Sensor (I/O module, 4 analog inputs) · Modbus register map
Seneca Z-4AI 4-channel analog input module Modbus register map
Updated 17 November 2026
The Z-4AI converts four ±10 V / ±20 mA single-ended inputs to normalized 16-bit values readable over RS-485 Modbus RTU. Everything is in single 16-bit holding registers: comms settings, per-channel filters and scaling, the four measurements and, from firmware 737, channel differences.
This page lists 34 Modbus registers for the Seneca Z-4AI 4-channel analog input module — 24 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seneca
- Model
- Z-4AI 4-channel analog input module
- Equipment type
- Sensor (I/O module, 4 analog inputs)
- Registers
- 34 (24 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Z-4AI
- Source document
- Z-4AI User Manual · MI002572-E
Integration notes: Seneca Z-4AI 4-channel analog input module
Read holding registers 40017-40020 (wire 16-19) for the four normalized inputs and 40016 for over/underflow bits.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 16 | IN1 normalized value | INT16 | IN1 | Read |
| HR 17 | IN2 normalized value | INT16 | IN2 | Read |
| HR 18 | IN3 normalized value | INT16 | IN3 | Read |
| HR 19 | IN4 normalized value | INT16 | IN4 | Read |
| HR 15 | Status | BITMAP16 | Status and over/underflow | Read/write |
Enable Modbus control & writes
Set address and baud with the SW1 DIP switches, or set all address switches OFF to use the values stored in 40002/40003.
Byte order & addressing
- 40002 packs baud code and address into one register.
- Input type must match the SW2 DIP switch for each channel.
Network setup
- SW1 switches 9-10 enable the RS-485 terminator.
- Write bit 7 of 40016 to store settings in EEPROM.
Watch out for
- Difference registers 40055-40058 exist only from firmware revision 737.
Seneca Z-4AI 4-channel analog input module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Machine ID | High byte = module ID code (default 0x07), low byte = module version. | UINT16 | Read | ||||
| HR | 1doc 40002 | Baud rate and address | High byte = baud code (0=4800,1=9600,2=19200,3=38400,4=57600,5=115200,6=1200,7=2400), low byte = address; EEPROM mode. | UINT16 | Read/write | ||||
| HR | 2doc 40003 | EEPROM flags | BITMAP16 | Read/write | bit 0 = Compatibility: 1 = Z-4AI-1, 0 = Z-4AI-0; bit 1 = Sampling time: 1 = 60 ms, 0 = 120 ms; bit 2 = RS-485 reply delay on; bit 3 = RS-485 parity on; bit 4 = Parity odd (0 = even) | ||||
| HR | 3doc 40004 | IN1 filter | Input filter level 0 (off) to 6 (strongest). | UINT16 | Read/write | ||||
| HR | 4doc 40005 | IN2 filter | Input filter level 0 (off) to 6 (strongest). | UINT16 | Read/write | ||||
| HR | 5doc 40006 | IN3 filter | Input filter level 0 (off) to 6 (strongest). | UINT16 | Read/write | ||||
| HR | 6doc 40007 | IN4 filter | Input filter level 0 (off) to 6 (strongest). | UINT16 | Read/write | ||||
| HR | 7doc 40008 | IN1 electrical end scale | ±10000 mV (voltage) or ±20000 µA (current); default 10000 mV. | INT16 | mV/µA | Read/write | |||
| HR | 8doc 40009 | IN2 electrical end scale | ±10000 mV (voltage) or ±20000 µA (current); default 10000 mV. | INT16 | mV/µA | Read/write | |||
| HR | 9doc 40010 | IN3 electrical end scale | ±10000 mV (voltage) or ±20000 µA (current); default 10000 mV. | INT16 | mV/µA | Read/write | |||
| HR | 10doc 40011 | IN4 electrical end scale | ±10000 mV (voltage) or ±20000 µA (current); default 10000 mV. | INT16 | mV/µA | Read/write | |||
| HR | 11doc 40012 | IN1 electrical start scale | Default 0 mV. | INT16 | mV/µA | Read/write | |||
| HR | 12doc 40013 | IN2 electrical start scale | Default 0 mV. | INT16 | mV/µA | Read/write | |||
| HR | 13doc 40014 | IN3 electrical start scale | Default 0 mV. | INT16 | mV/µA | Read/write | |||
| HR | 14doc 40015 | IN4 electrical start scale | Default 0 mV. | INT16 | mV/µA | Read/write | |||
| HR | 15doc 40016 | Status | BITMAP16 | Read/write | bit 0 = Reset module (write 1); bit 1 = Reset filter (write 1); bit 7 = Save configuration to EEPROM (write 1); bit 8 = IN1 overflow; bit 9 = IN1 underflow; bit 10 = IN2 overflow; bit 11 = IN2 underflow; bit 12 = IN3 overflow; bit 13 = IN3 underflow; bit 14 = IN4 overflow; bit 15 = IN4 underflow | ||||
| HR | 16doc 40017 | IN1 normalized value | Scaled between NSS and NES (fixed 0-10000 in Z-4AI-0 mode). | INT16 | Read | ||||
| HR | 17doc 40018 | IN2 normalized value | Scaled between NSS and NES (fixed 0-10000 in Z-4AI-0 mode). | INT16 | Read | ||||
| HR | 18doc 40019 | IN3 normalized value | Scaled between NSS and NES (fixed 0-10000 in Z-4AI-0 mode). | INT16 | Read | ||||
| HR | 19doc 40020 | IN4 normalized value | Scaled between NSS and NES (fixed 0-10000 in Z-4AI-0 mode). | INT16 | Read | ||||
