- Z-4TC 4-channel thermocouple input module
Sensor (I/O module, 4 thermocouple inputs) · Modbus register map
Seneca Z-4TC 4-channel thermocouple input module Modbus register map
Updated 17 November 2026
The Z-4TC reads four thermocouples (J, K, R, S, T, B, E, N) or ±160 mV signals and serves them over RS-485 Modbus RTU. This map lists the 16-bit integer registers: comms settings, input type and filter per channel, status/error words and the four measurements in tenths of a degree.
This page lists 18 Modbus registers for the Seneca Z-4TC 4-channel thermocouple input module — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seneca
- Model
- Z-4TC 4-channel thermocouple input module
- Equipment type
- Sensor (I/O module, 4 thermocouple inputs)
- Registers
- 18 (11 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Z-4TC
- Source document
- Z-4TC User Manual · MI00258-3-EN
Integration notes: Seneca Z-4TC 4-channel thermocouple input module
Read holding registers 40013-40016 (wire 12-15) and divide by 10 for °C; check 40012 for burn-out bits.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 12 | Channel 1 measure | INT16 | Channel 1 | Read |
| HR 13 | Channel 2 measure | INT16 | Channel 2 | Read |
| HR 14 | Channel 3 measure | INT16 | Channel 3 | Read |
| HR 15 | Channel 4 measure | INT16 | Channel 4 | Read |
| HR 11 | Status | BITMAP16 | Status / burn-out | Read/write |
| HR 3 | Input 1 type | UINT16 | Input 1 type | Read/write |
Enable Modbus control & writes
Supported functions are 3, 6 and 16; set the thermocouple type of each channel in 40004-40007.
Byte order & addressing
- 40002 packs baud code and address into one register.
- Voltage-mode readings use a different scale (0.005 mV).
Network setup
- Write bit 7 of 40012 to store settings in flash.
Watch out for
- Floating-point registers exist on newer firmware but their word order is not documented.
- Every input defaults to type 0 (voltage), where readings are in 0.005 mV steps; set the thermocouple type in 40004-40007 before using the 0.1 °C scaling.
Seneca Z-4TC 4-channel thermocouple input module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Machine ID | Module ID code. | UINT16 | Read | ||||
| HR | 1doc 40002 | Baud rate and address | High byte = baud code (0=4800,1=9600,2=19200,3=38400,4=57600,5=115200,6=1200,7=2400), low byte = station address. | UINT16 | Read/write | ||||
| HR | 2doc 40003 | EEPROM flags | BITMAP16 | Read/write | bit 0 = TC break detection off (0 = on); bit 1 = Sampling 60 ms per channel (0 = 120 ms); bit 2 = Reply delay on; bit 3 = Parity on; bit 4 = Parity odd (0 = even) | ||||
| HR | 3doc 40004 | Input 1 type | UINT16 | Read/write | 0 = Voltage ±160 mV; 1 = TC J; 2 = TC K; 3 = TC R; 4 = TC S; 5 = TC T; 6 = TC B; 7 = TC E; 8 = TC N | ||||
| HR | 4doc 40005 | Input 2 type | UINT16 | Read/write | 0 = Voltage ±160 mV; 1 = TC J; 2 = TC K; 3 = TC R; 4 = TC S; 5 = TC T; 6 = TC B; 7 = TC E; 8 = TC N | ||||
| HR | 5doc 40006 | Input 3 type | UINT16 | Read/write | 0 = Voltage ±160 mV; 1 = TC J; 2 = TC K; 3 = TC R; 4 = TC S; 5 = TC T; 6 = TC B; 7 = TC E; 8 = TC N | ||||
| HR | 6doc 40007 | Input 4 type | UINT16 | Read/write | 0 = Voltage ±160 mV; 1 = TC J; 2 = TC K; 3 = TC R; 4 = TC S; 5 = TC T; 6 = TC B; 7 = TC E; 8 = TC N | ||||
| HR | 7doc 40008 | IN1 filter | 0 = off, 1 = minimum ... 6 = maximum filtering. | UINT16 | Read/write | ||||
| HR | 8doc 40009 | IN2 filter | 0 = off, 1 = minimum ... 6 = maximum filtering. | UINT16 | Read/write | ||||
| HR | 9doc 40010 | IN3 filter | 0 = off, 1 = minimum ... 6 = maximum filtering. | UINT16 | Read/write | ||||
| HR | 10doc 40011 | IN4 filter | 0 = off, 1 = minimum ... 6 = maximum filtering. | UINT16 | Read/write | ||||
| HR | 11doc 40012 | Status | BITMAP16 | Read/write | bit 0 = Reset (write 1 to reboot); bit 1 = Generic error; bit 2 = Data-configuration acquisition error; bit 3 = Configuration error; bit 7 = Save configuration to flash (write 1); bit 8 = Input 1 acquisition error; bit 9 = Input 2 acquisition error; bit 10 = Input 3 acquisition error; bit 11 = Input 4 acquisition error; bit 12 = Input 1 burn-out; bit 13 = Input 2 burn-out; bit 14 = Input 3 burn-out; bit 15 = Input 4 burn-out | ||||
