- M-7088 8-channel PWM output / counter input module (Modbus RTU)
Sensor (PWM output and counter input module) · Modbus register map
ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU) Modbus register map
Updated 19 November 2026
The M-7088 is an RS-485 remote I/O module with eight PWM outputs and eight digital inputs that also count pulses. Over Modbus RTU the PWM duty cycle, frequency and burst settings are holding registers, PWM start/stop and modes are coils, and the 32-bit input counts are input registers stored low word first.
This page lists 80 Modbus registers for the ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU) — 63 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ICP DAS’s own free documentation (linked below) and checked against it.
- Manufacturer
- ICP DAS
- Model
- M-7088 8-channel PWM output / counter input module (Modbus RTU)
- Equipment type
- Sensor (PWM output and counter input module)
- Registers
- 80 (63 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- M-7088, M7088
- Source document
- M-7000 Series Address Mapping Table · V1.18 · rev. 2025-09
Integration notes: ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)
Set a channel's frequency (40737+, 32-bit low word first) and duty cycle (40705+, 0.1 % steps), then start it with its PWM status coil (00001+). Read input registers 0-15 for the eight 32-bit pulse counts.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 704 | PWM duty cycle channel 0 | UINT16 | PWM duty channel 0 | Read/write |
| HR 736 | PWM frequency channel 0 | UINT32 CDAB | PWM frequency channel 0 | Read/write |
| CO 0 | PWM status channel 0 | BIT | PWM start/stop channel 0 | Read/write |
| CO 864 | PWM mode channel 0 | BIT | PWM burst/continuous channel 0 | Read/write |
| IR 0 | DI count channel 0 | UINT32 CDAB | DI count channel 0 | Read |
| DI 32 | DI status channel 0 | BIT | DI status channel 0 | Read |
Enable Modbus control & writes
The module must run the Modbus RTU protocol (coil 00257 = 1, factory default 1).
Communication loss & watchdog
Host watchdog: enable with coil 00261, timeout in 40489 (0.1 s steps, factory 25.5 s); coil 00270 shows and clears a timeout.
Byte order & addressing
- 32-bit values are low word first (CDAB).
- Duty cycle is in 0.1 % steps (500 = 50.0 %).
Network setup
- Module address in 40485 (1-247); baud and parity code in 40486.
Watch out for
- Coil 00260 picks the host watchdog mode: in the new mode an AO or DO command also clears the watchdog timeout status.
ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | PWM status channel 0 | BIT | Read/write | 0 = Stopped; 1 = Started | ||||
| CO | 1doc 00002 | PWM status channel 1 | BIT | Read/write | 0 = Stopped; 1 = Started | ||||
| CO | 2doc 00003 | PWM status channel 2 | BIT | Read/write | 0 = Stopped; 1 = Started | ||||
| CO | 3doc 00004 | PWM status channel 3 | BIT | Read/write | 0 = Stopped; 1 = Started | ||||
| CO | 4doc 00005 | PWM status channel 4 | BIT | Read/write | 0 = Stopped; 1 = Started | ||||
| CO | 5doc 00006 | PWM status channel 5 | BIT | Read/write | 0 = Stopped; 1 = Started | ||||
| CO | 6doc 00007 | PWM status channel 6 | BIT | Read/write | 0 = Stopped; 1 = Started | ||||
| CO | 7doc 00008 | PWM status channel 7 | BIT | Read/write | 0 = Stopped; 1 = Started | ||||
| CO | 64doc 00065 | DI counter overflow channel 0 | Write 1 to clear. | BIT | Read/write | 0 = Normal; 1 = Overflow | |||
| CO | 65doc 00066 | DI counter overflow channel 1 | Write 1 to clear. | BIT | Read/write | 0 = Normal; 1 = Overflow | |||
| CO | 66doc 00067 | DI counter overflow channel 2 | Write 1 to clear. | BIT | Read/write | 0 = Normal; 1 = Overflow | |||
| CO | 67doc 00068 | DI counter overflow channel 3 | Write 1 to clear. | BIT | Read/write | 0 = Normal; 1 = Overflow | |||
