- Home
- Modbus register maps
- Seneca
- R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
Sensor (remote I/O module, RTD inputs) · Modbus register map
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) Modbus register map
Updated 17 November 2026
The R-4RTD-8DIDO is a Seneca R-series remote I/O with four RTD temperature inputs and eight digital channels that can be inputs or outputs, plus eight 32-bit counters. It serves Modbus TCP on a two-port Ethernet switch and Modbus RTU on RS-485. This map covers temperatures, resistances, engineering values, status flags, digital I/O and counters.
This page lists 50 Modbus registers for the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seneca
- Model
- R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
- Equipment type
- Sensor (remote I/O module, RTD inputs)
- Registers
- 50 (18 writable)
- Transport
- Modbus TCP, Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD
Integration notes: Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
Read holding registers 29-55 in one block: status flags, digital I/O, then temperature, resistance and engineering floats. Counters live high at 1843-1858.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 29 | Status | BITMAP16 | Over-range / burnout flags | Read |
| HR 32 | RTD1 temperature | FLOAT32 ABCD | RTD1 temperature | Read |
| HR 34 | RTD2 temperature | FLOAT32 ABCD | RTD2 temperature | Read |
| HR 36 | RTD3 temperature | FLOAT32 ABCD | RTD3 temperature | Read |
| HR 38 | RTD4 temperature | FLOAT32 ABCD | RTD4 temperature | Read |
| HR 31 | Digital inputs | BITMAP16 | Digital inputs | Read |
Enable Modbus control & writes
Modbus TCP server and RTU slave are on by default; configure through the web server or Seneca Discovery Device.
Communication loss & watchdog
Per the web-server chapter, digital outputs have an optional watchdog (default disabled, timeout default 100 s) on Modbus traffic or on output writes.
Byte order & addressing
- Offset is the wire address.
- Counters are at offsets 1843-1858, far from the measurement block.
Network setup
- Factory IP is 192.168.90.101; change it before adding a second unit.
Watch out for
- Check the burnout bits before trusting a temperature.
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 1 | Digital I/O 1 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 1doc 2 | Digital I/O 2 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 2doc 3 | Digital I/O 3 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 3doc 4 | Digital I/O 4 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 4doc 5 | Digital I/O 5 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 5doc 6 | Digital I/O 6 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 6doc 7 | Digital I/O 7 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| CO | 7doc 8 | Digital I/O 8 | Same channel as the digital I/O word. | BIT | Read/write | ||||
| DI | 0doc 10001 | Digital input 1 | BIT | Read | |||||
| DI | 1doc 10002 | Digital input 2 | BIT | Read | |||||
| DI | 2doc 10003 | Digital input 3 | BIT | Read | |||||
| DI | 3doc 10004 | Digital input 4 | BIT | Read | |||||
| DI | 4doc 10005 | Digital input 5 | BIT | Read | |||||
| DI | 5doc 10006 | Digital input 6 | BIT | Read | |||||
| DI | 6doc 10007 | Digital input 7 | BIT | Read | |||||
| DI | 7doc 10008 | Digital input 8 | BIT | Read | |||||
| HR | 0doc 40001 | Machine ID | Device identification code. | UINT16 | Read | ||||
| HR | 1doc 40002 | Firmware revision (major/minor) | UINT16 | Read | |||||
| HR | 2doc 40003 | Firmware revision (fix/build) | UINT16 | Read | |||||
| HR | 3doc 40004 | Firmware code | UINT16 | Read | |||||
| HR | 4doc 40005 | Board ID | Hardware revision. | UINT16 | Read | ||||
| HR | 5doc 40006 | Modbus ID | UINT16 | Read | |||||
| HR | 12doc 40013 | Command register | UINT16 | Read/write | 256 = Set factory default (0x0100); 49568 = Reset device (0xC1A0) | ||||
| HR | 29doc 40030 | Status | BITMAP16 | Read | bit 0 = RTD1 over-range; bit 1 = RTD2 over-range; bit 2 = RTD3 over-range; bit 3 = RTD4 over-range; bit 4 = RTD1 burnout; bit 5 = RTD2 burnout; bit 6 = RTD3 burnout; bit 7 = RTD4 burnout; bit 15 = Fail | ||||
| HR | 30doc 40031 | Digital outputs | BITMAP16 | Read/write | bit 0 = Output 1; bit 1 = Output 2; bit 2 = Output 3; bit 3 = Output 4; bit 4 = Output 5; bit 5 = Output 6; bit 6 = Output 7; bit 7 = Output 8 | ||||
| HR | 31doc 40032 | Digital inputs | BITMAP16 | Read | bit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4; bit 4 = Input 5; bit 5 = Input 6; bit 6 = Input 7; bit 7 = Input 8 | ||||
| HR | 32doc 40033 | RTD1 temperature | In the unit chosen for the channel (°C, K, °F or Ohm). | FLOAT32 | ABCD | Read | |||
| HR | 34doc 40035 | RTD2 temperature | In the unit chosen for the channel (°C, K, °F or Ohm). | FLOAT32 | ABCD | Read | |||
| HR | 36doc 40037 | RTD3 temperature | In the unit chosen for the channel (°C, K, °F or Ohm). | FLOAT32 | ABCD | Read | |||
| HR | 38doc 40039 | RTD4 temperature | In the unit chosen for the channel (°C, K, °F or Ohm). | FLOAT32 | ABCD | Read | |||
| HR | 40doc 40041 | RTD1 resistance | FLOAT32 | ABCD | Ohm | Read | |||
| HR | 42doc 40043 | RTD2 resistance | FLOAT32 | ABCD | Ohm | Read | |||
| HR | 44doc 40045 | RTD3 resistance | FLOAT32 | ABCD | Ohm | Read | |||
