- Home
- Modbus register maps
- Seneca
- R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
Sensor (remote I/O module, analog outputs) · Modbus register map
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) Modbus register map
Updated 17 November 2026
The R-4AO-8DIDO is a Seneca R-series remote I/O with four voltage/current analog outputs and eight digital channels that can each be an input or an output, plus eight 32-bit counters. It serves Modbus TCP on a two-port Ethernet switch and Modbus RTU on RS-485. This map covers integer output setpoints, status, digital I/O, counters, period/frequency and the command register.
This page lists 54 Modbus registers for the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seneca
- Model
- R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
- Equipment type
- Sensor (remote I/O module, analog outputs)
- Registers
- 54 (22 writable)
- Transport
- Modbus TCP, Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO
Integration notes: Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
Write the signed 16-bit engineering setpoint for each output to 79-82 (scaled by the output's engineering start/stop settings). Read 20 for under/over-scale and watchdog flags and 21 for the digital channels.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 79 | AO1 engineering value (integer) | INT16 | AO1 setpoint (integer) | Read/write |
| HR 80 | AO2 engineering value (integer) | INT16 | AO2 setpoint (integer) | Read/write |
| HR 81 | AO3 engineering value (integer) | INT16 | AO3 setpoint (integer) | Read/write |
| HR 82 | AO4 engineering value (integer) | INT16 | AO4 setpoint (integer) | Read/write |
| HR 20 | Analog output status | BITMAP16 | Output status flags | Read |
| HR 21 | Digital I/O value | BITMAP16 | Digital I/O word | Read/write |
| HR 23 | Counter 1 | UINT32 ABCD | Counter 1 | Read/write |
Enable Modbus control & writes
Modbus TCP server and RTU slave are on by default. Network and serial settings are changed in the web server or Seneca Discovery Device; DIP switches 1-2 select normal, factory reset or web-server-off.
Communication loss & watchdog
Per the web-server chapter, each analog output and each digital output has an optional watchdog (default disabled) with a timeout in seconds and a fail value or state.
Byte order & addressing
- Offset is the wire address.
- Counters, period and frequency are MSW first; the float setpoints have no stated word order.
Network setup
- Factory IP is 192.168.90.101; never put two factory-fresh units on the same network.
- Disable the web server with the DIP switches once commissioning is done.
Watch out for
- Channel direction (input or output) is set per channel in the configuration.
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 1 | Digital I/O 1 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 1doc 2 | Digital I/O 2 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 2doc 3 | Digital I/O 3 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 3doc 4 | Digital I/O 4 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 4doc 5 | Digital I/O 5 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 5doc 6 | Digital I/O 6 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 6doc 7 | Digital I/O 7 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 7doc 8 | Digital I/O 8 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| DI | 0doc 10001 | Digital input 1 | BIT | Read | |||||
| DI | 1doc 10002 | Digital input 2 | BIT | Read | |||||
| DI | 2doc 10003 | Digital input 3 | BIT | Read | |||||
| DI | 3doc 10004 | Digital input 4 | BIT | Read | |||||
| DI | 4doc 10005 | Digital input 5 | BIT | Read | |||||
| DI | 5doc 10006 | Digital input 6 | BIT | Read | |||||
| DI | 6doc 10007 | Digital input 7 | BIT | Read | |||||
| DI | 7doc 10008 | Digital input 8 | BIT | Read | |||||
