Short answer

The ioLogik R1212 is a Moxa RS-485 Modbus RTU remote I/O module with 8 digital inputs plus 8 configurable DIO channels with pulse output. It supports a repeater or dual RS-485 mode and a Modbus host-connection watchdog with safe-mode output states. This map covers the shared system registers (model, watchdog, serial settings) and the DI, DIO and DO pulse channels.

This page lists 312 Modbus registers for the Moxa ioLogik R1212 RS-485 remote I/O — 243 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Moxa’s own free documentation (linked below) and checked against it.

Manufacturer
Moxa
Model
ioLogik R1212 RS-485 remote I/O
Equipment type
Sensor (remote I/O module)
Registers
312 (243 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Also known as
ioLogik R1212, R1212, R1212-T
Source document
ioLogik R1200 Series User's Manual · Edition 3.4 · rev. 2021-04 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Moxa ioLogik R1212 RS-485 remote I/O

Integration in brief

Poll the I/O block with the function code shown for each register (01/02 for bits, 03/04 for words). Enable the Modbus watchdog (0x7564, timeout 0x7565) so outputs and counters fall back to their safe-mode settings if the master stops polling.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 30000SYS_modelIDUINT16Model ID checkRead
HR 30052SYS_modbusWatchdogFuntionUINT16Enable communication watchdogRead/write
HR 30053SYS_modbusWatchdogTimeoutUINT16Watchdog timeoutRead/write
DI 0DI-00_statusBITFirst digital inputRead
IR 32DI-00_counterValueUINT32 ABCDFirst counter valueRead
CO 320DO-00_statusBITFirst output on/offRead/write

Enable Modbus control & writes

Set the device ID (1-99) on the two rotary dials. Put the Initial/Run switch on Initial to configure the unit at 9600 baud, no parity, 8 data bits, 1 stop bit (with ioSearch or the SYS_port* registers), then switch back to Run.

Communication loss & watchdog

SYS_modbusWatchdogFuntion (0x7564) enables the host-connection watchdog, SYS_modbusWatchdogTimeout (0x7565) sets the timeout in seconds (factory default 10 s), SYS_modbusWatchdogStatus (0x7566) shows a timeout. It is disabled by default; safe-status settings only act when it is enabled.

Byte order & addressing

Network setup

Watch out for

Moxa ioLogik R1212 RS-485 remote I/O Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

