Sensor (remote I/O module, analog outputs) · Modbus register map

Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) Modbus register map

Updated 17 November 2026

Short answer

The R-4AO-8DIDO is a Seneca R-series remote I/O with four voltage/current analog outputs and eight digital channels that can each be an input or an output, plus eight 32-bit counters. It serves Modbus TCP on a two-port Ethernet switch and Modbus RTU on RS-485. This map covers integer output setpoints, status, digital I/O, counters, period/frequency and the command register.

This page lists 54 Modbus registers for the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.

Manufacturer
Seneca
Model
R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
Equipment type
Sensor (remote I/O module, analog outputs)
Registers
54 (22 writable)
Transport
Modbus TCP, Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8N1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO
Source document
Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)

Integration in brief

Write the signed 16-bit engineering setpoint for each output to 79-82 (scaled by the output's engineering start/stop settings). Read 20 for under/over-scale and watchdog flags and 21 for the digital channels.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 79AO1 engineering value (integer)INT16AO1 setpoint (integer)Read/write
HR 80AO2 engineering value (integer)INT16AO2 setpoint (integer)Read/write
HR 81AO3 engineering value (integer)INT16AO3 setpoint (integer)Read/write
HR 82AO4 engineering value (integer)INT16AO4 setpoint (integer)Read/write
HR 20Analog output statusBITMAP16Output status flagsRead
HR 21Digital I/O valueBITMAP16Digital I/O wordRead/write
HR 23Counter 1UINT32 ABCDCounter 1Read/write

Enable Modbus control & writes

Modbus TCP server and RTU slave are on by default. Network and serial settings are changed in the web server or Seneca Discovery Device; DIP switches 1-2 select normal, factory reset or web-server-off.

Communication loss & watchdog

Per the web-server chapter, each analog output and each digital output has an optional watchdog (default disabled) with a timeout in seconds and a fail value or state.