| CO | 68doc 00069 | DI counter overflow channel 4 | Write 1 to clear. | BIT | Read/write | 0 = Normal; 1 = Overflow | |||
| CO | 69doc 00070 | DI counter overflow channel 5 | Write 1 to clear. | BIT | Read/write | 0 = Normal; 1 = Overflow | |||
| CO | 70doc 00071 | DI counter overflow channel 6 | Write 1 to clear. | BIT | Read/write | 0 = Normal; 1 = Overflow | |||
| CO | 71doc 00072 | DI counter overflow channel 7 | Write 1 to clear. | BIT | Read/write | 0 = Normal; 1 = Overflow | |||
| CO | 260doc 00261 | Host watchdog enable | BIT | Read/write | 0 = Disabled; 1 = Enabled | ||||
| CO | 265doc 00266 | Clear all DI counters | Write 1. | BIT | Write | ||||
| CO | 269doc 00270 | Host watchdog timeout status | Write 1 to clear. | BIT | Read/write | 0 = Normal; 1 = Host watchdog timeout | |||
| CO | 864doc 00865 | PWM mode channel 0 | BIT | Read/write | 0 = Burst; 1 = Continuous | ||||
| CO | 865doc 00866 | PWM mode channel 1 | BIT | Read/write | 0 = Burst; 1 = Continuous | ||||
| CO | 866doc 00867 | PWM mode channel 2 | BIT | Read/write | 0 = Burst; 1 = Continuous | ||||
| CO | 867doc 00868 | PWM mode channel 3 | BIT | Read/write | 0 = Burst; 1 = Continuous | ||||
| CO | 868doc 00869 | PWM mode channel 4 | BIT | Read/write | 0 = Burst; 1 = Continuous | ||||
| CO | 869doc 00870 | PWM mode channel 5 | BIT | Read/write | 0 = Burst; 1 = Continuous | ||||
| CO | 870doc 00871 | PWM mode channel 6 | BIT | Read/write | 0 = Burst; 1 = Continuous | ||||
| CO | 871doc 00872 | PWM mode channel 7 | BIT | Read/write | 0 = Burst; 1 = Continuous | ||||
| DI | 32doc 10033 | DI status channel 0 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 33doc 10034 | DI status channel 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 34doc 10035 | DI status channel 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 35doc 10036 | DI status channel 3 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 36doc 10037 | DI status channel 4 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 37doc 10038 | DI status channel 5 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 38doc 10039 | DI status channel 6 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 39doc 10040 | DI status channel 7 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 272doc 10273 | Reset status | 1 on the first read after power-on. | BIT | Read | 0 = Not first read; 1 = First read after power-on | |||
| IR | 0doc 30001 | DI count channel 0 | Low word at the lower address. | UINT32 | CDAB | Read | |||
| IR | 2doc 30003 | DI count channel 1 | Low word at the lower address. | UINT32 | CDAB | Read | |||
| IR | 4doc 30005 | DI count channel 2 | Low word at the lower address. | UINT32 | CDAB | Read | |||
| IR | 6doc 30007 | DI count channel 3 | Low word at the lower address. | UINT32 | CDAB | Read | |||
| IR | 8doc 30009 | DI count channel 4 | Low word at the lower address. | UINT32 | CDAB | Read | |||
| IR | 10doc 30011 | DI count channel 5 | Low word at the lower address. | UINT32 | CDAB | Read | |||
| IR | 12doc 30013 | DI count channel 6 | Low word at the lower address. | UINT32 | CDAB | Read | |||
| IR | 14doc 30015 | DI count channel 7 | Low word at the lower address. | UINT32 | CDAB | Read | |||
| HR | 64doc 40065 | Max DI count channel 0 | Low word at the lower address. | UINT32 | CDAB | Read/write | |||
| HR | 66doc 40067 | Max DI count channel 1 | Low word at the lower address. | UINT32 | CDAB | Read/write | |||
| HR | 68doc 40069 | Max DI count channel 2 | Low word at the lower address. | UINT32 | CDAB | Read/write | |||
| HR | 70doc 40071 | Max DI count channel 3 | Low word at the lower address. | UINT32 | CDAB | Read/write | |||
