Sensor (I/O module, 4 analog inputs) · Modbus register map

Seneca Z-4AI 4-channel analog input module Modbus register map

Updated 17 November 2026

Short answer

The Z-4AI converts four ±10 V / ±20 mA single-ended inputs to normalized 16-bit values readable over RS-485 Modbus RTU. Everything is in single 16-bit holding registers: comms settings, per-channel filters and scaling, the four measurements and, from firmware 737, channel differences.

This page lists 34 Modbus registers for the Seneca Z-4AI 4-channel analog input module — 24 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.

Manufacturer
Seneca
Model
Z-4AI 4-channel analog input module
Equipment type
Sensor (I/O module, 4 analog inputs)
Registers
34 (24 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
Z-4AI
Source document
Z-4AI User Manual · MI002572-E
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Seneca Z-4AI 4-channel analog input module

Integration in brief

Read holding registers 40017-40020 (wire 16-19) for the four normalized inputs and 40016 for over/underflow bits.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 16IN1 normalized valueINT16IN1Read
HR 17IN2 normalized valueINT16IN2Read
HR 18IN3 normalized valueINT16IN3Read
HR 19IN4 normalized valueINT16IN4Read
HR 15StatusBITMAP16Status and over/underflowRead/write

Enable Modbus control & writes

Set address and baud with the SW1 DIP switches, or set all address switches OFF to use the values stored in 40002/40003.

Byte order & addressing

Network setup

Watch out for

Seneca Z-4AI 4-channel analog input module Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

34 of 34 shown
Seneca Z-4AI 4-channel analog input module Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Machine IDHigh byte = module ID code (default 0x07), low byte = module version.UINT16Read
HR1doc 40002Baud rate and addressHigh byte = baud code (0=4800,1=9600,2=19200,3=38400,4=57600,5=115200,6=1200,7=2400), low byte = address; EEPROM mode.UINT16Read/write
HR2doc 40003EEPROM flagsBITMAP16Read/writebit 0 = Compatibility: 1 = Z-4AI-1, 0 = Z-4AI-0; bit 1 = Sampling time: 1 = 60 ms, 0 = 120 ms; bit 2 = RS-485 reply delay on; bit 3 = RS-485 parity on; bit 4 = Parity odd (0 = even)
HR3doc 40004IN1 filterInput filter level 0 (off) to 6 (strongest).UINT16Read/write
HR4doc 40005IN2 filterInput filter level 0 (off) to 6 (strongest).UINT16Read/write
HR5doc 40006IN3 filterInput filter level 0 (off) to 6 (strongest).UINT16Read/write
HR6doc 40007IN4 filterInput filter level 0 (off) to 6 (strongest).UINT16Read/write
HR7doc 40008IN1 electrical end scale±10000 mV (voltage) or ±20000 µA (current); default 10000 mV.INT16mV/µARead/write
HR8doc 40009IN2 electrical end scale±10000 mV (voltage) or ±20000 µA (current); default 10000 mV.INT16mV/µARead/write
HR9doc 40010IN3 electrical end scale±10000 mV (voltage) or ±20000 µA (current); default 10000 mV.INT16mV/µARead/write
HR10doc 40011IN4 electrical end scale±10000 mV (voltage) or ±20000 µA (current); default 10000 mV.INT16mV/µARead/write
HR11doc 40012IN1 electrical start scaleDefault 0 mV.INT16mV/µARead/write
HR12doc 40013IN2 electrical start scaleDefault 0 mV.INT16mV/µARead/write
HR13doc 40014IN3 electrical start scaleDefault 0 mV.INT16mV/µARead/write
HR14doc 40015IN4 electrical start scaleDefault 0 mV.INT16mV/µARead/write
HR15doc 40016StatusBITMAP16Read/writebit 0 = Reset module (write 1); bit 1 = Reset filter (write 1); bit 7 = Save configuration to EEPROM (write 1); bit 8 = IN1 overflow; bit 9 = IN1 underflow; bit 10 = IN2 overflow; bit 11 = IN2 underflow; bit 12 = IN3 overflow; bit 13 = IN3 underflow; bit 14 = IN4 overflow; bit 15 = IN4 underflow
HR16doc 40017IN1 normalized valueScaled between NSS and NES (fixed 0-10000 in Z-4AI-0 mode).INT16Read
HR17doc 40018IN2 normalized valueScaled between NSS and NES (fixed 0-10000 in Z-4AI-0 mode).INT16Read
HR18doc 40019IN3 normalized valueScaled between NSS and NES (fixed 0-10000 in Z-4AI-0 mode).INT16Read
HR19doc 40020IN4 normalized valueScaled between NSS and NES (fixed 0-10000 in Z-4AI-0 mode).INT16Read
HR24doc 40025Input typesBITMAP16Read/writebit 0 = IN1 current (0 = voltage); bit 1 = IN2 current; bit 2 = IN3 current; bit 3 = IN4 current
HR25doc 40026IN1 normalized end scale±32000, default 10000.INT16Read/write
HR26doc 40027IN2 normalized end scale±32000, default 10000.INT16Read/write
HR27doc 40028IN3 normalized end scale±32000, default 10000.INT16Read/write
HR28doc 40029IN4 normalized end scale±32000, default 10000.INT16Read/write
HR29doc 40030IN1 normalized start scale±32000, default 0.INT16Read/write
HR30doc 40031IN2 normalized start scale±32000, default 0.INT16Read/write
HR31doc 40032IN3 normalized start scale±32000, default 0.INT16Read/write
HR32doc 40033IN4 normalized start scale±32000, default 0.INT16Read/write
HR34doc 40035Firmware codeUINT16Read
HR54doc 40055Difference IN2 - IN1Channel difference; firmware revision 737 or later.INT16Read
HR55doc 40056Difference IN1 - IN2Channel difference; firmware revision 737 or later.INT16Read
HR56doc 40057Difference IN4 - IN3Channel difference; firmware revision 737 or later.INT16Read
HR57doc 40058Difference IN3 - IN4Channel difference; firmware revision 737 or later.INT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Seneca Z-4AI 4-channel analog input module

What Modbus registers does the Seneca Z-4AI 4-channel analog input module have?

This map lists 34 registers: 34 holding registers. 24 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Seneca Z-4AI 4-channel analog input module Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints both the 4x number and the offset (40001 = offset 0); the offset is the wire address.

What are the minimum Modbus registers to integrate the Seneca Z-4AI 4-channel analog input module?

Start with HR 16 IN1 normalized value (IN1); HR 17 IN2 normalized value (IN2); HR 18 IN3 normalized value (IN3); HR 19 IN4 normalized value (IN4); HR 15 Status (Status and over/underflow).

How do I enable Modbus control of the Seneca Z-4AI 4-channel analog input module?

Set address and baud with the SW1 DIP switches, or set all address switches OFF to use the values stored in 40002/40003.

Where is the official Seneca Z-4AI 4-channel analog input module Modbus documentation?

The source is Z-4AI User Manual (MI002572-E), published free by Seneca at https://www.seneca.it/media/1329/mi00257-2-en.pdf.

More Seneca Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: Z-4AI User Manual · MI002572-E. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.