Sensor (counter/frequency input module) · Modbus register map

ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The M-7080 and M-7080B are RS-485 remote I/O modules that count pulses or measure frequency on two inputs and drive two digital outputs. In Modbus RTU mode the 32-bit counts sit in holding registers as low/high word pairs, and configuration flags are coils. This map covers the count/frequency values, maximum and preset values, input thresholds, outputs and counter control.

This page lists 24 Modbus registers for the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ICP DAS’s own free documentation (linked below) and checked against it.

Manufacturer
ICP DAS
Model
M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
Equipment type
Sensor (counter/frequency input module)
Registers
24 (20 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Also known as
M-7080, M-7080B, M7080, M7080B
Source document
M-7000 Series Address Mapping Table · V1.18 · rev. 2025-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)

Integration in brief

Read holding registers 0-3 for both 32-bit counts (low word first). Start or stop each counter with coils 00135/00136 and drive the outputs with coils 00001/00002.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Counter/frequency value channel 0UINT32 CDABChannel 0 count/frequencyRead
HR 2Counter/frequency value channel 1UINT32 CDABChannel 1 count/frequencyRead
CO 64Overflow flag of counter 0BITCounter 0 overflowRead
CO 134Start/stop counter 0BITStart/stop counter 0Read/write
CO 0DO 0BITDO 0Read/write

Enable Modbus control & writes

The module must be in Modbus RTU mode (ICP DAS modules also speak DCON); see the module's user manual for switching protocol.

Byte order & addressing

Network setup

Watch out for

ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

24 of 24 shown
ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001DO 0BITRead/write0 = Off; 1 = On
CO1doc 00002DO 1BITRead/write0 = Off; 1 = On
CO64doc 00065Overflow flag of counter 0BITRead0 = Normal; 1 = Overflow
CO65doc 00066Overflow flag of counter 1BITRead0 = Normal; 1 = Overflow
CO128doc 00129Input mode channel 0BITRead/write0 = Non-isolated; 1 = Isolated
CO129doc 00130Input mode channel 1BITRead/write0 = Non-isolated; 1 = Isolated
CO130doc 00131Gate active levelUsed when gate control is enabled.BITRead/write0 = Low active; 1 = High active
CO132doc 00133Set counter 0 to presetM-7080 only. Write 1.BITWrite
CO133doc 00134Set counter 1 to presetM-7080 only. Write 1.BITWrite
CO134doc 00135Start/stop counter 0BITRead/write0 = Stop; 1 = Start
CO135doc 00136Start/stop counter 1BITRead/write0 = Stop; 1 = Start
CO138doc 00139Digital filter enableBITRead/write0 = Disable; 1 = Enable
CO141doc 00142Frequency gate timeBITRead/write0 = 0.1 s; 1 = 1.0 s
CO142doc 00143LED configurationBITRead/write0 = Channel 0; 1 = Channel 1
HR0doc 40001Counter/frequency value channel 0Counter or frequency per the channel type code; low word at the lower address.UINT32CDABRead
HR2doc 40003Counter/frequency value channel 1Counter or frequency per the channel type code; low word at the lower address.UINT32CDABRead
HR64doc 40065Max value of counter 0Factory 65535 in each word.UINT32CDABRead/write
HR66doc 40067Max value of counter 1Factory 65535 in each word.UINT32CDABRead/write
HR96doc 40097Preset value of counter 0UINT32CDABRead/write
HR98doc 40099Preset value of counter 1UINT32CDABRead/write
HR160doc 40161Low level width threshold2-65535 us.UINT16usRead/write
HR161doc 40162High level width threshold2-65535 us.UINT16usRead/write
HR162doc 40163Low voltage trigger value0-5.0 V; factory 0.8 V.UINT16× 0.1VRead/write
HR163doc 40164High voltage trigger value0-5.0 V; factory 2.4 V.UINT16× 0.1VRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)

What Modbus registers does the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) have?

This map lists 24 registers: 14 coils, 10 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table is titled 'M-7000 Address Mapping (Base 1)': 00001 coils, 10001 discrete inputs, 30001 input registers, 40001 holding registers. Subtract the table base for the wire address (40001 = holding register 0).

What byte order does the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)?

Start with HR 0 Counter/frequency value channel 0 (Channel 0 count/frequency); HR 2 Counter/frequency value channel 1 (Channel 1 count/frequency); CO 64 Overflow flag of counter 0 (Counter 0 overflow); CO 134 Start/stop counter 0 (Start/stop counter 0); CO 0 DO 0 (DO 0).

How do I enable Modbus control of the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)?

The module must be in Modbus RTU mode (ICP DAS modules also speak DCON); see the module's user manual for switching protocol.

Where is the official ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) Modbus documentation?

The source is M-7000 Series Address Mapping Table (V1.18), revision 2025-09, published free by ICP DAS at https://www.icpdas.com/en/download/file.php?num=19906.

More ICP DAS Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: M-7000 Series Address Mapping Table · V1.18 · rev. 2025-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.