Sensor (remote I/O module, RTD inputs) · Modbus register map

Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) Modbus register map

Updated 17 November 2026

Short answer

The R-4RTD-8DIDO is a Seneca R-series remote I/O with four RTD temperature inputs and eight digital channels that can be inputs or outputs, plus eight 32-bit counters. It serves Modbus TCP on a two-port Ethernet switch and Modbus RTU on RS-485. This map covers temperatures, resistances, engineering values, status flags, digital I/O and counters.

This page lists 50 Modbus registers for the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.

Manufacturer
Seneca
Model
R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
Equipment type
Sensor (remote I/O module, RTD inputs)
Registers
50 (18 writable)
Transport
Modbus TCP, Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8N1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD
Source document
Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)

Integration in brief

Read holding registers 29-55 in one block: status flags, digital I/O, then temperature, resistance and engineering floats. Counters live high at 1843-1858.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 29StatusBITMAP16Over-range / burnout flagsRead
HR 32RTD1 temperatureFLOAT32 ABCDRTD1 temperatureRead
HR 34RTD2 temperatureFLOAT32 ABCDRTD2 temperatureRead
HR 36RTD3 temperatureFLOAT32 ABCDRTD3 temperatureRead
HR 38RTD4 temperatureFLOAT32 ABCDRTD4 temperatureRead
HR 31Digital inputsBITMAP16Digital inputsRead

Enable Modbus control & writes

Modbus TCP server and RTU slave are on by default; configure through the web server or Seneca Discovery Device.

Communication loss & watchdog

Per the web-server chapter, digital outputs have an optional watchdog (default disabled, timeout default 100 s) on Modbus traffic or on output writes.