| HR | 72doc 40073 | Max DI count channel 4 | Low word at the lower address. | UINT32 | CDAB | Read/write | |||
| HR | 74doc 40075 | Max DI count channel 5 | Low word at the lower address. | UINT32 | CDAB | Read/write | |||
| HR | 76doc 40077 | Max DI count channel 6 | Low word at the lower address. | UINT32 | CDAB | Read/write | |||
| HR | 78doc 40079 | Max DI count channel 7 | Low word at the lower address. | UINT32 | CDAB | Read/write | |||
| HR | 484doc 40485 | Module address | 1-247. | UINT16 | Read/write | ||||
| HR | 485doc 40486 | Baud rate and parity | Bits 0-5 baud code (03 = 1200 ... 06 = 9600 ... 0A = 115200); bits 6-7 parity/stop. | UINT16 | Read/write | ||||
| HR | 487doc 40488 | Modbus response delay | 0-30 ms. | UINT16 | ms | Read/write | |||
| HR | 488doc 40489 | Host watchdog timeout | 0-25.5 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 704doc 40705 | PWM duty cycle channel 0 | 0.1-99.9 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 705doc 40706 | PWM duty cycle channel 1 | 0.1-99.9 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 706doc 40707 | PWM duty cycle channel 2 | 0.1-99.9 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 707doc 40708 | PWM duty cycle channel 3 | 0.1-99.9 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 708doc 40709 | PWM duty cycle channel 4 | 0.1-99.9 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 709doc 40710 | PWM duty cycle channel 5 | 0.1-99.9 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 710doc 40711 | PWM duty cycle channel 6 | 0.1-99.9 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 711doc 40712 | PWM duty cycle channel 7 | 0.1-99.9 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 736doc 40737 | PWM frequency channel 0 | 1-500000; low word at the lower address. | UINT32 | CDAB | Hz | Read/write | ||
| HR | 738doc 40739 | PWM frequency channel 1 | 1-500000; low word at the lower address. | UINT32 | CDAB | Hz | Read/write | ||
| HR | 740doc 40741 | PWM frequency channel 2 | 1-500000; low word at the lower address. | UINT32 | CDAB | Hz | Read/write | ||
| HR | 742doc 40743 | PWM frequency channel 3 | 1-500000; low word at the lower address. | UINT32 | CDAB | Hz | Read/write | ||
| HR | 744doc 40745 | PWM frequency channel 4 | 1-500000; low word at the lower address. | UINT32 | CDAB | Hz | Read/write | ||
| HR | 746doc 40747 | PWM frequency channel 5 | 1-500000; low word at the lower address. | UINT32 | CDAB | Hz | Read/write | ||
| HR | 748doc 40749 | PWM frequency channel 6 | 1-500000; low word at the lower address. | UINT32 | CDAB | Hz | Read/write | ||
| HR | 750doc 40751 | PWM frequency channel 7 | 1-500000; low word at the lower address. | UINT32 | CDAB | Hz | Read/write | ||
| HR | 800doc 40801 | PWM burst steps channel 0 | 1-65535; used in burst mode. | UINT16 | Read/write | ||||
| HR | 801doc 40802 | PWM burst steps channel 1 | 1-65535; used in burst mode. | UINT16 | Read/write | ||||
| HR | 802doc 40803 | PWM burst steps channel 2 | 1-65535; used in burst mode. | UINT16 | Read/write | ||||
| HR | 803doc 40804 | PWM burst steps channel 3 | 1-65535; used in burst mode. | UINT16 | Read/write | ||||
| HR | 804doc 40805 | PWM burst steps channel 4 | 1-65535; used in burst mode. | UINT16 | Read/write | ||||
| HR | 805doc 40806 | PWM burst steps channel 5 | 1-65535; used in burst mode. | UINT16 | Read/write | ||||
| HR | 806doc 40807 | PWM burst steps channel 6 | 1-65535; used in burst mode. | UINT16 | Read/write | ||||
| HR | 807doc 40808 | PWM burst steps channel 7 | 1-65535; used in burst mode. | UINT16 | Read/write |
Notes on this map
- The table states low word then high word for the DI counts, maximum counts and PWM frequency, so these are CDAB.
