Easy Modbus
  1. Home
  2. Modbus register maps
  3. ICP DAS
  4. tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)

Sensor / remote digital I/O module · Modbus register map

ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

ICP DAS tM modules are small DIN-rail RS-485 I/O modules that speak DCON or Modbus RTU. The DIO models covered here give digital outputs as coils, digital inputs as discrete inputs, 16-bit input counters, latch bits and module settings. Only the channels a model actually has respond.

This page lists 94 Modbus registers for the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) — 40 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ICP DAS’s own free documentation (linked below) and checked against it.

Manufacturer
ICP DAS
Model
tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
Equipment type
Sensor / remote digital I/O module
Registers
94 (40 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
1
Default serial
9600 baud
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
tM-P4C4, tM-C8, tM-P8
Source document
tM Series DIO User Manual · Rev A1.4 (7PH-013-A14) · rev. 2018-12-28
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)

Integration in brief

Switch the module to Modbus RTU, then read inputs with function 02 from wire 32 and drive outputs with function 05 at wire 0-7. Counters are on function 04 from wire 0.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 0DO0 outputBITDO0 outputRead/write
DI 32DI0 inputBITDI0 inputRead
IR 0DI0 counterUINT16DI0 counterRead
CO 512Clear DI0 counterBITClear DI0 counterWrite
CO 260Host watchdog enableBITHost watchdog enableRead/write
CO 269Host watchdog timeout statusBITHost watchdog timeout statusRead/write

Enable Modbus control & writes

Factory default is already Modbus RTU, address 1, 9600 bps. Coil 00257 switches between DCON and Modbus; address and baud changes are made with the DCON utility or function 70.

Communication loss & watchdog

Host watchdog: enable with coil 00261, timeout 0-255 x 0.1 s in 40489. On timeout the outputs go to their safe values (00129-00136); clear the timeout status with coil 00270.