Byte order & addressing

Network setup

Watch out for

Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

50 of 50 shown
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 1Digital I/O 1Same channel as the digital I/O word.BITRead/write
CO1doc 2Digital I/O 2Same channel as the digital I/O word.BITRead/write
CO2doc 3Digital I/O 3Same channel as the digital I/O word.BITRead/write
CO3doc 4Digital I/O 4Same channel as the digital I/O word.BITRead/write
CO4doc 5Digital I/O 5Same channel as the digital I/O word.BITRead/write
CO5doc 6Digital I/O 6Same channel as the digital I/O word.BITRead/write
CO6doc 7Digital I/O 7Same channel as the digital I/O word.BITRead/write
CO7doc 8Digital I/O 8Same channel as the digital I/O word.BITRead/write
DI0doc 10001Digital input 1BITRead
DI1doc 10002Digital input 2BITRead
DI2doc 10003Digital input 3BITRead
DI3doc 10004Digital input 4BITRead
DI4doc 10005Digital input 5BITRead
DI5doc 10006Digital input 6BITRead
DI6doc 10007Digital input 7BITRead
DI7doc 10008Digital input 8BITRead
HR0doc 40001Machine IDDevice identification code.UINT16Read
HR1doc 40002Firmware revision (major/minor)UINT16Read
HR2doc 40003Firmware revision (fix/build)UINT16Read
HR3doc 40004Firmware codeUINT16Read
HR4doc 40005Board IDHardware revision.UINT16Read
HR5doc 40006Modbus IDUINT16Read
HR12doc 40013Command registerUINT16Read/write256 = Set factory default (0x0100); 49568 = Reset device (0xC1A0)
HR29doc 40030StatusBITMAP16Readbit 0 = RTD1 over-range; bit 1 = RTD2 over-range; bit 2 = RTD3 over-range; bit 3 = RTD4 over-range; bit 4 = RTD1 burnout; bit 5 = RTD2 burnout; bit 6 = RTD3 burnout; bit 7 = RTD4 burnout; bit 15 = Fail
HR30doc 40031Digital outputsBITMAP16Read/writebit 0 = Output 1; bit 1 = Output 2; bit 2 = Output 3; bit 3 = Output 4; bit 4 = Output 5; bit 5 = Output 6; bit 6 = Output 7; bit 7 = Output 8
HR31doc 40032Digital inputsBITMAP16Readbit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4; bit 4 = Input 5; bit 5 = Input 6; bit 6 = Input 7; bit 7 = Input 8
HR32doc 40033RTD1 temperatureIn the unit chosen for the channel (°C, K, °F or Ohm).FLOAT32ABCDRead
HR34doc 40035RTD2 temperatureIn the unit chosen for the channel (°C, K, °F or Ohm).FLOAT32ABCDRead
HR36doc 40037RTD3 temperatureIn the unit chosen for the channel (°C, K, °F or Ohm).FLOAT32ABCDRead
HR38doc 40039RTD4 temperatureIn the unit chosen for the channel (°C, K, °F or Ohm).FLOAT32ABCDRead
HR40doc 40041RTD1 resistanceFLOAT32ABCDOhmRead
HR42doc 40043RTD2 resistanceFLOAT32ABCDOhmRead
HR44doc 40045RTD3 resistanceFLOAT32ABCDOhmRead
HR46doc 40047RTD4 resistanceFLOAT32ABCDOhmRead
HR48doc 40049RTD1 engineering valueScaled per the channel engineering start/stop scale.FLOAT32ABCDRead
HR50doc 40051RTD2 engineering valueScaled per the channel engineering start/stop scale.FLOAT32ABCDRead
HR52doc 40053RTD3 engineering valueScaled per the channel engineering start/stop scale.FLOAT32ABCDRead
HR54doc 40055RTD4 engineering valueScaled per the channel engineering start/stop scale.FLOAT32ABCDRead
HR60doc 40061RTD1 ADC raw valueUINT32ABCDRead
HR62doc 40063RTD2 ADC raw valueUINT32ABCDRead
HR64doc 40065RTD3 ADC raw valueUINT32ABCDRead
HR66doc 40067RTD4 ADC raw valueUINT32ABCDRead
HR1843doc 41844Counter 1Digital input counter.UINT32ABCDRead/write
HR1845doc 41846Counter 2Digital input counter.UINT32ABCDRead/write
HR1847doc 41848Counter 3Digital input counter.UINT32ABCDRead/write
HR1849doc 41850Counter 4Digital input counter.UINT32ABCDRead/write
HR1851doc 41852Counter 5Digital input counter.UINT32ABCDRead/write
HR1853doc 41854Counter 6Digital input counter.UINT32ABCDRead/write
HR1855doc 41856Counter 7Digital input counter.UINT32ABCDRead/write
HR1857doc 41858Counter 8Digital input counter.UINT32ABCDRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)

What Modbus registers does the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) have?

This map lists 50 registers: 8 coils, 8 discrete inputs, 34 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Holding-register tables print the 4x number (40001) and the 0-based offset (0); coils print 1 / offset 0 and discrete inputs 10001 / offset 0. The offset is the wire address.

What byte order does the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)?

Start with HR 29 Status (Over-range / burnout flags); HR 32 RTD1 temperature (RTD1 temperature); HR 34 RTD2 temperature (RTD2 temperature); HR 36 RTD3 temperature (RTD3 temperature); HR 38 RTD4 temperature (RTD4 temperature); HR 31 Digital inputs (Digital inputs).

How do I enable Modbus control of the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)?

Modbus TCP server and RTU slave are on by default; configure through the web server or Seneca Discovery Device.

What happens when the Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) loses Modbus communication?

Per the web-server chapter, digital outputs have an optional watchdog (default disabled, timeout default 100 s) on Modbus traffic or on output writes.

Where is the official Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O) Modbus documentation?

The source is Series R I/O with protocol - User Manual (MI-00604-29-EN), revision 2026-09-03, published free by Seneca at https://www.seneca.it/media/6848135/mi00604-29-en.pdf.

More Seneca Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.