Sensor (RTD temperature input module) · Modbus register map

Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The Z-4RTD2-SI reads four RTD sensors (PT100, PT500, PT1000, NI100, NI120, NI1000, CU50, CU100) in 2, 3 or 4-wire mode and serves them over Modbus RTU. Each channel is available as a scaled 16-bit integer and as a float. This map covers measurements, error flags, serial settings, per-channel configuration, fault values, offsets and the command register.

This page lists 27 Modbus registers for the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.

Manufacturer
Seneca
Model
Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Equipment type
Sensor (RTD temperature input module)
Registers
27 (16 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI
Source document
Z-4RTD2-SI User Manual · MI00584-4-EN · rev. 2026-06-29
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)

Integration in brief

Read holding registers 1-13 (function 03): error flags, four scaled integers and four floats. Check the burnout and out-of-range bits in register 1 before trusting a value.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1ErrorsBITMAP16Error / burnout flagsRead
HR 6Channel 1 measure (float)FLOAT32 ABCDChannel 1 floatRead
HR 8Channel 2 measure (float)FLOAT32 ABCDChannel 2 floatRead
HR 10Channel 3 measure (float)FLOAT32 ABCDChannel 3 floatRead
HR 12Channel 4 measure (float)FLOAT32 ABCDChannel 4 floatRead
HR 2Channel 1 measure (16-bit)INT16Channel 1 integerRead

Enable Modbus control & writes

Modbus RTU is always on. Station address and parity are in register 34, baud rate in 35; write 51792 to register 47 to save configuration and 52428 to reboot.