Byte order & addressing

Network setup

Watch out for

ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

94 of 94 shown
ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001DO0 outputDigital output channel 0 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7).BITRead/write
CO1doc 00002DO1 outputDigital output channel 1 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7).BITRead/write
CO2doc 00003DO2 outputDigital output channel 2 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7).BITRead/write
CO3doc 00004DO3 outputDigital output channel 3 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7).BITRead/write
CO4doc 00005DO4 outputDigital output channel 4 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7).BITRead/write
CO5doc 00006DO5 outputDigital output channel 5 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7).BITRead/write
CO6doc 00007DO6 outputDigital output channel 6 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7).BITRead/write
CO7doc 00008DO7 outputDigital output channel 7 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7).BITRead/write
CO32doc 00033DI0 input (coil copy)Same DI value readable with function 01.BITRead
CO33doc 00034DI1 input (coil copy)Same DI value readable with function 01.BITRead
CO34doc 00035DI2 input (coil copy)Same DI value readable with function 01.BITRead
CO35doc 00036DI3 input (coil copy)Same DI value readable with function 01.BITRead
CO36doc 00037DI4 input (coil copy)Same DI value readable with function 01.BITRead
CO37doc 00038DI5 input (coil copy)Same DI value readable with function 01.BITRead
CO38doc 00039DI6 input (coil copy)Same DI value readable with function 01.BITRead
CO39doc 00040DI7 input (coil copy)Same DI value readable with function 01.BITRead
CO64doc 00065DI0 high latchLatched high state of the input; read with function 01.BITRead
CO65doc 00066DI1 high latchLatched high state of the input; read with function 01.BITRead
CO66doc 00067DI2 high latchLatched high state of the input; read with function 01.BITRead
CO67doc 00068DI3 high latchLatched high state of the input; read with function 01.BITRead
CO68doc 00069DI4 high latchLatched high state of the input; read with function 01.BITRead
CO69doc 00070DI5 high latchLatched high state of the input; read with function 01.BITRead
CO70doc 00071DI6 high latchLatched high state of the input; read with function 01.BITRead
CO71doc 00072DI7 high latchLatched high state of the input; read with function 01.BITRead
CO96doc 00097DI0 low latchLatched low state of the input; read with function 01.BITRead
CO97doc 00098DI1 low latchLatched low state of the input; read with function 01.BITRead
CO98doc 00099DI2 low latchLatched low state of the input; read with function 01.BITRead
CO99doc 00100DI3 low latchLatched low state of the input; read with function 01.BITRead
CO100doc 00101DI4 low latchLatched low state of the input; read with function 01.BITRead
CO101doc 00102DI5 low latchLatched low state of the input; read with function 01.BITRead
CO102doc 00103DI6 low latchLatched low state of the input; read with function 01.BITRead
CO103doc 00104DI7 low latchLatched low state of the input; read with function 01.BITRead
CO128doc 00129DO0 safe valueOutput state applied on a host watchdog timeout.BITRead/write
CO129doc 00130DO1 safe valueOutput state applied on a host watchdog timeout.BITRead/write
CO130doc 00131DO2 safe valueOutput state applied on a host watchdog timeout.BITRead/write
CO131doc 00132DO3 safe valueOutput state applied on a host watchdog timeout.BITRead/write
CO132doc 00133DO4 safe valueOutput state applied on a host watchdog timeout.BITRead/write
CO133doc 00134DO5 safe valueOutput state applied on a host watchdog timeout.BITRead/write
CO134doc 00135DO6 safe valueOutput state applied on a host watchdog timeout.BITRead/write
CO135doc 00136DO7 safe valueOutput state applied on a host watchdog timeout.BITRead/write
CO160doc 00161DO0 power-on valueOutput state at power-up.BITRead/write
CO161doc 00162DO1 power-on valueOutput state at power-up.BITRead/write
CO162doc 00163DO2 power-on valueOutput state at power-up.BITRead/write
CO163doc 00164DO3 power-on valueOutput state at power-up.BITRead/write
CO164doc 00165DO4 power-on valueOutput state at power-up.BITRead/write
CO165doc 00166DO5 power-on valueOutput state at power-up.BITRead/write
CO166doc 00167DO6 power-on valueOutput state at power-up.BITRead/write
CO167doc 00168DO7 power-on valueOutput state at power-up.BITRead/write
CO256doc 00257ProtocolBITRead/write0 = DCON; 1 = Modbus RTU
CO257doc 00258Modbus modeBITRead/write0 = Modbus RTU; 1 = Modbus ASCII
CO259doc 00260Host watchdog mode1 lets AO/DO commands clear a watchdog timeout.BITRead/write0 = Same as I-7000; 1 = AO/DO command clears timeout
CO260doc 00261Host watchdog enableBITRead/write0 = Disabled; 1 = Enabled
CO263doc 00264Clear latched DIOWrite ON to clear all latched values.BITWrite
CO264doc 00265DI active stateBITRead/write0 = Normal; 1 = Inverse
CO265doc 00266DO active stateBITRead/write0 = Normal; 1 = Inverse
CO269doc 00270Host watchdog timeout statusWrite ON to clear the timeout status.BITRead/write
CO272doc 00273Reset status1 on the first read after power-up.BITRead
CO512doc 00513Clear DI0 counterWrite ON to reset the counter.BITWrite
CO513doc 00514Clear DI1 counterWrite ON to reset the counter.BITWrite
CO514doc 00515Clear DI2 counterWrite ON to reset the counter.BITWrite
CO515doc 00516Clear DI3 counterWrite ON to reset the counter.BITWrite
CO516doc 00517Clear DI4 counterWrite ON to reset the counter.BITWrite
CO517doc 00518Clear DI5 counterWrite ON to reset the counter.BITWrite
CO518doc 00519Clear DI6 counterWrite ON to reset the counter.BITWrite
CO519doc 00520Clear DI7 counterWrite ON to reset the counter.BITWrite
DI32doc 10033DI0 inputDigital input channel 0 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7).BITRead
DI33doc 10034DI1 inputDigital input channel 1 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7).BITRead
DI34doc 10035DI2 inputDigital input channel 2 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7).BITRead
DI35doc 10036DI3 inputDigital input channel 3 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7).BITRead
DI36doc 10037DI4 inputDigital input channel 4 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7).BITRead
DI37doc 10038DI5 inputDigital input channel 5 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7).BITRead
DI38doc 10039DI6 inputDigital input channel 6 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7).BITRead
DI39doc 10040DI7 inputDigital input channel 7 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7).BITRead
IR0doc 30001DI0 counterInput pulse counter, 0-65535.UINT16Read
IR1doc 30002DI1 counterInput pulse counter, 0-65535.UINT16Read
IR2doc 30003DI2 counterInput pulse counter, 0-65535.UINT16Read
IR3doc 30004DI3 counterInput pulse counter, 0-65535.UINT16Read
IR4doc 30005DI4 counterInput pulse counter, 0-65535.UINT16Read
IR5doc 30006DI5 counterInput pulse counter, 0-65535.UINT16Read
IR6doc 30007DI6 counterInput pulse counter, 0-65535.UINT16Read
IR7doc 30008DI7 counterInput pulse counter, 0-65535.UINT16Read
HR0doc 40001DI0 counter (holding copy)Same counter readable with function 03.UINT16Read
HR1doc 40002DI1 counter (holding copy)Same counter readable with function 03.UINT16Read
HR2doc 40003DI2 counter (holding copy)Same counter readable with function 03.UINT16Read
HR3doc 40004DI3 counter (holding copy)Same counter readable with function 03.UINT16Read
HR4doc 40005DI4 counter (holding copy)Same counter readable with function 03.UINT16Read
HR5doc 40006DI5 counter (holding copy)Same counter readable with function 03.UINT16Read
HR6doc 40007DI6 counter (holding copy)Same counter readable with function 03.UINT16Read
HR7doc 40008DI7 counter (holding copy)Same counter readable with function 03.UINT16Read
HR484doc 40485Module address1-247.UINT16Read
HR485doc 40486Baud rate and parityBits 5:0 baud code 3-10 (1200-115200); bits 7:6 parity/stop.UINT16Read
HR487doc 40488Modbus response delay0-30 ms.UINT16msRead
HR488doc 40489Host watchdog timeout0-255 in 0.1 s.UINT16× 0.1sRead
HR491doc 40492Host watchdog timeout countNumber of watchdog timeouts.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)

What Modbus registers does the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) have?

This map lists 94 registers: 65 coils, 8 discrete inputs, 8 input registers, 13 holding registers. 40 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The address table uses Modicon numbers (00001, 10033, 30001, 40481). The function-code sections give the matching wire addresses: DO readback starts at 0x0000 (00001), DI at 0x0020 (00033/10033), latch clear at 0x0107 (00264) and counter clear at 0x0200 (00513). Subtract 1 from the 5-digit number.

What are the minimum Modbus registers to integrate the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)?

Start with CO 0 DO0 output (DO0 output); DI 32 DI0 input (DI0 input); IR 0 DI0 counter (DI0 counter); CO 512 Clear DI0 counter (Clear DI0 counter); CO 260 Host watchdog enable (Host watchdog enable); CO 269 Host watchdog timeout status (Host watchdog timeout status).

How do I enable Modbus control of the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)?

Factory default is already Modbus RTU, address 1, 9600 bps. Coil 00257 switches between DCON and Modbus; address and baud changes are made with the DCON utility or function 70.

What happens when the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) loses Modbus communication?

Host watchdog: enable with coil 00261, timeout 0-255 x 0.1 s in 40489. On timeout the outputs go to their safe values (00129-00136); clear the timeout status with coil 00270.

Where is the official ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) Modbus documentation?

The source is tM Series DIO User Manual (Rev A1.4 (7PH-013-A14)), revision 2018-12-28, published free by ICP DAS at https://www.icpdas.com/tw/download/file.php?num=7951.

More ICP DAS Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: tM Series DIO User Manual · Rev A1.4 (7PH-013-A14) · rev. 2018-12-28. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.