312 of 312 shown
Moxa ioLogik R1212 RS-485 remote I/O Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 0x0000DI-00_counterStatusBITRead/write0 = STOP; 1 = START
CO1doc 0x0001DI-01_counterStatusBITRead/write0 = STOP; 1 = START
CO2doc 0x0002DI-02_counterStatusBITRead/write0 = STOP; 1 = START
CO3doc 0x0003DI-03_counterStatusBITRead/write0 = STOP; 1 = START
CO4doc 0x0004DI-04_counterStatusBITRead/write0 = STOP; 1 = START
CO5doc 0x0005DI-05_counterStatusBITRead/write0 = STOP; 1 = START
CO6doc 0x0006DI-06_counterStatusBITRead/write0 = STOP; 1 = START
CO7doc 0x0007DI-07_counterStatusBITRead/write0 = STOP; 1 = START
CO8doc 0x0008DI-08_counterStatusBITRead/write0 = STOP; 1 = START
CO9doc 0x0009DI-09_counterStatusBITRead/write0 = STOP; 1 = START
CO10doc 0x000ADI-10_counterStatusBITRead/write0 = STOP; 1 = START
CO11doc 0x000BDI-11_counterStatusBITRead/write0 = STOP; 1 = START
CO12doc 0x000CDI-12_counterStatusBITRead/write0 = STOP; 1 = START
CO13doc 0x000DDI-13_counterStatusBITRead/write0 = STOP; 1 = START
CO14doc 0x000EDI-14_counterStatusBITRead/write0 = STOP; 1 = START
CO15doc 0x000FDI-15_counterStatusBITRead/write0 = STOP; 1 = START
CO32doc 0x0020DI-00_counterResetBITRead/write1 = reset to initial value
CO33doc 0x0021DI-01_counterResetBITRead/write1 = reset to initial value
CO34doc 0x0022DI-02_counterResetBITRead/write1 = reset to initial value
CO35doc 0x0023DI-03_counterResetBITRead/write1 = reset to initial value
CO36doc 0x0024DI-04_counterResetBITRead/write1 = reset to initial value
CO37doc 0x0025DI-05_counterResetBITRead/write1 = reset to initial value
CO38doc 0x0026DI-06_counterResetBITRead/write1 = reset to initial value
CO39doc 0x0027DI-07_counterResetBITRead/write1 = reset to initial value
CO40doc 0x0028DI-08_counterResetBITRead/write1 = reset to initial value
CO41doc 0x0029DI-09_counterResetBITRead/write1 = reset to initial value
CO42doc 0x002ADI-10_counterResetBITRead/write1 = reset to initial value
CO43doc 0x002BDI-11_counterResetBITRead/write1 = reset to initial value
CO44doc 0x002CDI-12_counterResetBITRead/write1 = reset to initial value
CO45doc 0x002DDI-13_counterResetBITRead/write1 = reset to initial value
CO46doc 0x002EDI-14_counterResetBITRead/write1 = reset to initial value
CO47doc 0x002FDI-15_counterResetBITRead/write1 = reset to initial value
CO64doc 0x0040DI-00_counterOverflowFlagBITRead/write1 = clear overflow flag
CO65doc 0x0041DI-01_counterOverflowFlagBITRead/write1 = clear overflow flag
CO66doc 0x0042DI-02_counterOverflowFlagBITRead/write1 = clear overflow flag
CO67doc 0x0043DI-03_counterOverflowFlagBITRead/write1 = clear overflow flag
CO68doc 0x0044DI-04_counterOverflowFlagBITRead/write1 = clear overflow flag
CO69doc 0x0045DI-05_counterOverflowFlagBITRead/write1 = clear overflow flag
CO70doc 0x0046DI-06_counterOverflowFlagBITRead/write1 = clear overflow flag
CO71doc 0x0047DI-07_counterOverflowFlagBITRead/write1 = clear overflow flag
CO72doc 0x0048DI-08_counterOverflowFlagBITRead/write1 = clear overflow flag
CO73doc 0x0049DI-09_counterOverflowFlagBITRead/write1 = clear overflow flag
CO74doc 0x004ADI-10_counterOverflowFlagBITRead/write1 = clear overflow flag
CO75doc 0x004BDI-11_counterOverflowFlagBITRead/write1 = clear overflow flag
CO76doc 0x004CDI-12_counterOverflowFlagBITRead/write1 = clear overflow flag
CO77doc 0x004DDI-13_counterOverflowFlagBITRead/write1 = clear overflow flag
CO78doc 0x004EDI-14_counterOverflowFlagBITRead/write1 = clear overflow flag
CO79doc 0x004FDI-15_counterOverflowFlagBITRead/write1 = clear overflow flag