| HR | 12doc 40013 | Channel 1 measure | Thermocouple: °C x 10 (220 = 22.0 °C). Voltage mode: steps of 0.005 mV. | INT16 | × 0.1 | °C | Read | ||
| HR | 13doc 40014 | Channel 2 measure | Thermocouple: °C x 10 (220 = 22.0 °C). Voltage mode: steps of 0.005 mV. | INT16 | × 0.1 | °C | Read | ||
| HR | 14doc 40015 | Channel 3 measure | Thermocouple: °C x 10 (220 = 22.0 °C). Voltage mode: steps of 0.005 mV. | INT16 | × 0.1 | °C | Read | ||
| HR | 15doc 40016 | Channel 4 measure | Thermocouple: °C x 10 (220 = 22.0 °C). Voltage mode: steps of 0.005 mV. | INT16 | × 0.1 | °C | Read | ||
| HR | 16doc 40017 | Firmware revision | UINT16 | Read | |||||
| HR | 18doc 40019 | Errors | BITMAP16 | Read | bit 0 = ADC error; bit 1 = Cold junction TC 1-2 error; bit 2 = Cold junction TC 3-4 error; bit 8 = Calibration error; bit 9 = Setting error; bit 11 = ADC zero error |
Notes on this map
- Left out: the 32-bit floating-point measures (40027-40034, firmware 667 on) and offsets (40037-40044, firmware 668 on), because the manual says only that a float spans two holding registers and never states which word comes first.
- Integer measures are °C x 10 for thermocouple inputs and units of 0.005 mV for voltage inputs (1848 = 9.24 mV); the map shows the thermocouple scaling.
- Address 1 and 38400 baud with no parity are the default register values (EEPROM mode).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seneca Z-4TC 4-channel thermocouple input module
What Modbus registers does the Seneca Z-4TC 4-channel thermocouple input module have?
This map lists 18 registers: 18 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seneca Z-4TC 4-channel thermocouple input module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints the Modbus address (40001) and the offset (0); the offset is the wire address.
What are the minimum Modbus registers to integrate the Seneca Z-4TC 4-channel thermocouple input module?
Start with HR 12 Channel 1 measure (Channel 1); HR 13 Channel 2 measure (Channel 2); HR 14 Channel 3 measure (Channel 3); HR 15 Channel 4 measure (Channel 4); HR 11 Status (Status / burn-out); HR 3 Input 1 type (Input 1 type).
How do I enable Modbus control of the Seneca Z-4TC 4-channel thermocouple input module?
Supported functions are 3, 6 and 16; set the thermocouple type of each channel in 40004-40007.
Where is the official Seneca Z-4TC 4-channel thermocouple input module Modbus documentation?
The source is Z-4TC User Manual (MI00258-3-EN), published free by Seneca at https://www.seneca.it/media/2285/mi00258-3-en.pdf.
More Seneca Modbus register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2 - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN
Other remote i/o modules register maps
- Sensor (remote I/O module)
Unipi Technology Unipi Extension xS51 I/O module
Unipi Extension xS51 RS-485 module per the Unipi Extension xS51 Modbus map v2.0.
Also known as: Unipi Extension xS51, xS51 - Sensor / remote I/O module
Brainboxes ED-538 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-538 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-538, ED538 - Sensor (remote I/O module)
Moxa ioLogik R1212 RS-485 remote I/O
ioLogik R1212 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1212, R1212, R1212-T - Sensor (Ethernet data logger / I/O module)
Teracom TCW220 Ethernet data logger
TCW220 per the Teracom TCW220 user manual Revision R4.24, firmware V2.012 or later.
Also known as: TCW220 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS54 universal analog input module
Unipi Extension xS54 RS-485 module per the Unipi Extension xS54 Modbus map v2.0.
Also known as: Unipi Extension xS54, xS54 - Sensor (counter/frequency input module)
ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
ICP DAS M-7080 and M-7080B two-channel 32-bit counter/frequency modules with two digital outputs, in Modbus RTU mode.
Also known as: M-7080, M-7080B, M7080, M7080B
All remote i/o modules Modbus register maps →
Source: Z-4TC User Manual · MI00258-3-EN. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.