the official Unipi Technology Unipi Extension xS51 I/O module Modbus documentation?
The source is Extension xS51 Modbus map (v2.0), published free by Unipi Technology at https://kb.unipi.technology/_media/files:products:extensions:unipi-extension-xs51-modbus-map-v2.0.pdf.
More Unipi Technology Modbus register maps
- Boiler gateway (OpenTherm to Modbus RTU)
Unipi Technology MM-OT101 Modbus / OpenTherm gateway
Unipi MM-OT101 DIN-rail gateway between Modbus RTU (RS-485) and OpenTherm/Plus boilers and thermostats, per its technical documentation.
Also known as: MM-OT101, MM-OT1010, Unipi OpenTherm gateway - Sensor (1-Wire temperature gateway)
Unipi Technology Unipi Extension xG18 1-Wire temperature gateway
Unipi Extension xG18 RS-485 module per the Unipi Extension xG18 Modbus map v1.1.
Also known as: Unipi Extension xG18, xG18 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS11 I/O module
Unipi Extension xS11 RS-485 module per the Unipi Extension xS11 Modbus map v2.0.
Also known as: Unipi Extension xS11, xS11 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS52 resistance input module
Unipi Extension xS52 RS-485 module per the Unipi Extension xS52 Modbus map v2.0.
Also known as: Unipi Extension xS52, xS52 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS53 analog input module
Unipi Extension xS53 RS-485 module per the Unipi Extension xS53 Modbus map v2.0.
Also known as: Unipi Extension xS53, xS53 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS54 universal analog input module
Unipi Extension xS54 RS-485 module per the Unipi Extension xS54 Modbus map v2.0.
Also known as: Unipi Extension xS54, xS54
Other remote i/o modules register maps
- Sensor / remote I/O module
Brainboxes ED-538 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-538 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-538, ED538 - Sensor (remote I/O module)
Moxa ioLogik R1212 RS-485 remote I/O
ioLogik R1212 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1212, R1212, R1212-T - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD - Sensor (Ethernet data logger / I/O module)
Teracom TCW220 Ethernet data logger
TCW220 per the Teracom TCW220 user manual Revision R4.24, firmware V2.012 or later.
Also known as: TCW220 - Sensor (counter/frequency input module)
ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
ICP DAS M-7080 and M-7080B two-channel 32-bit counter/frequency modules with two digital outputs, in Modbus RTU mode.
Also known as: M-7080, M-7080B, M7080, M7080B - Sensor (remote I/O module)
Moxa ioLogik R1241 RS-485 remote I/O
ioLogik R1241 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1241, R1241, R1241-T
All remote i/o modules Modbus register maps →
Source: Extension xS51 Modbus map · v2.0. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.