CO96doc 0x0060DI-00_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO97doc 0x0061DI-01_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO98doc 0x0062DI-02_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO99doc 0x0063DI-03_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO100doc 0x0064DI-04_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO101doc 0x0065DI-05_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO102doc 0x0066DI-06_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO103doc 0x0067DI-07_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO104doc 0x0068DI-08_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO105doc 0x0069DI-09_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO106doc 0x006ADI-10_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO107doc 0x006BDI-11_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO108doc 0x006CDI-12_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO109doc 0x006DDI-13_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO110doc 0x006EDI-14_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO111doc 0x006FDI-15_counterPowerOnStatusBITRead/write0 = STOP; 1 = START
CO128doc 0x0080DI-00_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO129doc 0x0081DI-01_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO130doc 0x0082DI-02_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO131doc 0x0083DI-03_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO132doc 0x0084DI-04_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO133doc 0x0085DI-05_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO134doc 0x0086DI-06_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO135doc 0x0087DI-07_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO136doc 0x0088DI-08_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO137doc 0x0089DI-09_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO138doc 0x008ADI-10_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO139doc 0x008BDI-11_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO140doc 0x008CDI-12_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO141doc 0x008DDI-13_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO142doc 0x008EDI-14_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO143doc 0x008FDI-15_counterSafeModeStatusBITRead/write0 = STOP; 1 = START
CO160doc 0x00A0DI-00_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO161doc 0x00A1DI-01_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO162doc 0x00A2DI-02_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO163doc 0x00A3DI-03_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO164doc 0x00A4DI-04_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO165doc 0x00A5DI-05_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO166doc 0x00A6DI-06_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO167doc 0x00A7DI-07_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO168doc 0x00A8DI-08_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO169doc 0x00A9DI-09_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO170doc 0x00AADI-10_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO171doc 0x00ABDI-11_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO172doc 0x00ACDI-12_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO173doc 0x00ADDI-13_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO174doc 0x00AEDI-14_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO175doc 0x00AFDI-15_counterPowerOffStorageBITRead/write0 = Disable; 1 = Enable
CO320doc 0x0140DO-00_statusBITRead/write0 = OFF; 1 = ON
CO321doc 0x0141DO-01_statusBITRead/write0 = OFF; 1 = ON
CO322doc 0x0142DO-02_statusBITRead/write0 = OFF; 1 = ON
CO323doc 0x0143DO-03_statusBITRead/write0 = OFF; 1 = ON
CO324doc 0x0144DO-04_statusBITRead/write0 = OFF; 1 = ON
CO325doc 0x0145DO-05_statusBITRead/write0 = OFF; 1 = ON
CO326doc 0x0146DO-06_statusBITRead/write0 = OFF; 1 = ON
CO327doc 0x0147DO-07_statusBITRead/write0 = OFF; 1 = ON
CO352doc 0x0160DO-00_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO353doc 0x0161DO-01_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO354doc 0x0162DO-02_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO355doc 0x0163DO-03_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO356doc 0x0164DO-04_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO357doc 0x0165DO-05_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO358doc 0x0166DO-06_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO359doc 0x0167DO-07_powerOnStatusBITRead/write0 = OFF; 1 = ON
CO384doc 0x0180DO-00_pulseStatusBITRead/write0 = STOP; 1 = START
CO385doc 0x0181DO-01_pulseStatusBITRead/write0 = STOP; 1 = START
