ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The M-7005 is an RS-485 module with eight thermistor inputs and six digital outputs. In Modbus RTU mode it gives each channel temperature as a 16-bit value (0.01-degree steps in engineering data format), an over/under-range or open-wire flag per channel, and the six digital outputs as coils.

This page lists 22 Modbus registers for the ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ICP DAS’s own free documentation (linked below) and checked against it.

Manufacturer
ICP DAS
Model
M-7005 8-channel thermistor input module (Modbus RTU)
Equipment type
Sensor (thermistor input module)
Registers
22 (6 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
M-7005, M7005, I-7005/M-7005
Source document
I-7005/M-7005 User Manual · Rev B2.4 (7MH-018-B24)
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)

Integration in brief

Read input registers 0-7 with function 04 for the eight temperatures (x0.01 in engineering format) and discrete inputs 128-135 with function 02 for over/under range or open wire. Drive the six outputs with coils 0-5 (functions 01, 05, 15).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Temperature ch0INT16Channel 0 temperatureRead
IR 1Temperature ch1INT16Channel 1 temperatureRead
DI 128Over/under range status ch0BITChannel 0 over/under range or open wireRead
DI 129Over/under range status ch1BITChannel 1 over/under range or open wireRead
CO 0DO0 outputBITDigital output 0Read/write

Enable Modbus control & writes

Select Modbus RTU with function 70 sub-function 06 (mode 1), or with the DCON configuration procedure in the manual. The new protocol and baud rate take effect after the next power-on.

Byte order & addressing

Network setup

Watch out for

ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

22 of 22 shown
ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001DO0 outputBITRead/write0 = Off; 1 = On
CO1doc 00002DO1 outputBITRead/write0 = Off; 1 = On
CO2doc 00003DO2 outputBITRead/write0 = Off; 1 = On
CO3doc 00004DO3 outputBITRead/write0 = Off; 1 = On
CO4doc 00005DO4 outputBITRead/write0 = Off; 1 = On
CO5doc 00006DO5 outputBITRead/write0 = Off; 1 = On
DI128doc 10129Over/under range status ch0BITRead
DI129doc 10130Over/under range status ch1BITRead
DI130doc 10131Over/under range status ch2BITRead
DI131doc 10132Over/under range status ch3BITRead
DI132doc 10133Over/under range status ch4BITRead
DI133doc 10134Over/under range status ch5BITRead
DI134doc 10135Over/under range status ch6BITRead
DI135doc 10136Over/under range status ch7BITRead
IR0doc 30001Temperature ch0x0.01 degrees in engineering data format; -32768/+32767 = under/over range.INT16× 0.01Read
IR1doc 30002Temperature ch1x0.01 degrees in engineering data format; -32768/+32767 = under/over range.INT16× 0.01Read
IR2doc 30003Temperature ch2x0.01 degrees in engineering data format; -32768/+32767 = under/over range.INT16× 0.01Read
IR3doc 30004Temperature ch3x0.01 degrees in engineering data format; -32768/+32767 = under/over range.INT16× 0.01Read
IR4doc 30005Temperature ch4x0.01 degrees in engineering data format; -32768/+32767 = under/over range.INT16× 0.01Read
IR5doc 30006Temperature ch5x0.01 degrees in engineering data format; -32768/+32767 = under/over range.INT16× 0.01Read
IR6doc 30007Temperature ch6x0.01 degrees in engineering data format; -32768/+32767 = under/over range.INT16× 0.01Read
IR7doc 30008Temperature ch7x0.01 degrees in engineering data format; -32768/+32767 = under/over range.INT16× 0.01Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)

What Modbus registers does the ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) have?

This map lists 22 registers: 6 coils, 8 discrete inputs, 8 input registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Section 3.7 is titled 'Address Mappings, Base 1': 00001 coils, 10001 discrete inputs, 30001 input and 40001 holding registers. Subtract the table base: 30001 is input register 0, 40225 is holding register 224.

What are the minimum Modbus registers to integrate the ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)?

Start with IR 0 Temperature ch0 (Channel 0 temperature); IR 1 Temperature ch1 (Channel 1 temperature); DI 128 Over/under range status ch0 (Channel 0 over/under range or open wire); DI 129 Over/under range status ch1 (Channel 1 over/under range or open wire); CO 0 DO0 output (Digital output 0).

How do I enable Modbus control of the ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)?

Select Modbus RTU with function 70 sub-function 06 (mode 1), or with the DCON configuration procedure in the manual. The new protocol and baud rate take effect after the next power-on.

Where is the official ICP DAS M-7005 8-channel thermistor input module (Modbus RTU) Modbus documentation?

The source is I-7005/M-7005 User Manual (Rev B2.4 (7MH-018-B24)), published free by ICP DAS at https://www.icpdas.com/en/download/file.php?num=6184.

More ICP DAS Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: I-7005/M-7005 User Manual · Rev B2.4 (7MH-018-B24). Register numbers, types, scaling and units are reproduced as published; descriptions are our own.