| HR | 24doc 40025 | Input types | BITMAP16 | Read/write | bit 0 = IN1 current (0 = voltage); bit 1 = IN2 current; bit 2 = IN3 current; bit 3 = IN4 current | ||||
| HR | 25doc 40026 | IN1 normalized end scale | ±32000, default 10000. | INT16 | Read/write | ||||
| HR | 26doc 40027 | IN2 normalized end scale | ±32000, default 10000. | INT16 | Read/write | ||||
| HR | 27doc 40028 | IN3 normalized end scale | ±32000, default 10000. | INT16 | Read/write | ||||
| HR | 28doc 40029 | IN4 normalized end scale | ±32000, default 10000. | INT16 | Read/write | ||||
| HR | 29doc 40030 | IN1 normalized start scale | ±32000, default 0. | INT16 | Read/write | ||||
| HR | 30doc 40031 | IN2 normalized start scale | ±32000, default 0. | INT16 | Read/write | ||||
| HR | 31doc 40032 | IN3 normalized start scale | ±32000, default 0. | INT16 | Read/write | ||||
| HR | 32doc 40033 | IN4 normalized start scale | ±32000, default 0. | INT16 | Read/write | ||||
| HR | 34doc 40035 | Firmware code | UINT16 | Read | |||||
| HR | 54doc 40055 | Difference IN2 - IN1 | Channel difference; firmware revision 737 or later. | INT16 | Read | ||||
| HR | 55doc 40056 | Difference IN1 - IN2 | Channel difference; firmware revision 737 or later. | INT16 | Read | ||||
| HR | 56doc 40057 | Difference IN4 - IN3 | Channel difference; firmware revision 737 or later. | INT16 | Read | ||||
| HR | 57doc 40058 | Difference IN3 - IN4 | Channel difference; firmware revision 737 or later. | INT16 | Read |
Notes on this map
- All registers are single 16-bit words; there are no 32-bit values.
- Address 1 and 38400 baud are the EEPROM defaults, used only when the address DIP switches are all OFF; otherwise DIP switches set address (1-63) and baud (9600-57600).
- Bit 0 of 40003 selects Z-4AI-0 compatibility, in which the measurement is fixed to 0-10000.
- Left out: 40036, labelled 'Errors' but printed with the same parity/delay/sampling bit list as 40003, so its real content is unclear.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seneca Z-4AI 4-channel analog input module
What Modbus registers does the Seneca Z-4AI 4-channel analog input module have?
This map lists 34 registers: 34 holding registers. 24 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seneca Z-4AI 4-channel analog input module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints both the 4x number and the offset (40001 = offset 0); the offset is the wire address.
What are the minimum Modbus registers to integrate the Seneca Z-4AI 4-channel analog input module?
Start with HR 16 IN1 normalized value (IN1); HR 17 IN2 normalized value (IN2); HR 18 IN3 normalized value (IN3); HR 19 IN4 normalized value (IN4); HR 15 Status (Status and over/underflow).
How do I enable Modbus control of the Seneca Z-4AI 4-channel analog input module?
Set address and baud with the SW1 DIP switches, or set all address switches OFF to use the values stored in 40002/40003.
Where is the official Seneca Z-4AI 4-channel analog input module Modbus documentation?
The source is Z-4AI User Manual (MI002572-E), published free by Seneca at https://www.seneca.it/media/1329/mi00257-2-en.pdf.
More Seneca Modbus register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2 - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN
Other remote i/o modules register maps
- Sensor (thermocouple input module)
Teracom TST320 2-channel thermocouple module with Modbus RTU
TST320 per the Teracom TST320 user manual Revision R1.6.
Also known as: TST320 - Sensor (Ethernet analog input module)
Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP)
BusWorks XT1211-000 (current) and XT1221-000 (voltage) per user's manual 8500951K.
Also known as: XT1211-000, XT1221-000, XT1211, XT1221, BusWorks XT1211, BusWorks XT1221 - Sensor / remote digital I/O module
ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
tM-P4C4 (4 DI + 4 DO), tM-C8 (8 DO) and tM-P8 (8 DI) with the Modbus RTU protocol selected, per the tM Series DIO User Manual Rev A1.4.
Also known as: tM-P4C4, tM-C8, tM-P8 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS52 resistance input module
Unipi Extension xS52 RS-485 module per the Unipi Extension xS52 Modbus map v2.0.
Also known as: Unipi Extension xS52, xS52 - Sensor / remote I/O module
Brainboxes ED-588 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-588 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-588, ED588 - Sensor (remote I/O module)
Moxa ioLogik R1214 RS-485 remote I/O
ioLogik R1214 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1214, R1214, R1214-T
All remote i/o modules Modbus register maps →
Source: Z-4AI User Manual · MI002572-E. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.