CO386doc 0x0182DO-02_pulseStatusBITRead/write0 = STOP; 1 = START
CO387doc 0x0183DO-03_pulseStatusBITRead/write0 = STOP; 1 = START
CO388doc 0x0184DO-04_pulseStatusBITRead/write0 = STOP; 1 = START
CO389doc 0x0185DO-05_pulseStatusBITRead/write0 = STOP; 1 = START
CO390doc 0x0186DO-06_pulseStatusBITRead/write0 = STOP; 1 = START
CO391doc 0x0187DO-07_pulseStatusBITRead/write0 = STOP; 1 = START
CO416doc 0x01A0DO-00_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO417doc 0x01A1DO-01_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO418doc 0x01A2DO-02_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO419doc 0x01A3DO-03_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO420doc 0x01A4DO-04_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO421doc 0x01A5DO-05_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO422doc 0x01A6DO-06_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO423doc 0x01A7DO-07_pulsePowerOnStatusBITRead/write0 = STOP; 1 = START
CO448doc 0x01C0DO-00_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO449doc 0x01C1DO-01_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO450doc 0x01C2DO-02_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO451doc 0x01C3DO-03_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO452doc 0x01C4DO-04_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO453doc 0x01C5DO-05_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO454doc 0x01C6DO-06_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
CO455doc 0x01C7DO-07_pulseSafeModeStatusBITRead/write0 = STOP; 1 = START
DI0doc 0x0000DI-00_statusBITRead0 = OFF; 1 = ON
DI1doc 0x0001DI-01_statusBITRead0 = OFF; 1 = ON
DI2doc 0x0002DI-02_statusBITRead0 = OFF; 1 = ON
DI3doc 0x0003DI-03_statusBITRead0 = OFF; 1 = ON
DI4doc 0x0004DI-04_statusBITRead0 = OFF; 1 = ON
DI5doc 0x0005DI-05_statusBITRead0 = OFF; 1 = ON
DI6doc 0x0006DI-06_statusBITRead0 = OFF; 1 = ON
DI7doc 0x0007DI-07_statusBITRead0 = OFF; 1 = ON
DI8doc 0x0008DI-08_statusBITRead0 = OFF; 1 = ON
DI9doc 0x0009DI-09_statusBITRead0 = OFF; 1 = ON
DI10doc 0x000ADI-10_statusBITRead0 = OFF; 1 = ON
DI11doc 0x000BDI-11_statusBITRead0 = OFF; 1 = ON
DI12doc 0x000CDI-12_statusBITRead0 = OFF; 1 = ON
DI13doc 0x000DDI-13_statusBITRead0 = OFF; 1 = ON
DI14doc 0x000EDI-14_statusBITRead0 = OFF; 1 = ON
DI15doc 0x000FDI-15_statusBITRead0 = OFF; 1 = ON
DI10288doc 0x2830DIO-00_modeBITRead0 = DI; 1 = DO
DI10289doc 0x2831DIO-01_modeBITRead0 = DI; 1 = DO
DI10290doc 0x2832DIO-02_modeBITRead0 = DI; 1 = DO
DI10291doc 0x2833DIO-03_modeBITRead0 = DI; 1 = DO
DI10292doc 0x2834DIO-04_modeBITRead0 = DI; 1 = DO
DI10293doc 0x2835DIO-05_modeBITRead0 = DI; 1 = DO
DI10294doc 0x2836DIO-06_modeBITRead0 = DI; 1 = DO
DI10295doc 0x2837DIO-07_modeBITRead0 = DI; 1 = DO
IR0doc 0x0000DI-00_statusUINT16Read0 = OFF; 1 = ON
IR1doc 0x0001DI-01_statusUINT16Read0 = OFF; 1 = ON
IR2doc 0x0002DI-02_statusUINT16Read0 = OFF; 1 = ON
IR3doc 0x0003DI-03_statusUINT16Read0 = OFF; 1 = ON
IR4doc 0x0004DI-04_statusUINT16Read0 = OFF; 1 = ON
IR5doc 0x0005DI-05_statusUINT16Read0 = OFF; 1 = ON
IR6doc 0x0006DI-06_statusUINT16Read0 = OFF; 1 = ON
IR7doc 0x0007DI-07_statusUINT16Read0 = OFF; 1 = ON
IR8doc 0x0008DI-08_statusUINT16Read0 = OFF; 1 = ON
IR9doc 0x0009DI-09_statusUINT16Read0 = OFF; 1 = ON
IR10doc 0x000ADI-10_statusUINT16Read0 = OFF; 1 = ON
IR11doc 0x000BDI-11_statusUINT16Read0 = OFF; 1 = ON
IR12doc 0x000CDI-12_statusUINT16Read0 = OFF; 1 = ON
IR13doc 0x000DDI-13_statusUINT16Read0 = OFF; 1 = ON
IR14doc 0x000EDI-14_statusUINT16Read0 = OFF; 1 = ON
IR15doc 0x000FDI-15_statusUINT16Read0 = OFF; 1 = ON