Byte order & addressing

Network setup

Watch out for

Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

27 of 27 shown
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Machine identificationUINT16Read
HR1doc 40002ErrorsBITMAP16Readbit 8 = IN4 burnout; bit 9 = IN3 burnout; bit 10 = IN2 burnout; bit 11 = IN1 burnout; bit 12 = IN4 out of range; bit 13 = IN3 out of range; bit 14 = IN2 out of range; bit 15 = IN1 out of range
HR2doc 40003Channel 1 measure (16-bit)°C/10 in temperature mode; resistance mode uses Ohm/100 or Ohm/10 by sensor.INT16× 0.1°CRead
HR3doc 40004Channel 2 measure (16-bit)°C/10 in temperature mode; resistance mode uses Ohm/100 or Ohm/10 by sensor.INT16× 0.1°CRead
HR4doc 40005Channel 3 measure (16-bit)°C/10 in temperature mode; resistance mode uses Ohm/100 or Ohm/10 by sensor.INT16× 0.1°CRead
HR5doc 40006Channel 4 measure (16-bit)°C/10 in temperature mode; resistance mode uses Ohm/100 or Ohm/10 by sensor.INT16× 0.1°CRead
HR6doc 40007Channel 1 measure (float)°C, or Ohm in resistance mode.FLOAT32ABCD°CRead
HR8doc 40009Channel 2 measure (float)°C, or Ohm in resistance mode.FLOAT32ABCD°CRead
HR10doc 40011Channel 3 measure (float)°C, or Ohm in resistance mode.FLOAT32ABCD°CRead
HR12doc 40013Channel 4 measure (float)°C, or Ohm in resistance mode.FLOAT32ABCD°CRead
HR14doc 40015Firmware revisionUINT16Read
HR34doc 40035RS485 address and parityHigh byte = station address 1-255; low byte = parity.UINT16Read/writebit 0-7 = Parity: 0 none, 1 even, 2 odd; bit 8-15 = Modbus station address (1-255)
HR35doc 40036RS485 baud rateUINT16Read/writebit 8-15 = Baud: 0=4800 1=9600 2=19200 3=38400 4=57600 5=115200 6=1200 7=2400
HR36doc 40037Channel 1 input configurationBITMAP16Read/writebit 4 = Wiring: 0 = 2/4-wire, 1 = 3-wire; bit 5 = Measure type: 0 temperature, 1 resistance; bit 0-2 = Channel speed: 0 disabled, 1 25 ms, 2 50 ms, 3 100 ms, 4 200 ms, 5 400 ms; bit 6-8 = RTD type: 0 PT100, 1 NI100, 2 PT500, 3 PT1000, 4 CU50, 5 CU100, 6 NI120, 7 NI1000; bit 9-11 = Filter: 0 off, 1 on
HR37doc 40038Channel 2 input configurationBITMAP16Read/writebit 4 = Wiring: 0 = 2/4-wire, 1 = 3-wire; bit 5 = Measure type: 0 temperature, 1 resistance; bit 0-2 = Channel speed: 0 disabled, 1 25 ms, 2 50 ms, 3 100 ms, 4 200 ms, 5 400 ms; bit 6-8 = RTD type: 0 PT100, 1 NI100, 2 PT500, 3 PT1000, 4 CU50, 5 CU100, 6 NI120, 7 NI1000; bit 9-11 = Filter: 0 off, 1 on
HR38doc 40039Channel 3 input configurationBITMAP16Read/writebit 4 = Wiring: 0 = 2/4-wire, 1 = 3-wire; bit 5 = Measure type: 0 temperature, 1 resistance; bit 0-2 = Channel speed: 0 disabled, 1 25 ms, 2 50 ms, 3 100 ms, 4 200 ms, 5 400 ms; bit 6-8 = RTD type: 0 PT100, 1 NI100, 2 PT500, 3 PT1000, 4 CU50, 5 CU100, 6 NI120, 7 NI1000; bit 9-11 = Filter: 0 off, 1 on
HR39doc 40040Channel 4 input configurationBITMAP16Read/writebit 4 = Wiring: 0 = 2/4-wire, 1 = 3-wire; bit 5 = Measure type: 0 temperature, 1 resistance; bit 0-2 = Channel speed: 0 disabled, 1 25 ms, 2 50 ms, 3 100 ms, 4 200 ms, 5 400 ms; bit 6-8 = RTD type: 0 PT100, 1 NI100, 2 PT500, 3 PT1000, 4 CU50, 5 CU100, 6 NI120, 7 NI1000; bit 9-11 = Filter: 0 off, 1 on
HR40doc 40041Configuration 2BITMAP16Read/writebit 0 = IN4 fault: 1 load fail value, 0 keep last; bit 1 = IN3 fault: 1 load fail value, 0 keep last; bit 2 = IN2 fault: 1 load fail value, 0 keep last; bit 3 = IN1 fault: 1 load fail value, 0 keep last; bit 15 = Float word order: 0 MSW first, 1 LSW first
HR41doc 40042Channel 1 fail valueLoaded on fault when fail-value behaviour is set; °C/10 or Ohm.INT16Read/write
HR42doc 40043Channel 2 fail valueLoaded on fault when fail-value behaviour is set; °C/10 or Ohm.INT16Read/write
HR43doc 40044Channel 3 fail valueLoaded on fault when fail-value behaviour is set; °C/10 or Ohm.INT16Read/write
HR44doc 40045Channel 4 fail valueLoaded on fault when fail-value behaviour is set; °C/10 or Ohm.INT16Read/write
HR47doc 40048Command registerUINT16Read/write51792 = Save configuration; 52428 = Reboot
HR132doc 40133Channel 1 offsetOffset added to the channel, °C or Ohm.FLOAT32ABCD°CRead/write
HR134doc 40135Channel 2 offsetOffset added to the channel, °C or Ohm.FLOAT32ABCD°CRead/write
HR136doc 40137Channel 3 offsetOffset added to the channel, °C or Ohm.FLOAT32ABCD°CRead/write
HR138doc 40139Channel 4 offsetOffset added to the channel, °C or Ohm.FLOAT32ABCD°CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)

What Modbus registers does the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) have?

This map lists 27 registers: 27 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints the 4x number (40003) and the 0-based offset (2). The offset is the wire address.

What byte order does the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)?

Start with HR 1 Errors (Error / burnout flags); HR 6 Channel 1 measure (float) (Channel 1 float); HR 8 Channel 2 measure (float) (Channel 2 float); HR 10 Channel 3 measure (float) (Channel 3 float); HR 12 Channel 4 measure (float) (Channel 4 float); HR 2 Channel 1 measure (16-bit) (Channel 1 integer).

How do I enable Modbus control of the Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)?

Modbus RTU is always on. Station address and parity are in register 34, baud rate in 35; write 51792 to register 47 to save configuration and 52428 to reboot.

Where is the official Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU) Modbus documentation?

The source is Z-4RTD2-SI User Manual (MI00584-4-EN), revision 2026-06-29, published free by Seneca at https://www.seneca.it/media/6849343/mi00584-4-en.pdf.

More Seneca Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: Z-4RTD2-SI User Manual · MI00584-4-EN · rev. 2026-06-29. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.