- Preset values (40097-40112) are left out: the table's example pairs 40097 with 40104, which contradicts the low/high pattern.
- Defaults come from the table: address 1 (40485) and baud/parity code 6 = 9600 bps, no parity, 1 stop bit (40486).
- PWM trigger, synchronisation, burst count readback, LED and EEPROM-save items are left out.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)
What Modbus registers does the ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU) have?
This map lists 80 registers: 27 coils, 9 discrete inputs, 8 input registers, 36 holding registers. 63 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table is titled 'M-7000 Address Mapping (Base 1)': 00001 coils, 10001 discrete inputs, 30001 input registers, 40001 holding registers. Subtract the table base for the wire address (40001 = holding register 0).
What byte order does the ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)?
Start with HR 704 PWM duty cycle channel 0 (PWM duty channel 0); HR 736 PWM frequency channel 0 (PWM frequency channel 0); CO 0 PWM status channel 0 (PWM start/stop channel 0); CO 864 PWM mode channel 0 (PWM burst/continuous channel 0); IR 0 DI count channel 0 (DI count channel 0); DI 32 DI status channel 0 (DI status channel 0).
How do I enable Modbus control of the ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)?
The module must run the Modbus RTU protocol (coil 00257 = 1, factory default 1).
What happens when the ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU) loses Modbus communication?
Host watchdog: enable with coil 00261, timeout in 40489 (0.1 s steps, factory 25.5 s); coil 00270 shows and clears a timeout.
Where is the official ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU) Modbus documentation?
The source is M-7000 Series Address Mapping Table (V1.18), revision 2025-09, published free by ICP DAS at https://www.icpdas.com/en/download/file.php?num=19906.
More ICP DAS Modbus register maps
- Sensor (thermistor input module)
ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)
M-7005 in Modbus RTU mode, per I-7005/M-7005 User Manual Rev B2.4 (7MH-018-B24). The I-7005 uses the DCON protocol and is not covered.
Also known as: M-7005, M7005, I-7005/M-7005 - Sensor (counter/frequency input module)
ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
ICP DAS M-7080 and M-7080B two-channel 32-bit counter/frequency modules with two digital outputs, in Modbus RTU mode.
Also known as: M-7080, M-7080B, M7080, M7080B - Sensor / remote digital I/O module
ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
tM-P4C4 (4 DI + 4 DO), tM-C8 (8 DO) and tM-P8 (8 DI) with the Modbus RTU protocol selected, per the tM Series DIO User Manual Rev A1.4.
Also known as: tM-P4C4, tM-C8, tM-P8
Other remote i/o modules register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS51 I/O module
Unipi Extension xS51 RS-485 module per the Unipi Extension xS51 Modbus map v2.0.
Also known as: Unipi Extension xS51, xS51 - Sensor / remote I/O module
Brainboxes ED-538 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-538 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-538, ED538 - Sensor (remote I/O module)
Moxa ioLogik R1212 RS-485 remote I/O
ioLogik R1212 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1212, R1212, R1212-T - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD
All remote i/o modules Modbus register maps →
Source: M-7000 Series Address Mapping Table · V1.18 · rev. 2025-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.