| HR | 46doc 40047 | RTD4 resistance | FLOAT32 | ABCD | Ohm | Read | |||
| HR | 48doc 40049 | RTD1 engineering value | Scaled per the channel engineering start/stop scale. | FLOAT32 | ABCD | Read | |||
| HR | 50doc 40051 | RTD2 engineering value | Scaled per the channel engineering start/stop scale. | FLOAT32 | ABCD | Read | |||
| HR | 52doc 40053 | RTD3 engineering value | Scaled per the channel engineering start/stop scale. | FLOAT32 | ABCD | Read | |||
| HR | 54doc 40055 | RTD4 engineering value | Scaled per the channel engineering start/stop scale. | FLOAT32 | ABCD | Read | |||
| HR | 60doc 40061 | RTD1 ADC raw value | UINT32 | ABCD | Read | ||||
| HR | 62doc 40063 | RTD2 ADC raw value | UINT32 | ABCD | Read | ||||
| HR | 64doc 40065 | RTD3 ADC raw value | UINT32 | ABCD | Read | ||||
| HR | 66doc 40067 | RTD4 ADC raw value | UINT32 | ABCD | Read | ||||
| HR | 1843doc 41844 | Counter 1 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 1845doc 41846 | Counter 2 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 1847doc 41848 | Counter 3 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 1849doc 41850 | Counter 4 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 1851doc 41852 | Counter 5 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 1853doc 41854 | Counter 6 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 1855doc 41856 | Counter 7 | Digital input counter. | UINT32 | ABCD | Read/write | |||
| HR | 1857doc 41858 | Counter 8 | Digital input counter. | UINT32 | ABCD | Read/write |
Notes on this map
- The protocol page lists function codes 01, 03, 05, 06, 15 and 16; the tables also give the digital inputs as 1x input status read with function 02. Modbus RTU runs on RS-485 and Modbus TCP serves up to 8 clients.
- 32-bit values are printed MSW at the lower address (ABCD).
- Factory settings from the manual: static IP 192.168.90.101/24, gateway 192.168.90.1, Modbus TCP port 502, station address 1; RS-485 38400 baud, 8 data bits, no parity, 1 stop bit, address 1.
- RW* registers are stored in flash and survive about 10,000 writes.
- Temperature floats are in the unit chosen per channel in the web server (°C, K, °F or Ohm).
- Left out: the signed 16-bit temperature copies at 40057-40060, because the table gives no scale for them.
- The table prints the reserved range as 40014..40029 / offset 13..39; the offset end looks like a typo and is not used here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
What Modbus registers does the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) have?
This map lists 50 registers: 8 coils, 8 discrete inputs, 34 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Holding-register tables print the 4x number (40001) and the 0-based offset (0); coils print 1 / offset 0 and discrete inputs 10001 / offset 0. The offset is the wire address.
What byte order does the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)?
Start with HR 29 Status (Over-range / burnout flags); HR 32 RTD1 temperature (RTD1 temperature); HR 34 RTD2 temperature (RTD2 temperature); HR 36 RTD3 temperature (RTD3 temperature); HR 38 RTD4 temperature (RTD4 temperature); HR 31 Digital inputs (Digital inputs).
How do I enable Modbus control of the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)?
Modbus TCP server and RTU slave are on by default; configure through the web server or Seneca Discovery Device.
What happens when the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) loses Modbus communication?
Per the web-server chapter, digital outputs have an optional watchdog (default disabled, timeout default 100 s) on Modbus traffic or on output writes.
Where is the official Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) Modbus documentation?
The source is Series R I/O with protocol - User Manual (MI-00604-29-EN), revision 2026-09-03, published free by Seneca at https://www.seneca.it/media/6848135/mi00604-29-en.pdf.
More Seneca Modbus register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2 - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN
Other remote i/o modules register maps
- Sensor (Ethernet data logger / I/O module)
Teracom TCW220 Ethernet data logger
TCW220 per the Teracom TCW220 user manual Revision R4.24, firmware V2.012 or later.
Also known as: TCW220 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS54 universal analog input module
Unipi Extension xS54 RS-485 module per the Unipi Extension xS54 Modbus map v2.0.
Also known as: Unipi Extension xS54, xS54 - Sensor (counter/frequency input module)
ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
ICP DAS M-7080 and M-7080B two-channel 32-bit counter/frequency modules with two digital outputs, in Modbus RTU mode.
Also known as: M-7080, M-7080B, M7080, M7080B - Sensor (remote I/O module)
Moxa ioLogik R1241 RS-485 remote I/O
ioLogik R1241 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1241, R1241, R1241-T - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS11 I/O module
Unipi Extension xS11 RS-485 module per the Unipi Extension xS11 Modbus map v2.0.
Also known as: Unipi Extension xS11, xS11 - Sensor / remote I/O module
Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-516 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-516, ED516
All remote i/o modules Modbus register maps →
Source: Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.