IR32doc 0x0020DI-00_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR34doc 0x0022DI-01_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR36doc 0x0024DI-02_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR38doc 0x0026DI-03_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR40doc 0x0028DI-04_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR42doc 0x002ADI-05_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR44doc 0x002CDI-06_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR46doc 0x002EDI-07_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR48doc 0x0030DI-08_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR50doc 0x0032DI-09_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR52doc 0x0034DI-10_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR54doc 0x0036DI-11_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR56doc 0x0038DI-12_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR58doc 0x003ADI-13_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR60doc 0x003CDI-14_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR62doc 0x003EDI-15_counterValueHigh word at this address, low word next.UINT32ABCDRead
IR288doc 0x0120DIO-00_modeUINT16Read0 = DI; 1 = DO
IR289doc 0x0121DIO-01_modeUINT16Read0 = DI; 1 = DO
IR290doc 0x0122DIO-02_modeUINT16Read0 = DI; 1 = DO
IR291doc 0x0123DIO-03_modeUINT16Read0 = DI; 1 = DO
IR292doc 0x0124DIO-04_modeUINT16Read0 = DI; 1 = DO
IR293doc 0x0125DIO-05_modeUINT16Read0 = DI; 1 = DO
IR294doc 0x0126DIO-06_modeUINT16Read0 = DI; 1 = DO
IR295doc 0x0127DIO-07_modeUINT16Read0 = DI; 1 = DO
IR30000doc 0x7530SYS_modelIDUINT16Read
IR30025doc 0x7549SYS_vendorIDUINT16Read
IR30026doc 0x754ASYS_unitIDUINT16Read
IR30037doc 0x7555SYS_productNameSTRING[20]Read
IR30058doc 0x756ASYS_rs485PortModeUINT16Read0 = initial-repeater; 1 = initial-dual RS- 485; 2 = run-repeater; 3 = run-dual RS-485
HR0doc 0x0000DI-00_modeUINT16Read/write0 = DI; 1 = Counter
HR1doc 0x0001DI-01_modeUINT16Read/write0 = DI; 1 = Counter
HR2doc 0x0002DI-02_modeUINT16Read/write0 = DI; 1 = Counter
HR3doc 0x0003DI-03_modeUINT16Read/write0 = DI; 1 = Counter
HR4doc 0x0004DI-04_modeUINT16Read/write0 = DI; 1 = Counter
HR5doc 0x0005DI-05_modeUINT16Read/write0 = DI; 1 = Counter
HR6doc 0x0006DI-06_modeUINT16Read/write0 = DI; 1 = Counter
HR7doc 0x0007DI-07_modeUINT16Read/write0 = DI; 1 = Counter
HR8doc 0x0008DI-08_modeUINT16Read/write0 = DI; 1 = Counter
HR9doc 0x0009DI-09_modeUINT16Read/write0 = DI; 1 = Counter
HR10doc 0x000ADI-10_modeUINT16Read/write0 = DI; 1 = Counter
HR11doc 0x000BDI-11_modeUINT16Read/write0 = DI; 1 = Counter
HR12doc 0x000CDI-12_modeUINT16Read/write0 = DI; 1 = Counter
HR13doc 0x000DDI-13_modeUINT16Read/write0 = DI; 1 = Counter
HR14doc 0x000EDI-14_modeUINT16Read/write0 = DI; 1 = Counter
HR15doc 0x000FDI-15_modeUINT16Read/write0 = DI; 1 = Counter
HR32doc 0x0020DI-00_filterUINT16× 100µsRead/write
HR33doc 0x0021DI-01_filterUINT16× 100µsRead/write
HR34doc 0x0022DI-02_filterUINT16× 100µsRead/write
HR35doc 0x0023DI-03_filterUINT16× 100µsRead/write
HR36doc 0x0024DI-04_filterUINT16× 100µsRead/write
HR37doc 0x0025DI-05_filterUINT16× 100µsRead/write
HR38doc 0x0026DI-06_filterUINT16× 100µsRead/write
HR39doc 0x0027DI-07_filterUINT16× 100µsRead/write
HR40doc 0x0028DI-08_filterUINT16× 100µsRead/write
HR41doc 0x0029DI-09_filterUINT16× 100µsRead/write
HR42doc 0x002ADI-10_filterUINT16× 100µsRead/write
HR43doc 0x002BDI-11_filterUINT16× 100µsRead/write
HR44doc 0x002CDI-12_filterUINT16× 100µsRead/write
HR45doc 0x002DDI-13_filterUINT16× 100µsRead/write
HR46doc 0x002EDI-14_filterUINT16× 100µsRead/write
HR47doc 0x002FDI-15_filterUINT16× 100µsRead/write
HR64doc 0x0040DI-00_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR65doc 0x0041DI-01_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR66doc 0x0042DI-02_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR67doc 0x0043DI-03_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR68doc 0x0044DI-04_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR69doc 0x0045DI-05_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR70doc 0x0046DI-06_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR71doc 0x0047DI-07_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR72doc 0x0048DI-08_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR73doc 0x0049DI-09_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR74doc 0x004ADI-10_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR75doc 0x004BDI-11_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR76doc 0x004CDI-12_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR77doc 0x004DDI-13_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR78doc 0x004EDI-14_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR79doc 0x004FDI-15_counterEventUINT16Read/write0 = Rising Edge; 1 = Falling Edge; 2 = Both