| HR | 0doc 40001 | Machine ID | Device identification code. | UINT16 | Read | ||||
| HR | 1doc 40002 | Firmware revision (major/minor) | UINT16 | Read | |||||
| HR | 2doc 40003 | Firmware revision (fix/build) | UINT16 | Read | |||||
| HR | 3doc 40004 | Firmware code | UINT16 | Read | |||||
| HR | 4doc 40005 | Board ID | Hardware revision. | UINT16 | Read | ||||
| HR | 5doc 40006 | Modbus ID | UINT16 | Read | |||||
| HR | 16doc 40017 | Command register | UINT16 | Read/write | 256 = Set factory default (0x0100); 257 = Clear all counters (0x0101); 49568 = Reset device (0xC1A0) | ||||
| HR | 17doc 40018 | Device status | UINT16 | Read | |||||
| HR | 20doc 40021 | Analog output status | BITMAP16 | Read | bit 0 = AO1 under-scale; bit 1 = AO2 under-scale; bit 2 = AO3 under-scale; bit 3 = AO4 under-scale; bit 4 = AO1 over-scale; bit 5 = AO2 over-scale; bit 6 = AO3 over-scale; bit 7 = AO4 over-scale; bit 8 = AO1 watchdog fail; bit 9 = AO2 watchdog fail; bit 10 = AO3 watchdog fail; bit 11 = AO4 watchdog fail | ||||
| HR | 21doc 40022 | Digital I/O value | Bit 0 = channel 1 ... bit 7 = channel 8. | BITMAP16 | Read/write | bit 0 = Channel 1; bit 1 = Channel 2; bit 2 = Channel 3; bit 3 = Channel 4; bit 4 = Channel 5; bit 5 = Channel 6; bit 6 = Channel 7; bit 7 = Channel 8 | |||
| HR | 23doc 40024 | Counter 1 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 25doc 40026 | Counter 2 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 27doc 40028 | Counter 3 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 29doc 40030 | Counter 4 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 31doc 40032 | Counter 5 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 33doc 40034 | Counter 6 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 35doc 40036 | Counter 7 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 37doc 40038 | Counter 8 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 39doc 40040 | Period channel 1 | FLOAT32 | ABCD | s | Read | |||
| HR | 41doc 40042 | Period channel 2 | FLOAT32 | ABCD | s | Read | |||
| HR | 43doc 40044 | Period channel 3 | FLOAT32 | ABCD | s | Read | |||
| HR | 45doc 40046 | Period channel 4 | FLOAT32 | ABCD | s | Read | |||
| HR | 47doc 40048 | Period channel 5 | FLOAT32 | ABCD | s | Read | |||
| HR | 49doc 40050 | Period channel 6 | FLOAT32 | ABCD | s | Read | |||
| HR | 51doc 40052 | Period channel 7 | FLOAT32 | ABCD | s | Read | |||
| HR | 53doc 40054 | Period channel 8 | FLOAT32 | ABCD | s | Read | |||
| HR | 55doc 40056 | Frequency channel 1 | FLOAT32 | ABCD | Hz | Read | |||
| HR | 57doc 40058 | Frequency channel 2 | FLOAT32 | ABCD | Hz | Read | |||
| HR | 59doc 40060 | Frequency channel 3 | FLOAT32 | ABCD | Hz | Read | |||
| HR | 61doc 40062 | Frequency channel 4 | FLOAT32 | ABCD | Hz | Read | |||
| HR | 63doc 40064 | Frequency channel 5 | FLOAT32 | ABCD | Hz | Read | |||
| HR | 65doc 40066 | Frequency channel 6 | FLOAT32 | ABCD | Hz | Read | |||
| HR | 67doc 40068 | Frequency channel 7 | FLOAT32 | ABCD | Hz | Read | |||
| HR | 69doc 40070 | Frequency channel 8 | FLOAT32 | ABCD | Hz | Read | |||
| HR | 79doc 40080 | AO1 engineering value (integer) | Scaled output setpoint; default units mV or uA. | INT16 | Read/write | ||||
| HR | 80doc 40081 | AO2 engineering value (integer) | Scaled output setpoint; default units mV or uA. | INT16 | Read/write | ||||
| HR | 81doc 40082 | AO3 engineering value (integer) | Scaled output setpoint; default units mV or uA. | INT16 | Read/write | ||||
| HR | 82doc 40083 | AO4 engineering value (integer) | Scaled output setpoint; default units mV or uA. | INT16 | Read/write |
Notes on this map
- The protocol page lists function codes 01, 03, 05, 06, 15 and 16; the tables also give the digital inputs as 1x input status read with function 02. Modbus RTU runs on RS-485 and Modbus TCP serves up to 8 clients.
