- Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Sensor (RTD temperature input module) · Modbus register map
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) Modbus register map
Updated 17 November 2026
The Z-4RTD2-SI reads four RTD sensors (PT100, PT500, PT1000, NI100, NI120, NI1000, CU50, CU100) in 2, 3 or 4-wire mode and serves them over Modbus RTU. Each channel is available as a scaled 16-bit integer and as a float. This map covers measurements, error flags, serial settings, per-channel configuration, fault values, offsets and the command register.
This page lists 27 Modbus registers for the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seneca
- Model
- Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
- Equipment type
- Sensor (RTD temperature input module)
- Registers
- 27 (16 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI
- Source document
- Z-4RTD2-SI User Manual · MI00584-4-EN · rev. 2026-06-29
Integration notes: Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Read holding registers 1-13 (function 03): error flags, four scaled integers and four floats. Check the burnout and out-of-range bits in register 1 before trusting a value.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Errors | BITMAP16 | Error / burnout flags | Read |
| HR 6 | Channel 1 measure (float) | FLOAT32 ABCD | Channel 1 float | Read |
| HR 8 | Channel 2 measure (float) | FLOAT32 ABCD | Channel 2 float | Read |
| HR 10 | Channel 3 measure (float) | FLOAT32 ABCD | Channel 3 float | Read |
| HR 12 | Channel 4 measure (float) | FLOAT32 ABCD | Channel 4 float | Read |
| HR 2 | Channel 1 measure (16-bit) | INT16 | Channel 1 integer | Read |
Enable Modbus control & writes
Modbus RTU is always on. Station address and parity are in register 34, baud rate in 35; write 51792 to register 47 to save configuration and 52428 to reboot.
Byte order & addressing
- Offset is the wire address.
- Float word order can be flipped by Configuration 2 bit 15.
Network setup
- Set sensor type, wiring and speed per channel in registers 36-39, then save (51792 to register 47).
Watch out for
- Integer scaling changes when a channel is switched to resistance mode.
- While a USB cable is plugged in, the RS-485 port is disabled; unplug USB to restore it.
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Machine identification | UINT16 | Read | |||||
| HR | 1doc 40002 | Errors | BITMAP16 | Read | bit 8 = IN4 burnout; bit 9 = IN3 burnout; bit 10 = IN2 burnout; bit 11 = IN1 burnout; bit 12 = IN4 out of range; bit 13 = IN3 out of range; bit 14 = IN2 out of range; bit 15 = IN1 out of range | ||||
| HR | 2doc 40003 | Channel 1 measure (16-bit) | °C/10 in temperature mode; resistance mode uses Ohm/100 or Ohm/10 by sensor. | INT16 | × 0.1 | °C | Read | ||
| HR | 3doc 40004 | Channel 2 measure (16-bit) | °C/10 in temperature mode; resistance mode uses Ohm/100 or Ohm/10 by sensor. | INT16 | × 0.1 | °C | Read | ||
| HR | 4doc 40005 | Channel 3 measure (16-bit) | °C/10 in temperature mode; resistance mode uses Ohm/100 or Ohm/10 by sensor. | INT16 | × 0.1 | °C | Read | ||
| HR | 5doc 40006 | Channel 4 measure (16-bit) | °C/10 in temperature mode; resistance mode uses Ohm/100 or Ohm/10 by sensor. | INT16 | × 0.1 | °C | Read | ||
| HR | 6doc 40007 | Channel 1 measure (float) | °C, or Ohm in resistance mode. | FLOAT32 | ABCD | °C | Read | ||
| HR | 8doc 40009 | Channel 2 measure (float) | °C, or Ohm in resistance mode. | FLOAT32 | ABCD | °C | Read | ||
| HR | 10doc 40011 | Channel 3 measure (float) | °C, or Ohm in resistance mode. | FLOAT32 | ABCD | °C | Read | ||