HR320doc 0x0140DO-00_statusUINT16Read/write0 = OFF; 1 = ON
HR321doc 0x0141DO-01_statusUINT16Read/write0 = OFF; 1 = ON
HR322doc 0x0142DO-02_statusUINT16Read/write0 = OFF; 1 = ON
HR323doc 0x0143DO-03_statusUINT16Read/write0 = OFF; 1 = ON
HR324doc 0x0144DO-04_statusUINT16Read/write0 = OFF; 1 = ON
HR325doc 0x0145DO-05_statusUINT16Read/write0 = OFF; 1 = ON
HR326doc 0x0146DO-06_statusUINT16Read/write0 = OFF; 1 = ON
HR327doc 0x0147DO-07_statusUINT16Read/write0 = OFF; 1 = ON
HR352doc 0x0160DO-00_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR354doc 0x0162DO-01_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR356doc 0x0164DO-02_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR358doc 0x0166DO-03_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR360doc 0x0168DO-04_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR362doc 0x016ADO-05_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR364doc 0x016CDO-06_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR366doc 0x016EDO-07_pulseCountHigh word at this address, low word next.UINT32ABCDRead/write
HR416doc 0x01A0DO-00_pulseOnWidthUINT16msRead/write
HR417doc 0x01A1DO-01_pulseOnWidthUINT16msRead/write
HR418doc 0x01A2DO-02_pulseOnWidthUINT16msRead/write
HR419doc 0x01A3DO-03_pulseOnWidthUINT16msRead/write
HR420doc 0x01A4DO-04_pulseOnWidthUINT16msRead/write
HR421doc 0x01A5DO-05_pulseOnWidthUINT16msRead/write
HR422doc 0x01A6DO-06_pulseOnWidthUINT16msRead/write
HR423doc 0x01A7DO-07_pulseOnWidthUINT16msRead/write
HR448doc 0x01C0DO-00_pulseOffWidthUINT16msRead/write
HR449doc 0x01C1DO-01_pulseOffWidthUINT16msRead/write
HR450doc 0x01C2DO-02_pulseOffWidthUINT16msRead/write
HR451doc 0x01C3DO-03_pulseOffWidthUINT16msRead/write
HR452doc 0x01C4DO-04_pulseOffWidthUINT16msRead/write
HR453doc 0x01C5DO-05_pulseOffWidthUINT16msRead/write
HR454doc 0x01C6DO-06_pulseOffWidthUINT16msRead/write
HR455doc 0x01C7DO-07_pulseOffWidthUINT16msRead/write
HR480doc 0x01E0DO-00_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR481doc 0x01E1DO-01_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR482doc 0x01E2DO-02_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR483doc 0x01E3DO-03_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR484doc 0x01E4DO-04_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR485doc 0x01E5DO-05_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR486doc 0x01E6DO-06_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR487doc 0x01E7DO-07_safeModeStatusUINT16Read/write0 = OFF; 1 = ON; 2 = Hold Last
HR512doc 0x0200DO-00_modeUINT16Read/write0 = DO; 1 = Pulse
HR513doc 0x0201DO-01_modeUINT16Read/write0 = DO; 1 = Pulse
HR514doc 0x0202DO-02_modeUINT16Read/write0 = DO; 1 = Pulse
HR515doc 0x0203DO-03_modeUINT16Read/write0 = DO; 1 = Pulse
HR516doc 0x0204DO-04_modeUINT16Read/write0 = DO; 1 = Pulse
HR517doc 0x0205DO-05_modeUINT16Read/write0 = DO; 1 = Pulse
HR518doc 0x0206DO-06_modeUINT16Read/write0 = DO; 1 = Pulse
HR519doc 0x0207DO-07_modeUINT16Read/write0 = DO; 1 = Pulse
HR30052doc 0x7564SYS_modbusWatchdogFuntionUINT16Read/write0 = Disable; 1 = Enable
HR30053doc 0x7565SYS_modbusWatchdogTimeoutUINT16sRead/write
HR30054doc 0x7566SYS_modbusWatchdogStatusUINT16Read/write0 = Normal; 1 = Timeout
HR30056doc 0x7568SYS_restartDeviceWrite 404 to trigger.UINT16Read/write
HR30057doc 0x7569SYS_loadFactoryDefaultWrite 404 to trigger.UINT16Read/write
HR30060doc 0x756CSYS_port0BaudrateUINT16Read/write1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 19200; 6 = 38400; 7 = 57600; 8 = 115200; 9 = 921600
HR30061doc 0x756DSYS_port1BaudrateUINT16Read/write1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 19200; 6 = 38400; 7 = 57600; 8 = 115200; 9 = 921600
HR30064doc 0x7570SYS_port0StopBitUINT16Read/write0 = 1; 1 = 2
HR30065doc 0x7571SYS_port1StopBitUINT16Read/write0 = 1; 1 = 2
HR30066doc 0x7572SYS_port0ParityUINT16Read/write0 = None; 1 = Even; 2 = Odd
HR30067doc 0x7573SYS_port1ParityUINT16Read/write0 = None; 1 = Even; 2 = Odd

