Sensor (remote I/O module) · Modbus register map
Moxa ioLogik R1241 RS-485 remote I/O Modbus register map
Updated 17 November 2026
The ioLogik R1241 is a Moxa RS-485 Modbus RTU remote I/O module with 4 analog outputs (0-10 V, 0-20 mA, 4-20 mA). It supports a repeater or dual RS-485 mode and a Modbus host-connection watchdog with safe-mode output states. This map covers the shared system registers (model, watchdog, serial settings) and the analog output raw values, power-on and safe values, range.
This page lists 32 Modbus registers for the Moxa ioLogik R1241 RS-485 remote I/O — 27 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Moxa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Moxa
- Model
- ioLogik R1241 RS-485 remote I/O
- Equipment type
- Sensor (remote I/O module)
- Registers
- 32 (27 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- ioLogik R1241, R1241, R1241-T
Integration notes: Moxa ioLogik R1241 RS-485 remote I/O
Poll the I/O block with the function code shown for each register (01/02 for bits, 03/04 for words). Enable the Modbus watchdog (0x7564, timeout 0x7565) so outputs and counters fall back to their safe-mode settings if the master stops polling.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 30000 | SYS_modelID | UINT16 | Model ID check | Read |
| HR 30052 | SYS_modbusWatchdogFuntion | UINT16 | Enable communication watchdog | Read/write |
| HR 30053 | SYS_modbusWatchdogTimeout | UINT16 | Watchdog timeout | Read/write |
| HR 1184 | AO-00_rawValue | UINT16 | First analog output raw value | Read/write |
| HR 1280 | AO-00_mode | UINT16 | First analog output range | Read/write |
Enable Modbus control & writes
Set the device ID (1-99) on the two rotary dials. Put the Initial/Run switch on Initial to configure the unit at 9600 baud, no parity, 8 data bits, 1 stop bit (with ioSearch or the SYS_port* registers), then switch back to Run.
Communication loss & watchdog
SYS_modbusWatchdogFuntion (0x7564) enables the host-connection watchdog, SYS_modbusWatchdogTimeout (0x7565) sets the timeout in seconds (factory default 10 s), SYS_modbusWatchdogStatus (0x7566) shows a timeout. It is disabled by default; safe-status settings only act when it is enabled.
Byte order & addressing
- System registers sit at 0x7530 and up (six-digit references 330001/430002).
- Write 404 to SYS_restartDevice or SYS_loadFactoryDefault to trigger them.
Network setup
- Device ID 1-99 on the rotary dials (x1 and x10).
- The Dual/Rep switch selects two separate RS-485 ports or repeater mode; SYS_rs485PortMode reports which is active.
- Baud rate codes: 1=1200 ... 4=9600, 5=19200 ... 9=921600.
Watch out for
- Factory defaults (reset button held 5 s, ioSearch, or SYS_loadFactoryDefault) return the serial settings to 9600 n 8 1 and disable the watchdog.
Moxa ioLogik R1241 RS-485 remote I/O Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 30000doc 0x7530 | SYS_modelID | UINT16 | Read | |||||
| IR | 30025doc 0x7549 | SYS_vendorID | UINT16 | Read | |||||
| IR | 30026doc 0x754A | SYS_unitID | UINT16 | Read | |||||
| IR | 30037doc 0x7555 | SYS_productName | STRING[20] | Read | |||||
| IR | 30058doc 0x756A | SYS_rs485PortMode | UINT16 | Read | 0 = initial-repeater; 1 = initial-dual RS- 485; 2 = run-repeater; 3 = run-dual RS-485 | ||||
| HR | 1184doc 0x04A0 | AO-00_rawValue | UINT16 | Read/write | |||||
| HR | 1185doc 0x04A1 | AO-01_rawValue | UINT16 | Read/write | |||||
| HR | 1186doc 0x04A2 | AO-02_rawValue | UINT16 | Read/write | |||||
| HR | 1187doc 0x04A3 | AO-03_rawValue | UINT16 | Read/write | |||||
| HR | 1216doc 0x04C0 | AO-00_rawValuePowerOn | UINT16 | Read/write | |||||
| HR | 1217doc 0x04C1 | AO-01_rawValuePowerOn | UINT16 | Read/write | |||||
| HR | 1218doc 0x04C2 | AO-02_rawValuePowerOn | UINT16 | Read/write | |||||
| HR | 1219doc 0x04C3 | AO-03_rawValuePowerOn | UINT16 | Read/write | |||||
| HR | 1248doc 0x04E0 | AO-00_rawValueSafeMode | UINT16 | Read/write | |||||
| HR | 1249doc 0x04E1 | AO-01_rawValueSafeMode | UINT16 | Read/write | |||||
| HR | 1250doc 0x04E2 | AO-02_rawValueSafeMode | UINT16 | Read/write | |||||
| HR | 1251doc 0x04E3 | AO-03_rawValueSafeMode | UINT16 | Read/write | |||||
| HR | 1280doc 0x0500 | AO-00_mode | UINT16 | Read/write | 0 = 0-10 V; 1 = 0-20 mA; 2 = 4-20 mA | ||||
| HR | 1281doc 0x0501 | AO-01_mode | UINT16 | Read/write | 0 = 0-10 V; 1 = 0-20 mA; 2 = 4-20 mA | ||||
| HR | 1282doc 0x0502 | AO-02_mode | UINT16 | Read/write | 0 = 0-10 V; 1 = 0-20 mA; 2 = 4-20 mA | ||||
| HR | 1283doc 0x0503 | AO-03_mode | UINT16 | Read/write | 0 = 0-10 V; 1 = 0-20 mA; 2 = 4-20 m | ||||
| HR | 30052doc 0x7564 | SYS_modbusWatchdogFuntion | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 30053doc 0x7565 | SYS_modbusWatchdogTimeout | UINT16 | s | Read/write | ||||
| HR | 30054doc 0x7566 | SYS_modbusWatchdogStatus | UINT16 | Read/write | 0 = Normal; 1 = Timeout | ||||
| HR | 30056doc 0x7568 | SYS_restartDevice | Write 404 to trigger. | UINT16 | Read/write | ||||
