- M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
Sensor (counter/frequency input module) · Modbus register map
ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) Modbus register map
Updated 19 November 2026
The M-7080 and M-7080B are RS-485 remote I/O modules that count pulses or measure frequency on two inputs and drive two digital outputs. In Modbus RTU mode the 32-bit counts sit in holding registers as low/high word pairs, and configuration flags are coils. This map covers the count/frequency values, maximum and preset values, input thresholds, outputs and counter control.
This page lists 24 Modbus registers for the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ICP DAS’s own free documentation (linked below) and checked against it.
- Manufacturer
- ICP DAS
- Model
- M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
- Equipment type
- Sensor (counter/frequency input module)
- Registers
- 24 (20 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- M-7080, M-7080B, M7080, M7080B
- Source document
- M-7000 Series Address Mapping Table · V1.18 · rev. 2025-09
Integration notes: ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
Read holding registers 0-3 for both 32-bit counts (low word first). Start or stop each counter with coils 00135/00136 and drive the outputs with coils 00001/00002.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Counter/frequency value channel 0 | UINT32 CDAB | Channel 0 count/frequency | Read |
| HR 2 | Counter/frequency value channel 1 | UINT32 CDAB | Channel 1 count/frequency | Read |
| CO 64 | Overflow flag of counter 0 | BIT | Counter 0 overflow | Read |
| CO 134 | Start/stop counter 0 | BIT | Start/stop counter 0 | Read/write |
| CO 0 | DO 0 | BIT | DO 0 | Read/write |
Enable Modbus control & writes
The module must be in Modbus RTU mode (ICP DAS modules also speak DCON); see the module's user manual for switching protocol.
Byte order & addressing
- 32-bit values are low word first (CDAB).
- Counters are started by default (coils 00135/00136 default 1).
Network setup
- Voltage trigger levels are in 0.1 V steps (factory 0.8 V low, 2.4 V high).
Watch out for
- On the M-7080B, writing the preset registers 40097-40100 with type code 52 also loads them into the counters.
ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | DO 0 | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 1doc 00002 | DO 1 | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 64doc 00065 | Overflow flag of counter 0 | BIT | Read | 0 = Normal; 1 = Overflow | ||||
| CO | 65doc 00066 | Overflow flag of counter 1 | BIT | Read | 0 = Normal; 1 = Overflow | ||||
| CO | 128doc 00129 | Input mode channel 0 | BIT | Read/write | 0 = Non-isolated; 1 = Isolated | ||||
| CO | 129doc 00130 | Input mode channel 1 | BIT | Read/write | 0 = Non-isolated; 1 = Isolated | ||||
| CO | 130doc 00131 | Gate active level | Used when gate control is enabled. | BIT | Read/write | 0 = Low active; 1 = High active | |||
| CO | 132doc 00133 | Set counter 0 to preset | M-7080 only. Write 1. | BIT | Write | ||||
| CO | 133doc 00134 | Set counter 1 to preset | M-7080 only. Write 1. | BIT | Write | ||||
| CO | 134doc 00135 | Start/stop counter 0 | BIT | Read/write | 0 = Stop; 1 = Start | ||||
| CO | 135doc 00136 | Start/stop counter 1 | BIT | Read/write | 0 = Stop; 1 = Start | ||||
| CO | 138doc 00139 | Digital filter enable | BIT | Read/write | 0 = Disable; 1 = Enable | ||||
| CO | 141doc 00142 | Frequency gate time | BIT | Read/write | 0 = 0.1 s; 1 = 1.0 s | ||||
| CO | 142doc 00143 | LED configuration | BIT | Read/write | 0 = Channel 0; 1 = Channel 1 | ||||
| HR | 0doc 40001 | Counter/frequency value channel 0 | Counter or frequency per the channel type code; low word at the lower address. | UINT32 | CDAB | Read | |||
| HR | 2doc 40003 | Counter/frequency value channel 1 | Counter or frequency per the channel type code; low word at the lower address. | UINT32 | CDAB | Read | |||
| HR | 64doc 40065 | Max value of counter 0 | Factory 65535 in each word. | UINT32 | CDAB | Read/write | |||
| HR | 66doc 40067 | Max value of counter 1 | Factory 65535 in each word. | UINT32 | CDAB | Read/write | |||
| HR | 96doc 40097 | Preset value of counter 0 | UINT32 | CDAB | Read/write | ||||
| HR | 98doc 40099 | Preset value of counter 1 | UINT32 | CDAB | Read/write | ||||
| HR | 160doc 40161 | Low level width threshold | 2-65535 us. | UINT16 | us | Read/write | |||
| HR | 161doc 40162 | High level width threshold | 2-65535 us. | UINT16 | us | Read/write | |||
| HR | 162doc 40163 | Low voltage trigger value | 0-5.0 V; factory 0.8 V. | UINT16 | × 0.1 | V | Read/write | ||
| HR | 163doc 40164 | High voltage trigger value | 0-5.0 V; factory 2.4 V. | UINT16 | × 0.1 | V | Read/write |
Notes on this map
- Each 32-bit value is listed as a low word followed by a high word, so read two registers and treat them as low word first (CDAB).
