- M-7005 8-channel thermistor input module (Modbus RTU)
Sensor (thermistor input module) · Modbus register map
ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) Modbus register map
Updated 17 November 2026
The M-7005 is an RS-485 module with eight thermistor inputs and six digital outputs. In Modbus RTU mode it gives each channel temperature as a 16-bit value (0.01-degree steps in engineering data format), an over/under-range or open-wire flag per channel, and the six digital outputs as coils.
This page lists 22 Modbus registers for the ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ICP DAS’s own free documentation (linked below) and checked against it.
- Manufacturer
- ICP DAS
- Model
- M-7005 8-channel thermistor input module (Modbus RTU)
- Equipment type
- Sensor (thermistor input module)
- Registers
- 22 (6 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- M-7005, M7005, I-7005/M-7005
- Source document
- I-7005/M-7005 User Manual · Rev B2.4 (7MH-018-B24)
Integration notes: ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)
Read input registers 0-7 with function 04 for the eight temperatures (x0.01 in engineering format) and discrete inputs 128-135 with function 02 for over/under range or open wire. Drive the six outputs with coils 0-5 (functions 01, 05, 15).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Temperature ch0 | INT16 | Channel 0 temperature | Read |
| IR 1 | Temperature ch1 | INT16 | Channel 1 temperature | Read |
| DI 128 | Over/under range status ch0 | BIT | Channel 0 over/under range or open wire | Read |
| DI 129 | Over/under range status ch1 | BIT | Channel 1 over/under range or open wire | Read |
| CO 0 | DO0 output | BIT | Digital output 0 | Read/write |
Enable Modbus control & writes
Select Modbus RTU with function 70 sub-function 06 (mode 1), or with the DCON configuration procedure in the manual. The new protocol and baud rate take effect after the next power-on.
Byte order & addressing
- Serial format is 8 data bits, no parity, 1 stop bit per section 3.
Network setup
- Baud 1200-115200, set with function 70 sub-function 06; module address 1-247 with sub-function 04; type code with sub-function 08.
Watch out for
- -32768 / +32767 mean under range / over range or an open thermistor.
- Function 02 starts at channel address 0x80 (128), not 0.
ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | DO0 output | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 1doc 00002 | DO1 output | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 2doc 00003 | DO2 output | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 3doc 00004 | DO3 output | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 4doc 00005 | DO4 output | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 5doc 00006 | DO5 output | BIT | Read/write | 0 = Off; 1 = On | ||||
| DI | 128doc 10129 | Over/under range status ch0 | BIT | Read | |||||
| DI | 129doc 10130 | Over/under range status ch1 | BIT | Read | |||||
| DI | 130doc 10131 | Over/under range status ch2 | BIT | Read | |||||
| DI | 131doc 10132 | Over/under range status ch3 | BIT | Read | |||||
| DI | 132doc 10133 | Over/under range status ch4 | BIT | Read | |||||
| DI | 133doc 10134 | Over/under range status ch5 | BIT | Read | |||||
| DI | 134doc 10135 | Over/under range status ch6 | BIT | Read | |||||
| DI | 135doc 10136 | Over/under range status ch7 | BIT | Read | |||||
| IR | 0doc 30001 | Temperature ch0 | x0.01 degrees in engineering data format; -32768/+32767 = under/over range. | INT16 | × 0.01 | Read | |||
| IR | 1doc 30002 | Temperature ch1 | x0.01 degrees in engineering data format; -32768/+32767 = under/over range. | INT16 | × 0.01 | Read | |||
| IR | 2doc 30003 | Temperature ch2 | x0.01 degrees in engineering data format; -32768/+32767 = under/over range. | INT16 | × 0.01 | Read | |||
| IR | 3doc 30004 | Temperature ch3 | x0.01 degrees in engineering data format; -32768/+32767 = under/over range. | INT16 | × 0.01 | Read | |||
| IR | 4doc 30005 | Temperature ch4 | x0.01 degrees in engineering data format; -32768/+32767 = under/over range. | INT16 | × 0.01 | Read | |||
| IR | 5doc 30006 | Temperature ch5 | x0.01 degrees in engineering data format; -32768/+32767 = under/over range. | INT16 | × 0.01 | Read | |||
| IR | 6doc 30007 | Temperature ch6 | x0.01 degrees in engineering data format; -32768/+32767 = under/over range. | INT16 | × 0.01 | Read | |||
| IR | 7doc 30008 | Temperature ch7 | x0.01 degrees in engineering data format; -32768/+32767 = under/over range. | INT16 | × 0.01 | Read |
Notes on this map
- Temperatures read as 0.01-degree steps only when the module data format is engineering units (manual section 3.8; e.g. type 60 spans -3000 to 24000 for -30.00 to +240.00). The format is set with the DCON configuration command or, per the address table, coil 00269; other formats (section 1.10) scale differently.