| HR | 30057doc 0x7569 | SYS_loadFactoryDefault | Write 404 to trigger. | UINT16 | Read/write | ||||
| HR | 30060doc 0x756C | SYS_port0Baudrate | UINT16 | Read/write | 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 19200; 6 = 38400; 7 = 57600; 8 = 115200; 9 = 921600 | ||||
| HR | 30061doc 0x756D | SYS_port1Baudrate | UINT16 | Read/write | 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 19200; 6 = 38400; 7 = 57600; 8 = 115200; 9 = 921600 | ||||
| HR | 30064doc 0x7570 | SYS_port0StopBit | UINT16 | Read/write | 0 = 1; 1 = 2 | ||||
| HR | 30065doc 0x7571 | SYS_port1StopBit | UINT16 | Read/write | 0 = 1; 1 = 2 | ||||
| HR | 30066doc 0x7572 | SYS_port0Parity | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | ||||
| HR | 30067doc 0x7573 | SYS_port1Parity | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd |
Notes on this map
- Moxa does not appear to offer this manual on a public URL found in this pass; the link is an unaltered copy of the Moxa user's manual on a reseller's file host.
- Each table row gives the hex wire address, the 1-based decimal reference (e.g. 0x0000 = 40001; system registers use six digits, 0x7530 = 330001), access, size and function code.
- Left out: system strings and multi-word values whose format is not described (firmware version and release date, serial number, server name/location, password, vendor name).
- Raw AO values are listed without scaling; the table does not give the raw-to-engineering range.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Moxa ioLogik R1241 RS-485 remote I/O
What Modbus registers does the Moxa ioLogik R1241 RS-485 remote I/O have?
This map lists 32 registers: 5 input registers, 27 holding registers. 27 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Moxa ioLogik R1241 RS-485 remote I/O Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints the hex protocol address and a 1-based reference number (0x0000 = 00001/10001/30001/40001). The hex address is sent on the wire; the table (coil, discrete input, input or holding) is set by the function code column.
What are the minimum Modbus registers to integrate the Moxa ioLogik R1241 RS-485 remote I/O?
Start with IR 30000 SYS_modelID (Model ID check); HR 30052 SYS_modbusWatchdogFuntion (Enable communication watchdog); HR 30053 SYS_modbusWatchdogTimeout (Watchdog timeout); HR 1184 AO-00_rawValue (First analog output raw value); HR 1280 AO-00_mode (First analog output range).
How do I enable Modbus control of the Moxa ioLogik R1241 RS-485 remote I/O?
Set the device ID (1-99) on the two rotary dials. Put the Initial/Run switch on Initial to configure the unit at 9600 baud, no parity, 8 data bits, 1 stop bit (with ioSearch or the SYS_port* registers), then switch back to Run.
What happens when the Moxa ioLogik R1241 RS-485 remote I/O loses Modbus communication?
SYS_modbusWatchdogFuntion (0x7564) enables the host-connection watchdog, SYS_modbusWatchdogTimeout (0x7565) sets the timeout in seconds (factory default 10 s), SYS_modbusWatchdogStatus (0x7566) shows a timeout. It is disabled by default; safe-status settings only act when it is enabled.
Where is the official Moxa ioLogik R1241 RS-485 remote I/O Modbus documentation?
The source is ioLogik R1200 Series User's Manual (Edition 3.4), revision 2021-04. Moxa doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn11.bigcommerce.com/s-hltjsp5jm3/content/pdfs/moxa-iologik-r1200-series-manual.pdf. It may be an older revision, so check it against the live unit.
More Moxa Modbus register maps
- Sensor (remote I/O module)
Moxa ioLogik R1210 RS-485 remote I/O
ioLogik R1210 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1210, R1210, R1210-T - Sensor (remote I/O module)
Moxa ioLogik R1212 RS-485 remote I/O
ioLogik R1212 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1212, R1212, R1212-T - Sensor (remote I/O module)
Moxa ioLogik R1214 RS-485 remote I/O
ioLogik R1214 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1214, R1214, R1214-T - Sensor (remote I/O module)
Moxa ioLogik R1240 RS-485 remote I/O
ioLogik R1240 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1240, R1240, R1240-T
Other remote i/o modules register maps
- Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS11 I/O module
Unipi Extension xS11 RS-485 module per the Unipi Extension xS11 Modbus map v2.0.
Also known as: Unipi Extension xS11, xS11 - Sensor / remote I/O module
Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-516 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-516, ED516 - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS53 analog input module
Unipi Extension xS53 RS-485 module per the Unipi Extension xS53 Modbus map v2.0.
Also known as: Unipi Extension xS53, xS53
All remote i/o modules Modbus register maps →
Source: ioLogik R1200 Series User's Manual · Edition 3.4 · rev. 2021-04 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.