- Whether channel values are counts or frequency depends on the module type code, which this table does not map; frequency units are not stated.
- The M-7080B table has no set-to-preset coils (00133/00134); on the M-7080B, writing the preset registers with type code 52 also loads them into the counters.
- The M-7080 counter-mode coils 00145/00146 need firmware 0A24 or later and are left out, as are the module name, address and baud registers not printed for these models.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
What Modbus registers does the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) have?
This map lists 24 registers: 14 coils, 10 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table is titled 'M-7000 Address Mapping (Base 1)': 00001 coils, 10001 discrete inputs, 30001 input registers, 40001 holding registers. Subtract the table base for the wire address (40001 = holding register 0).
What byte order does the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)?
Start with HR 0 Counter/frequency value channel 0 (Channel 0 count/frequency); HR 2 Counter/frequency value channel 1 (Channel 1 count/frequency); CO 64 Overflow flag of counter 0 (Counter 0 overflow); CO 134 Start/stop counter 0 (Start/stop counter 0); CO 0 DO 0 (DO 0).
How do I enable Modbus control of the ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)?
The module must be in Modbus RTU mode (ICP DAS modules also speak DCON); see the module's user manual for switching protocol.
Where is the official ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU) Modbus documentation?
The source is M-7000 Series Address Mapping Table (V1.18), revision 2025-09, published free by ICP DAS at https://www.icpdas.com/en/download/file.php?num=19906.
More ICP DAS Modbus register maps
- Sensor (thermistor input module)
ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)
M-7005 in Modbus RTU mode, per I-7005/M-7005 User Manual Rev B2.4 (7MH-018-B24). The I-7005 uses the DCON protocol and is not covered.
Also known as: M-7005, M7005, I-7005/M-7005 - Sensor (PWM output and counter input module)
ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)
ICP DAS M-7088 eight-channel PWM output module with eight digital inputs and counters, Modbus RTU firmware.
Also known as: M-7088, M7088 - Sensor / remote digital I/O module
ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
tM-P4C4 (4 DI + 4 DO), tM-C8 (8 DO) and tM-P8 (8 DI) with the Modbus RTU protocol selected, per the tM Series DIO User Manual Rev A1.4.
Also known as: tM-P4C4, tM-C8, tM-P8
Other remote i/o modules register maps
- Sensor (remote I/O module)
Moxa ioLogik R1241 RS-485 remote I/O
ioLogik R1241 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1241, R1241, R1241-T - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS11 I/O module
Unipi Extension xS11 RS-485 module per the Unipi Extension xS11 Modbus map v2.0.
Also known as: Unipi Extension xS11, xS11 - Sensor / remote I/O module
Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-516 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-516, ED516 - Sensor (remote I/O module)
Moxa ioLogik R1210 RS-485 remote I/O
ioLogik R1210 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1210, R1210, R1210-T - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO
All remote i/o modules Modbus register maps →
Source: M-7000 Series Address Mapping Table · V1.18 · rev. 2025-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.