Seneca Z-4TC 4-channel thermocouple input module Modbus register map

Updated 17 November 2026

Short answer

The Z-4TC reads four thermocouples (J, K, R, S, T, B, E, N) or ±160 mV signals and serves them over RS-485 Modbus RTU. This map lists the 16-bit integer registers: comms settings, input type and filter per channel, status/error words and the four measurements in tenths of a degree.

This page lists 18 Modbus registers for the Seneca Z-4TC 4-channel thermocouple input module — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.

Manufacturer
Seneca
Model
Z-4TC 4-channel thermocouple input module
Equipment type
Sensor (I/O module, 4 thermocouple inputs)
Registers
18 (11 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
Z-4TC
Source document
Z-4TC User Manual · MI00258-3-EN
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Seneca Z-4TC 4-channel thermocouple input module

Integration in brief

Read holding registers 40013-40016 (wire 12-15) and divide by 10 for °C; check 40012 for burn-out bits.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 12Channel 1 measureINT16Channel 1Read
HR 13Channel 2 measureINT16Channel 2Read
HR 14Channel 3 measureINT16Channel 3Read
HR 15Channel 4 measureINT16Channel 4Read
HR 11StatusBITMAP16Status / burn-outRead/write
HR 3Input 1 typeUINT16Input 1 typeRead/write

Enable Modbus control & writes

Supported functions are 3, 6 and 16; set the thermocouple type of each channel in 40004-40007.

Byte order & addressing

Network setup

Watch out for

Seneca Z-4TC 4-channel thermocouple input module Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

18 of 18 shown
Seneca Z-4TC 4-channel thermocouple input module Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Machine IDModule ID code.UINT16Read
HR1doc 40002Baud rate and addressHigh byte = baud code (0=4800,1=9600,2=19200,3=38400,4=57600,5=115200,6=1200,7=2400), low byte = station address.UINT16Read/write
HR2doc 40003EEPROM flagsBITMAP16Read/writebit 0 = TC break detection off (0 = on); bit 1 = Sampling 60 ms per channel (0 = 120 ms); bit 2 = Reply delay on; bit 3 = Parity on; bit 4 = Parity odd (0 = even)
HR3doc 40004Input 1 typeUINT16Read/write0 = Voltage ±160 mV; 1 = TC J; 2 = TC K; 3 = TC R; 4 = TC S; 5 = TC T; 6 = TC B; 7 = TC E; 8 = TC N
HR4doc 40005Input 2 typeUINT16Read/write0 = Voltage ±160 mV; 1 = TC J; 2 = TC K; 3 = TC R; 4 = TC S; 5 = TC T; 6 = TC B; 7 = TC E; 8 = TC N
HR5doc 40006Input 3 typeUINT16Read/write0 = Voltage ±160 mV; 1 = TC J; 2 = TC K; 3 = TC R; 4 = TC S; 5 = TC T; 6 = TC B; 7 = TC E; 8 = TC N
HR6doc 40007Input 4 typeUINT16Read/write0 = Voltage ±160 mV; 1 = TC J; 2 = TC K; 3 = TC R; 4 = TC S; 5 = TC T; 6 = TC B; 7 = TC E; 8 = TC N
HR7doc 40008IN1 filter0 = off, 1 = minimum ... 6 = maximum filtering.UINT16Read/write
HR8doc 40009IN2 filter0 = off, 1 = minimum ... 6 = maximum filtering.UINT16Read/write
HR9doc 40010IN3 filter0 = off, 1 = minimum ... 6 = maximum filtering.UINT16Read/write
HR10doc 40011IN4 filter0 = off, 1 = minimum ... 6 = maximum filtering.UINT16Read/write
HR11doc 40012StatusBITMAP16Read/writebit 0 = Reset (write 1 to reboot); bit 1 = Generic error; bit 2 = Data-configuration acquisition error; bit 3 = Configuration error; bit 7 = Save configuration to flash (write 1); bit 8 = Input 1 acquisition error; bit 9 = Input 2 acquisition error; bit 10 = Input 3 acquisition error; bit 11 = Input 4 acquisition error; bit 12 = Input 1 burn-out; bit 13 = Input 2 burn-out; bit 14 = Input 3 burn-out; bit 15 = Input 4 burn-out
HR12doc 40013Channel 1 measureThermocouple: °C x 10 (220 = 22.0 °C). Voltage mode: steps of 0.005 mV.INT16× 0.1°CRead
HR13doc 40014Channel 2 measureThermocouple: °C x 10 (220 = 22.0 °C). Voltage mode: steps of 0.005 mV.INT16× 0.1°CRead
HR14doc 40015Channel 3 measureThermocouple: °C x 10 (220 = 22.0 °C). Voltage mode: steps of 0.005 mV.INT16× 0.1°CRead
HR15doc 40016Channel 4 measureThermocouple: °C x 10 (220 = 22.0 °C). Voltage mode: steps of 0.005 mV.INT16× 0.1°CRead
HR16doc 40017Firmware revisionUINT16Read
HR18doc 40019ErrorsBITMAP16Readbit 0 = ADC error; bit 1 = Cold junction TC 1-2 error; bit 2 = Cold junction TC 3-4 error; bit 8 = Calibration error; bit 9 = Setting error; bit 11 = ADC zero error

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Seneca Z-4TC 4-channel thermocouple input module

What Modbus registers does the Seneca Z-4TC 4-channel thermocouple input module have?

This map lists 18 registers: 18 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Seneca Z-4TC 4-channel thermocouple input module Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints the Modbus address (40001) and the offset (0); the offset is the wire address.

What are the minimum Modbus registers to integrate the Seneca Z-4TC 4-channel thermocouple input module?

Start with HR 12 Channel 1 measure (Channel 1); HR 13 Channel 2 measure (Channel 2); HR 14 Channel 3 measure (Channel 3); HR 15 Channel 4 measure (Channel 4); HR 11 Status (Status / burn-out); HR 3 Input 1 type (Input 1 type).

How do I enable Modbus control of the Seneca Z-4TC 4-channel thermocouple input module?

Supported functions are 3, 6 and 16; set the thermocouple type of each channel in 40004-40007.

Where is the official Seneca Z-4TC 4-channel thermocouple input module Modbus documentation?

The source is Z-4TC User Manual (MI00258-3-EN), published free by Seneca at https://www.seneca.it/media/2285/mi00258-3-en.pdf.

More Seneca Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: Z-4TC User Manual · MI00258-3-EN. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.