| HR | 12doc 40013 | Channel 4 measure (float) | °C, or Ohm in resistance mode. | FLOAT32 | ABCD | °C | Read | ||
| HR | 14doc 40015 | Firmware revision | UINT16 | Read | |||||
| HR | 34doc 40035 | RS485 address and parity | High byte = station address 1-255; low byte = parity. | UINT16 | Read/write | bit 0-7 = Parity: 0 none, 1 even, 2 odd; bit 8-15 = Modbus station address (1-255) | |||
| HR | 35doc 40036 | RS485 baud rate | UINT16 | Read/write | bit 8-15 = Baud: 0=4800 1=9600 2=19200 3=38400 4=57600 5=115200 6=1200 7=2400 | ||||
| HR | 36doc 40037 | Channel 1 input configuration | BITMAP16 | Read/write | bit 4 = Wiring: 0 = 2/4-wire, 1 = 3-wire; bit 5 = Measure type: 0 temperature, 1 resistance; bit 0-2 = Channel speed: 0 disabled, 1 25 ms, 2 50 ms, 3 100 ms, 4 200 ms, 5 400 ms; bit 6-8 = RTD type: 0 PT100, 1 NI100, 2 PT500, 3 PT1000, 4 CU50, 5 CU100, 6 NI120, 7 NI1000; bit 9-11 = Filter: 0 off, 1 on | ||||
| HR | 37doc 40038 | Channel 2 input configuration | BITMAP16 | Read/write | bit 4 = Wiring: 0 = 2/4-wire, 1 = 3-wire; bit 5 = Measure type: 0 temperature, 1 resistance; bit 0-2 = Channel speed: 0 disabled, 1 25 ms, 2 50 ms, 3 100 ms, 4 200 ms, 5 400 ms; bit 6-8 = RTD type: 0 PT100, 1 NI100, 2 PT500, 3 PT1000, 4 CU50, 5 CU100, 6 NI120, 7 NI1000; bit 9-11 = Filter: 0 off, 1 on | ||||
| HR | 38doc 40039 | Channel 3 input configuration | BITMAP16 | Read/write | bit 4 = Wiring: 0 = 2/4-wire, 1 = 3-wire; bit 5 = Measure type: 0 temperature, 1 resistance; bit 0-2 = Channel speed: 0 disabled, 1 25 ms, 2 50 ms, 3 100 ms, 4 200 ms, 5 400 ms; bit 6-8 = RTD type: 0 PT100, 1 NI100, 2 PT500, 3 PT1000, 4 CU50, 5 CU100, 6 NI120, 7 NI1000; bit 9-11 = Filter: 0 off, 1 on | ||||
| HR | 39doc 40040 | Channel 4 input configuration | BITMAP16 | Read/write | bit 4 = Wiring: 0 = 2/4-wire, 1 = 3-wire; bit 5 = Measure type: 0 temperature, 1 resistance; bit 0-2 = Channel speed: 0 disabled, 1 25 ms, 2 50 ms, 3 100 ms, 4 200 ms, 5 400 ms; bit 6-8 = RTD type: 0 PT100, 1 NI100, 2 PT500, 3 PT1000, 4 CU50, 5 CU100, 6 NI120, 7 NI1000; bit 9-11 = Filter: 0 off, 1 on | ||||
| HR | 40doc 40041 | Configuration 2 | BITMAP16 | Read/write | bit 0 = IN4 fault: 1 load fail value, 0 keep last; bit 1 = IN3 fault: 1 load fail value, 0 keep last; bit 2 = IN2 fault: 1 load fail value, 0 keep last; bit 3 = IN1 fault: 1 load fail value, 0 keep last; bit 15 = Float word order: 0 MSW first, 1 LSW first | ||||
| HR | 41doc 40042 | Channel 1 fail value | Loaded on fault when fail-value behaviour is set; °C/10 or Ohm. | INT16 | Read/write | ||||
| HR | 42doc 40043 | Channel 2 fail value | Loaded on fault when fail-value behaviour is set; °C/10 or Ohm. | INT16 | Read/write | ||||
| HR | 43doc 40044 | Channel 3 fail value | Loaded on fault when fail-value behaviour is set; °C/10 or Ohm. | INT16 | Read/write | ||||
| HR | 44doc 40045 | Channel 4 fail value | Loaded on fault when fail-value behaviour is set; °C/10 or Ohm. | INT16 | Read/write | ||||
| HR | 47doc 40048 | Command register | UINT16 | Read/write | 51792 = Save configuration; 52428 = Reboot | ||||
| HR | 132doc 40133 | Channel 1 offset | Offset added to the channel, °C or Ohm. | FLOAT32 | ABCD | °C | Read/write | ||
| HR | 134doc 40135 | Channel 2 offset | Offset added to the channel, °C or Ohm. | FLOAT32 | ABCD | °C | Read/write | ||
| HR | 136doc 40137 | Channel 3 offset | Offset added to the channel, °C or Ohm. | FLOAT32 | ABCD | °C | Read/write | ||
| HR | 138doc 40139 | Channel 4 offset | Offset added to the channel, °C or Ohm. | FLOAT32 | ABCD | °C | Read/write |
Notes on this map
- All values are holding registers.