- Counters, period and frequency rows are printed MSW at the lower address (ABCD). The float analog output setpoints (40072-40079) carry no MSW/LSW marks and the manual has no general word-order rule (a sibling model in the same manual is LSW first), so they are left out; use the signed 16-bit setpoints at 40080-40083 instead.
- Factory settings from the manual: static IP 192.168.90.101/24, gateway 192.168.90.1, Modbus TCP port 502, station address 1; RS-485 38400 baud, 8 data bits, no parity, 1 stop bit, address 1.
- RW* registers are stored in flash and survive about 10,000 writes.
- Analog output values are in engineering units set by the configured scale (default mV or uA); the manual does not give a fixed scale.
- Left out: the auxiliary command registers 40013-40016, whose codes are not described, and reserved registers.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
What Modbus registers does the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) have?
This map lists 54 registers: 8 coils, 8 discrete inputs, 38 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Holding-register tables print the 4x number (40001) and the 0-based offset (0); coils print 1 / offset 0 and discrete inputs 10001 / offset 0. The offset is the wire address.
What byte order does the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)?
Start with HR 79 AO1 engineering value (integer) (AO1 setpoint (integer)); HR 80 AO2 engineering value (integer) (AO2 setpoint (integer)); HR 81 AO3 engineering value (integer) (AO3 setpoint (integer)); HR 82 AO4 engineering value (integer) (AO4 setpoint (integer)); HR 20 Analog output status (Output status flags); HR 21 Digital I/O value (Digital I/O word); HR 23 Counter 1 (Counter 1).
How do I enable Modbus control of the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)?
Modbus TCP server and RTU slave are on by default. Network and serial settings are changed in the web server or Seneca Discovery Device; DIP switches 1-2 select normal, factory reset or web-server-off.
What happens when the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) loses Modbus communication?
Per the web-server chapter, each analog output and each digital output has an optional watchdog (default disabled) with a timeout in seconds and a fail value or state.
Where is the official Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) Modbus documentation?
The source is Series R I/O with protocol - User Manual (MI-00604-29-EN), revision 2026-09-03, published free by Seneca at https://www.seneca.it/media/6848135/mi00604-29-en.pdf.
More Seneca Modbus register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2 - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN
Other remote i/o modules register maps
- Sensor (remote I/O module)
Unipi Technology Unipi Extension xS53 analog input module
Unipi Extension xS53 RS-485 module per the Unipi Extension xS53 Modbus map v2.0.
Also known as: Unipi Extension xS53, xS53 - Sensor (thermistor input module)
ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)
M-7005 in Modbus RTU mode, per I-7005/M-7005 User Manual Rev B2.4 (7MH-018-B24). The I-7005 uses the DCON protocol and is not covered.
Also known as: M-7005, M7005, I-7005/M-7005 - Sensor (remote I/O module)
Moxa ioLogik R1240 RS-485 remote I/O
ioLogik R1240 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1240, R1240, R1240-T - Sensor (thermocouple input module)
Teracom TST320 2-channel thermocouple module with Modbus RTU
TST320 per the Teracom TST320 user manual Revision R1.6.
Also known as: TST320 - Sensor (Ethernet analog input module)
Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP)
BusWorks XT1211-000 (current) and XT1221-000 (voltage) per user's manual 8500951K.
Also known as: XT1211-000, XT1221-000, XT1211, XT1221, BusWorks XT1211, BusWorks XT1221 - Sensor / remote digital I/O module
ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
tM-P4C4 (4 DI + 4 DO), tM-C8 (8 DO) and tM-P8 (8 DI) with the Modbus RTU protocol selected, per the tM Series DIO User Manual Rev A1.4.
Also known as: tM-P4C4, tM-C8, tM-P8
All remote i/o modules Modbus register maps →
Source: Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.