Byte order & addressing

Network setup

Watch out for

Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

54 of 54 shown
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 1Digital I/O 1Same channel as the digital I/O word.BITRead/write
CO1doc 2Digital I/O 2Same channel as the digital I/O word.BITRead/write
CO2doc 3Digital I/O 3Same channel as the digital I/O word.BITRead/write
CO3doc 4Digital I/O 4Same channel as the digital I/O word.BITRead/write
CO4doc 5Digital I/O 5Same channel as the digital I/O word.BITRead/write
CO5doc 6Digital I/O 6Same channel as the digital I/O word.BITRead/write
CO6doc 7Digital I/O 7Same channel as the digital I/O word.BITRead/write
CO7doc 8Digital I/O 8Same channel as the digital I/O word.BITRead/write
DI0doc 10001Digital input 1BITRead
DI1doc 10002Digital input 2BITRead
DI2doc 10003Digital input 3BITRead
DI3doc 10004Digital input 4BITRead
DI4doc 10005Digital input 5BITRead
DI5doc 10006Digital input 6BITRead
DI6doc 10007Digital input 7BITRead
DI7doc 10008Digital input 8BITRead
HR0doc 40001Machine IDDevice identification code.UINT16Read
HR1doc 40002Firmware revision (major/minor)UINT16Read
HR2doc 40003Firmware revision (fix/build)UINT16Read
HR3doc 40004Firmware codeUINT16Read
HR4doc 40005Board IDHardware revision.UINT16Read
HR5doc 40006Modbus IDUINT16Read
HR16doc 40017Command registerUINT16Read/write256 = Set factory default (0x0100); 257 = Clear all counters (0x0101); 49568 = Reset device (0xC1A0)
HR17doc 40018Device statusUINT16Read
HR20doc 40021Analog output statusBITMAP16Readbit 0 = AO1 under-scale; bit 1 = AO2 under-scale; bit 2 = AO3 under-scale; bit 3 = AO4 under-scale; bit 4 = AO1 over-scale; bit 5 = AO2 over-scale; bit 6 = AO3 over-scale; bit 7 = AO4 over-scale; bit 8 = AO1 watchdog fail; bit 9 = AO2 watchdog fail; bit 10 = AO3 watchdog fail; bit 11 = AO4 watchdog fail
HR21doc 40022Digital I/O valueBit 0 = channel 1 ... bit 7 = channel 8.BITMAP16Read/writebit 0 = Channel 1; bit 1 = Channel 2; bit 2 = Channel 3; bit 3 = Channel 4; bit 4 = Channel 5; bit 5 = Channel 6; bit 6 = Channel 7; bit 7 = Channel 8
HR23doc 40024Counter 1Digital input counter.UINT32ABCDRead/write
HR25doc 40026Counter 2Digital input counter.UINT32ABCDRead/write
HR27doc 40028Counter 3Digital input counter.UINT32ABCDRead/write
HR29doc 40030Counter 4Digital input counter.UINT32ABCDRead/write
HR31doc 40032Counter 5Digital input counter.UINT32ABCDRead/write
HR33doc 40034Counter 6Digital input counter.UINT32ABCDRead/write
HR35doc 40036Counter 7Digital input counter.UINT32ABCDRead/write
HR37doc 40038Counter 8Digital input counter.UINT32ABCDRead/write
HR39doc 40040Period channel 1FLOAT32ABCDsRead
HR41doc 40042Period channel 2FLOAT32ABCDsRead
HR43doc 40044Period channel 3FLOAT32ABCDsRead
HR45doc 40046Period channel 4FLOAT32ABCDsRead
HR47doc 40048Period channel 5FLOAT32ABCDsRead
HR49doc 40050Period channel 6FLOAT32ABCDsRead
HR51doc 40052Period channel 7FLOAT32ABCDsRead
HR53doc 40054Period channel 8FLOAT32ABCDsRead
HR55doc 40056Frequency channel 1FLOAT32ABCDHzRead
HR57doc 40058Frequency channel 2FLOAT32ABCDHzRead
HR59doc 40060Frequency channel 3FLOAT32ABCDHzRead
HR61doc 40062Frequency channel 4FLOAT32ABCDHzRead
HR63doc 40064Frequency channel 5FLOAT32ABCDHzRead
HR65doc 40066Frequency channel 6FLOAT32ABCDHzRead
HR67doc 40068Frequency channel 7FLOAT32ABCDHzRead
HR69doc 40070Frequency channel 8FLOAT32ABCDHzRead
HR79doc 40080AO1 engineering value (integer)Scaled output setpoint; default units mV or uA.INT16Read/write
HR80doc 40081AO2 engineering value (integer)Scaled output setpoint; default units mV or uA.INT16Read/write
HR81doc 40082AO3 engineering value (integer)Scaled output setpoint; default units mV or uA.INT16Read/write
HR82doc 40083AO4 engineering value (integer)Scaled output setpoint; default units mV or uA.INT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)

What Modbus registers does the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) have?

This map lists 54 registers: 8 coils, 8 discrete inputs, 38 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Holding-register tables print the 4x number (40001) and the 0-based offset (0); coils print 1 / offset 0 and discrete inputs 10001 / offset 0. The offset is the wire address.

What byte order does the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)?

Start with HR 79 AO1 engineering value (integer) (AO1 setpoint (integer)); HR 80 AO2 engineering value (integer) (AO2 setpoint (integer)); HR 81 AO3 engineering value (integer) (AO3 setpoint (integer)); HR 82 AO4 engineering value (integer) (AO4 setpoint (integer)); HR 20 Analog output status (Output status flags); HR 21 Digital I/O value (Digital I/O word); HR 23 Counter 1 (Counter 1).

How do I enable Modbus control of the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)?

Modbus TCP server and RTU slave are on by default. Network and serial settings are changed in the web server or Seneca Discovery Device; DIP switches 1-2 select normal, factory reset or web-server-off.

What happens when the Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) loses Modbus communication?

Per the web-server chapter, each analog output and each digital output has an optional watchdog (default disabled) with a timeout in seconds and a fail value or state.

Where is the official Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O) Modbus documentation?

The source is Series R I/O with protocol - User Manual (MI-00604-29-EN), revision 2026-09-03, published free by Seneca at https://www.seneca.it/media/6848135/mi00604-29-en.pdf.

More Seneca Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.