- Floats are printed MSW at the lower address (ABCD); bit 15 of Configuration 2 (offset 40) switches them to LSW first. The manual does not state the factory value of that bit, so confirm it reads 0 before trusting ABCD. The manual also lists a word-swapped copy at +1000 (e.g. 41007); not included here.
- The 16-bit measures are °C/10 in temperature mode. In resistance mode they are Ohm/100 for PT100/NI100/NI120/CU50/CU100 and Ohm/10 for PT500/PT1000/NI1000, so the listed 0.1 scale only fits temperature mode.
- RW* registers are in flash (about 10,000 writes).
- The manual does not give factory defaults for address or baud rate.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
What Modbus registers does the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) have?
This map lists 27 registers: 27 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints the 4x number (40003) and the 0-based offset (2). The offset is the wire address.
What byte order does the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)?
Start with HR 1 Errors (Error / burnout flags); HR 6 Channel 1 measure (float) (Channel 1 float); HR 8 Channel 2 measure (float) (Channel 2 float); HR 10 Channel 3 measure (float) (Channel 3 float); HR 12 Channel 4 measure (float) (Channel 4 float); HR 2 Channel 1 measure (16-bit) (Channel 1 integer).
How do I enable Modbus control of the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)?
Modbus RTU is always on. Station address and parity are in register 34, baud rate in 35; write 51792 to register 47 to save configuration and 52428 to reboot.
Where is the official Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) Modbus documentation?
The source is Z-4RTD2-SI User Manual (MI00584-4-EN), revision 2026-06-29, published free by Seneca at https://www.seneca.it/media/6849343/mi00584-4-en.pdf.
More Seneca Modbus register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2 - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN
Other remote i/o modules register maps
- Sensor (remote I/O module)
Unipi Technology Unipi Extension xS11 I/O module
Unipi Extension xS11 RS-485 module per the Unipi Extension xS11 Modbus map v2.0.
Also known as: Unipi Extension xS11, xS11 - Sensor / remote I/O module
Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-516 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-516, ED516 - Sensor (remote I/O module)
Moxa ioLogik R1210 RS-485 remote I/O
ioLogik R1210 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1210, R1210, R1210-T - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS53 analog input module
Unipi Extension xS53 RS-485 module per the Unipi Extension xS53 Modbus map v2.0.
Also known as: Unipi Extension xS53, xS53 - Sensor (thermistor input module)
ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)
M-7005 in Modbus RTU mode, per I-7005/M-7005 User Manual Rev B2.4 (7MH-018-B24). The I-7005 uses the DCON protocol and is not covered.
Also known as: M-7005, M7005, I-7005/M-7005 - Sensor (remote I/O module)
Moxa ioLogik R1240 RS-485 remote I/O
ioLogik R1240 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1240, R1240, R1240-T
All remote i/o modules Modbus register maps →
Source: Z-4RTD2-SI User Manual · MI00584-4-EN · rev. 2026-06-29. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.