- Left out: the configuration coils in the address table (safe and power-on DO values 00097+, protocol 00257, host watchdog 00260/00261/00270, temperature scale 00267, data format 00269, alarm coils 00289-00352). The function descriptions for 01, 05 and 15 only accept channels 0-5, which contradicts the table, so these addresses are not certain to work.
- Left out: all 4xxxx holding registers (temperature copies, alarm limits, type codes, offsets, module address, baud, watchdog timeout, channel enable). The manual lists only functions 01, 02, 04, 05, 15 and 70, so there is no documented way to read or write them; settings are made with function 70 or DCON commands.
- Left out: the two-register resistance values 30865-30880 (word order not stated) and the duplicate 00129-00136 listing of the range flags.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)
What Modbus registers does the ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) have?
This map lists 22 registers: 6 coils, 8 discrete inputs, 8 input registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Section 3.7 is titled 'Address Mappings, Base 1': 00001 coils, 10001 discrete inputs, 30001 input and 40001 holding registers. Subtract the table base: 30001 is input register 0, 40225 is holding register 224.
What are the minimum Modbus registers to integrate the ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)?
Start with IR 0 Temperature ch0 (Channel 0 temperature); IR 1 Temperature ch1 (Channel 1 temperature); DI 128 Over/under range status ch0 (Channel 0 over/under range or open wire); DI 129 Over/under range status ch1 (Channel 1 over/under range or open wire); CO 0 DO0 output (Digital output 0).
How do I enable Modbus control of the ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)?
Select Modbus RTU with function 70 sub-function 06 (mode 1), or with the DCON configuration procedure in the manual. The new protocol and baud rate take effect after the next power-on.
Where is the official ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) Modbus documentation?
The source is I-7005/M-7005 User Manual (Rev B2.4 (7MH-018-B24)), published free by ICP DAS at https://www.icpdas.com/en/download/file.php?num=6184.
More ICP DAS Modbus register maps
- Sensor (counter/frequency input module)
ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
ICP DAS M-7080 and M-7080B two-channel 32-bit counter/frequency modules with two digital outputs, in Modbus RTU mode.
Also known as: M-7080, M-7080B, M7080, M7080B - Sensor (PWM output and counter input module)
ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)
ICP DAS M-7088 eight-channel PWM output module with eight digital inputs and counters, Modbus RTU firmware.
Also known as: M-7088, M7088 - Sensor / remote digital I/O module
ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
tM-P4C4 (4 DI + 4 DO), tM-C8 (8 DO) and tM-P8 (8 DI) with the Modbus RTU protocol selected, per the tM Series DIO User Manual Rev A1.4.
Also known as: tM-P4C4, tM-C8, tM-P8
Other remote i/o modules register maps
- Sensor (remote I/O module)
Moxa ioLogik R1240 RS-485 remote I/O
ioLogik R1240 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1240, R1240, R1240-T - Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (thermocouple input module)
Teracom TST320 2-channel thermocouple module with Modbus RTU
TST320 per the Teracom TST320 user manual Revision R1.6.
Also known as: TST320 - Sensor (Ethernet analog input module)
Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP)
BusWorks XT1211-000 (current) and XT1221-000 (voltage) per user's manual 8500951K.
Also known as: XT1211-000, XT1221-000, XT1211, XT1221, BusWorks XT1211, BusWorks XT1221 - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI
All remote i/o modules Modbus register maps →
Source: I-7005/M-7005 User Manual · Rev B2.4 (7MH-018-B24). Register numbers, types, scaling and units are reproduced as published; descriptions are our own.