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Moxa ioLogik R1212 RS-485 remote I/O

What Modbus registers does the Moxa ioLogik R1212 RS-485 remote I/O have?

This map lists 312 registers: 136 coils, 24 discrete inputs, 45 input registers, 107 holding registers. 243 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Moxa ioLogik R1212 RS-485 remote I/O Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints the hex protocol address and a 1-based reference number (0x0000 = 00001/10001/30001/40001). The hex address is sent on the wire; the table (coil, discrete input, input or holding) is set by the function code column.

What byte order does the Moxa ioLogik R1212 RS-485 remote I/O use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Moxa ioLogik R1212 RS-485 remote I/O?

Start with IR 30000 SYS_modelID (Model ID check); HR 30052 SYS_modbusWatchdogFuntion (Enable communication watchdog); HR 30053 SYS_modbusWatchdogTimeout (Watchdog timeout); DI 0 DI-00_status (First digital input); IR 32 DI-00_counterValue (First counter value); CO 320 DO-00_status (First output on/off).

How do I enable Modbus control of the Moxa ioLogik R1212 RS-485 remote I/O?

Set the device ID (1-99) on the two rotary dials. Put the Initial/Run switch on Initial to configure the unit at 9600 baud, no parity, 8 data bits, 1 stop bit (with ioSearch or the SYS_port* registers), then switch back to Run.

What happens when the Moxa ioLogik R1212 RS-485 remote I/O loses Modbus communication?

SYS_modbusWatchdogFuntion (0x7564) enables the host-connection watchdog, SYS_modbusWatchdogTimeout (0x7565) sets the timeout in seconds (factory default 10 s), SYS_modbusWatchdogStatus (0x7566) shows a timeout. It is disabled by default; safe-status settings only act when it is enabled.

Where is the official Moxa ioLogik R1212 RS-485 remote I/O Modbus documentation?

The source is ioLogik R1200 Series User's Manual (Edition 3.4), revision 2021-04. Moxa doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn11.bigcommerce.com/s-hltjsp5jm3/content/pdfs/moxa-iologik-r1200-series-manual.pdf. It may be an older revision, so check it against the live unit.

More Moxa Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →