- Home
- Modbus register maps
- ICP DAS
- tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
Sensor / remote digital I/O module · Modbus register map
ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) Modbus register map
Updated 17 November 2026
ICP DAS tM modules are small DIN-rail RS-485 I/O modules that speak DCON or Modbus RTU. The DIO models covered here give digital outputs as coils, digital inputs as discrete inputs, 16-bit input counters, latch bits and module settings. Only the channels a model actually has respond.
This page lists 94 Modbus registers for the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) — 40 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ICP DAS’s own free documentation (linked below) and checked against it.
- Manufacturer
- ICP DAS
- Model
- tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
- Equipment type
- Sensor / remote digital I/O module
- Registers
- 94 (40 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 1
- Default serial
- 9600 baud
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- tM-P4C4, tM-C8, tM-P8
Integration notes: ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
Switch the module to Modbus RTU, then read inputs with function 02 from wire 32 and drive outputs with function 05 at wire 0-7. Counters are on function 04 from wire 0.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 0 | DO0 output | BIT | DO0 output | Read/write |
| DI 32 | DI0 input | BIT | DI0 input | Read |
| IR 0 | DI0 counter | UINT16 | DI0 counter | Read |
| CO 512 | Clear DI0 counter | BIT | Clear DI0 counter | Write |
| CO 260 | Host watchdog enable | BIT | Host watchdog enable | Read/write |
| CO 269 | Host watchdog timeout status | BIT | Host watchdog timeout status | Read/write |
Enable Modbus control & writes
Factory default is already Modbus RTU, address 1, 9600 bps. Coil 00257 switches between DCON and Modbus; address and baud changes are made with the DCON utility or function 70.
Communication loss & watchdog
Host watchdog: enable with coil 00261, timeout 0-255 x 0.1 s in 40489. On timeout the outputs go to their safe values (00129-00136); clear the timeout status with coil 00270.
Byte order & addressing
- No function 06/16: use 05/15 for coils; settings registers are read only over standard Modbus.
- Inputs can be read as coils (00033+) or discrete inputs (10033+).
Network setup
- Address 1-247 and baud/parity are module settings (40485/40486); use the DCON utility, function 70 or INIT mode to change them.
- RS-485.
Watch out for
- Each model accepts only the channel addresses listed for it in the function-code sections.
- Counters are 16-bit with a maximum of 65535.
- After a host watchdog timeout the outputs hold their safe values and ignore DO writes until the timeout status (coil 00270) is cleared; the status survives a power cycle.
ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | DO0 output | Digital output channel 0 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7). | BIT | Read/write | ||||
| CO | 1doc 00002 | DO1 output | Digital output channel 1 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7). | BIT | Read/write | ||||
| CO | 2doc 00003 | DO2 output | Digital output channel 2 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7). | BIT | Read/write | ||||
| CO | 3doc 00004 | DO3 output | Digital output channel 3 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7). | BIT | Read/write | ||||
| CO | 4doc 00005 | DO4 output | Digital output channel 4 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7). | BIT | Read/write | ||||
| CO | 5doc 00006 | DO5 output | Digital output channel 5 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7). | BIT | Read/write | ||||
| CO | 6doc 00007 | DO6 output | Digital output channel 6 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7). | BIT | Read/write | ||||
| CO | 7doc 00008 | DO7 output | Digital output channel 7 (tM-P4C4: DO0-DO3, tM-C8: DO0-DO7). | BIT | Read/write | ||||
| CO | 32doc 00033 | DI0 input (coil copy) | Same DI value readable with function 01. | BIT | Read | ||||
| CO | 33doc 00034 | DI1 input (coil copy) | Same DI value readable with function 01. | BIT | Read | ||||
| CO | 34doc 00035 | DI2 input (coil copy) | Same DI value readable with function 01. | BIT | Read | ||||
| CO | 35doc 00036 | DI3 input (coil copy) | Same DI value readable with function 01. | BIT | Read | ||||
| CO | 36doc 00037 | DI4 input (coil copy) | Same DI value readable with function 01. | BIT | Read | ||||
| CO | 37doc 00038 | DI5 input (coil copy) | Same DI value readable with function 01. | BIT | Read | ||||
| CO | 38doc 00039 | DI6 input (coil copy) | Same DI value readable with function 01. | BIT | Read | ||||
| CO | 39doc 00040 | DI7 input (coil copy) | Same DI value readable with function 01. | BIT | Read | ||||
| CO | 64doc 00065 | DI0 high latch | Latched high state of the input; read with function 01. | BIT | Read | ||||
| CO | 65doc 00066 | DI1 high latch | Latched high state of the input; read with function 01. | BIT | Read | ||||
| CO | 66doc 00067 | DI2 high latch | Latched high state of the input; read with function 01. | BIT | Read | ||||
| CO | 67doc 00068 | DI3 high latch | Latched high state of the input; read with function 01. | BIT | Read | ||||
| CO | 68doc 00069 | DI4 high latch | Latched high state of the input; read with function 01. | BIT | Read | ||||
| CO | 69doc 00070 | DI5 high latch | Latched high state of the input; read with function 01. | BIT | Read | ||||
| CO | 70doc 00071 | DI6 high latch | Latched high state of the input; read with function 01. | BIT | Read | ||||
| CO | 71doc 00072 | DI7 high latch | Latched high state of the input; read with function 01. | BIT | Read | ||||
| CO | 96doc 00097 | DI0 low latch | Latched low state of the input; read with function 01. | BIT | Read | ||||
| CO | 97doc 00098 | DI1 low latch | Latched low state of the input; read with function 01. | BIT | Read | ||||
| CO | 98doc 00099 | DI2 low latch | Latched low state of the input; read with function 01. | BIT | Read | ||||
| CO | 99doc 00100 | DI3 low latch | Latched low state of the input; read with function 01. | BIT | Read | ||||
| CO | 100doc 00101 | DI4 low latch | Latched low state of the input; read with function 01. | BIT | Read | ||||
| CO | 101doc 00102 | DI5 low latch | Latched low state of the input; read with function 01. | BIT | Read | ||||
| CO | 102doc 00103 | DI6 low latch | Latched low state of the input; read with function 01. | BIT | Read | ||||
| CO | 103doc 00104 | DI7 low latch | Latched low state of the input; read with function 01. | BIT | Read | ||||
| CO | 128doc 00129 | DO0 safe value | Output state applied on a host watchdog timeout. | BIT | Read/write | ||||
| CO | 129doc 00130 | DO1 safe value | Output state applied on a host watchdog timeout. | BIT | Read/write | ||||
| CO | 130doc 00131 | DO2 safe value | Output state applied on a host watchdog timeout. | BIT | Read/write | ||||
| CO | 131doc 00132 | DO3 safe value | Output state applied on a host watchdog timeout. | BIT | Read/write | ||||
| CO | 132doc 00133 | DO4 safe value | Output state applied on a host watchdog timeout. | BIT | Read/write | ||||
| CO | 133doc 00134 | DO5 safe value | Output state applied on a host watchdog timeout. | BIT | Read/write | ||||
| CO | 134doc 00135 | DO6 safe value | Output state applied on a host watchdog timeout. | BIT | Read/write | ||||
| CO | 135doc 00136 | DO7 safe value | Output state applied on a host watchdog timeout. | BIT | Read/write | ||||
| CO | 160doc 00161 | DO0 power-on value | Output state at power-up. | BIT | Read/write | ||||
| CO | 161doc 00162 | DO1 power-on value | Output state at power-up. | BIT | Read/write | ||||
| CO | 162doc 00163 | DO2 power-on value | Output state at power-up. | BIT | Read/write | ||||
| CO | 163doc 00164 | DO3 power-on value | Output state at power-up. | BIT | Read/write | ||||
| CO | 164doc 00165 | DO4 power-on value | Output state at power-up. | BIT | Read/write | ||||
| CO | 165doc 00166 | DO5 power-on value | Output state at power-up. | BIT | Read/write | ||||
| CO | 166doc 00167 | DO6 power-on value | Output state at power-up. | BIT | Read/write | ||||
| CO | 167doc 00168 | DO7 power-on value | Output state at power-up. | BIT | Read/write | ||||
| CO | 256doc 00257 | Protocol | BIT | Read/write | 0 = DCON; 1 = Modbus RTU | ||||
| CO | 257doc 00258 | Modbus mode | BIT | Read/write | 0 = Modbus RTU; 1 = Modbus ASCII | ||||
| CO | 259doc 00260 | Host watchdog mode | 1 lets AO/DO commands clear a watchdog timeout. | BIT | Read/write | 0 = Same as I-7000; 1 = AO/DO command clears timeout | |||
| CO | 260doc 00261 | Host watchdog enable | BIT | Read/write | 0 = Disabled; 1 = Enabled | ||||
| CO | 263doc 00264 | Clear latched DIO | Write ON to clear all latched values. | BIT | Write | ||||
| CO | 264doc 00265 | DI active state | BIT | Read/write | 0 = Normal; 1 = Inverse | ||||
| CO | 265doc 00266 | DO active state | BIT | Read/write | 0 = Normal; 1 = Inverse | ||||
| CO | 269doc 00270 | Host watchdog timeout status | Write ON to clear the timeout status. | BIT | Read/write | ||||
| CO | 272doc 00273 | Reset status | 1 on the first read after power-up. | BIT | Read | ||||
| CO | 512doc 00513 | Clear DI0 counter | Write ON to reset the counter. | BIT | Write | ||||
| CO | 513doc 00514 | Clear DI1 counter | Write ON to reset the counter. | BIT | Write | ||||
| CO | 514doc 00515 | Clear DI2 counter | Write ON to reset the counter. | BIT | Write | ||||
| CO | 515doc 00516 | Clear DI3 counter | Write ON to reset the counter. | BIT | Write | ||||
| CO | 516doc 00517 | Clear DI4 counter | Write ON to reset the counter. | BIT | Write | ||||
| CO | 517doc 00518 | Clear DI5 counter | Write ON to reset the counter. | BIT | Write | ||||
| CO | 518doc 00519 | Clear DI6 counter | Write ON to reset the counter. | BIT | Write | ||||
| CO | 519doc 00520 | Clear DI7 counter | Write ON to reset the counter. | BIT | Write | ||||
| DI | 32doc 10033 | DI0 input | Digital input channel 0 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7). | BIT | Read | ||||
| DI | 33doc 10034 | DI1 input | Digital input channel 1 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7). | BIT | Read | ||||
| DI | 34doc 10035 | DI2 input | Digital input channel 2 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7). | BIT | Read | ||||
| DI | 35doc 10036 | DI3 input | Digital input channel 3 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7). | BIT | Read | ||||
| DI | 36doc 10037 | DI4 input | Digital input channel 4 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7). | BIT | Read | ||||
| DI | 37doc 10038 | DI5 input | Digital input channel 5 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7). | BIT | Read | ||||
| DI | 38doc 10039 | DI6 input | Digital input channel 6 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7). | BIT | Read | ||||
| DI | 39doc 10040 | DI7 input | Digital input channel 7 (tM-P4C4: DI0-DI3, tM-P8: DI0-DI7). | BIT | Read | ||||
| IR | 0doc 30001 | DI0 counter | Input pulse counter, 0-65535. | UINT16 | Read | ||||
| IR | 1doc 30002 | DI1 counter | Input pulse counter, 0-65535. | UINT16 | Read | ||||
| IR | 2doc 30003 | DI2 counter | Input pulse counter, 0-65535. | UINT16 | Read | ||||
| IR | 3doc 30004 | DI3 counter | Input pulse counter, 0-65535. | UINT16 | Read | ||||
| IR | 4doc 30005 | DI4 counter | Input pulse counter, 0-65535. | UINT16 | Read | ||||
| IR | 5doc 30006 | DI5 counter | Input pulse counter, 0-65535. | UINT16 | Read | ||||
| IR | 6doc 30007 | DI6 counter | Input pulse counter, 0-65535. | UINT16 | Read | ||||
| IR | 7doc 30008 | DI7 counter | Input pulse counter, 0-65535. | UINT16 | Read | ||||
| HR | 0doc 40001 | DI0 counter (holding copy) | Same counter readable with function 03. | UINT16 | Read | ||||
| HR | 1doc 40002 | DI1 counter (holding copy) | Same counter readable with function 03. | UINT16 | Read | ||||
| HR | 2doc 40003 | DI2 counter (holding copy) | Same counter readable with function 03. | UINT16 | Read | ||||
| HR | 3doc 40004 | DI3 counter (holding copy) | Same counter readable with function 03. | UINT16 | Read | ||||
| HR | 4doc 40005 | DI4 counter (holding copy) | Same counter readable with function 03. | UINT16 | Read | ||||
| HR | 5doc 40006 | DI5 counter (holding copy) | Same counter readable with function 03. | UINT16 | Read | ||||
| HR | 6doc 40007 | DI6 counter (holding copy) | Same counter readable with function 03. | UINT16 | Read | ||||
| HR | 7doc 40008 | DI7 counter (holding copy) | Same counter readable with function 03. | UINT16 | Read | ||||
| HR | 484doc 40485 | Module address | 1-247. | UINT16 | Read | ||||
| HR | 485doc 40486 | Baud rate and parity | Bits 5:0 baud code 3-10 (1200-115200); bits 7:6 parity/stop. | UINT16 | Read | ||||
| HR | 487doc 40488 | Modbus response delay | 0-30 ms. | UINT16 | ms | Read | |||
| HR | 488doc 40489 | Host watchdog timeout | 0-255 in 0.1 s. | UINT16 | × 0.1 | s | Read | ||
| HR | 491doc 40492 | Host watchdog timeout count | Number of watchdog timeouts. | UINT16 | Read |
Notes on this map
- Channels are listed 0-7. tM-P4C4 has DO0-DO3 and DI0-DI3, tM-C8 has DO0-DO7 only, tM-P8 has DI0-DI7 only; each function-code section lists only the channel addresses valid for each model.
- Supported function codes are 01, 02, 03, 04, 05, 15 and 70 (module settings). There is no 06 or 16, so the holding registers 40485-40492, although marked R/W in the table, cannot be written with standard Modbus writes; they are listed as read only. Change settings with the DCON utility or function 70.
- Counters are 16-bit (maximum 65535) and can be read with function 03 or 04.
- DI latch values are listed as coils (00065-00072 high, 00097-00104 low) because function 01 accepts 0x0040/0x0060 while function 02 accepts only 0x0020-0x003F; the table's 10065/10097 copies are not listed. Latched DO values (00073-00080, 00105-00112) are left out.
- Firmware version and module name (40481-40484, low word first) are left out because their encoding is not described.
- In INIT mode (INIT switch) the module starts at address 00, 9600 bps, DCON protocol, for recovery.
- The address table marks the safe-value, power-on-value and settings coils R/W, but the function 05/15 sections list only the DO channels, 0x0107 and 0x0200+ as valid outputs. If a write to a settings coil is refused, use the DCON utility or function 70.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
What Modbus registers does the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) have?
This map lists 94 registers: 65 coils, 8 discrete inputs, 8 input registers, 13 holding registers. 40 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The address table uses Modicon numbers (00001, 10033, 30001, 40481). The function-code sections give the matching wire addresses: DO readback starts at 0x0000 (00001), DI at 0x0020 (00033/10033), latch clear at 0x0107 (00264) and counter clear at 0x0200 (00513). Subtract 1 from the 5-digit number.
What are the minimum Modbus registers to integrate the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)?
Start with CO 0 DO0 output (DO0 output); DI 32 DI0 input (DI0 input); IR 0 DI0 counter (DI0 counter); CO 512 Clear DI0 counter (Clear DI0 counter); CO 260 Host watchdog enable (Host watchdog enable); CO 269 Host watchdog timeout status (Host watchdog timeout status).
How do I enable Modbus control of the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)?
Factory default is already Modbus RTU, address 1, 9600 bps. Coil 00257 switches between DCON and Modbus; address and baud changes are made with the DCON utility or function 70.
What happens when the ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) loses Modbus communication?
Host watchdog: enable with coil 00261, timeout 0-255 x 0.1 s in 40489. On timeout the outputs go to their safe values (00129-00136); clear the timeout status with coil 00270.
Where is the official ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU) Modbus documentation?
The source is tM Series DIO User Manual (Rev A1.4 (7PH-013-A14)), revision 2018-12-28, published free by ICP DAS at https://www.icpdas.com/tw/download/file.php?num=7951.
More ICP DAS Modbus register maps
- Sensor (thermistor input module)
ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)
M-7005 in Modbus RTU mode, per I-7005/M-7005 User Manual Rev B2.4 (7MH-018-B24). The I-7005 uses the DCON protocol and is not covered.
Also known as: M-7005, M7005, I-7005/M-7005 - Sensor (counter/frequency input module)
ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
ICP DAS M-7080 and M-7080B two-channel 32-bit counter/frequency modules with two digital outputs, in Modbus RTU mode.
Also known as: M-7080, M-7080B, M7080, M7080B - Sensor (PWM output and counter input module)
ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)
ICP DAS M-7088 eight-channel PWM output module with eight digital inputs and counters, Modbus RTU firmware.
Also known as: M-7088, M7088
Other remote i/o modules register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS52 resistance input module
Unipi Extension xS52 RS-485 module per the Unipi Extension xS52 Modbus map v2.0.
Also known as: Unipi Extension xS52, xS52 - Sensor / remote I/O module
Brainboxes ED-588 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-588 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-588, ED588 - Sensor (remote I/O module)
Moxa ioLogik R1214 RS-485 remote I/O
ioLogik R1214 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1214, R1214, R1214-T - Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2
All remote i/o modules Modbus register maps →
Source: tM Series DIO User Manual · Rev A1.4 (7PH-013-A14) · rev. 2018-12-28. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.