Easy Modbus
  1. Home
  2. Modbus register maps
  3. Unipi Technology
  4. Unipi Extension xS11 I/O module

Sensor (remote I/O module) · Modbus register map

Unipi Technology Unipi Extension xS11 I/O module Modbus register map

Updated 19 November 2026

Short answer

The Unipi Extension xS11 is an RS-485 Modbus RTU extension module with 12 digital inputs and 13 relay outputs. The map covers I/O state words, coils, per-input counters and debounce, DirectSwitch settings, the master watchdog and RS-485 configuration.

This page lists 74 Modbus registers for the Unipi Technology Unipi Extension xS11 I/O module — 54 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Unipi Technology’s own free documentation (linked below) and checked against it.

Manufacturer
Unipi Technology
Model
Unipi Extension xS11 I/O module
Equipment type
Sensor (remote I/O module)
Registers
74 (54 writable)
Transport
Modbus RTU
Default unit ID
15
Default serial
19200 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
CDAB low word first (word-swapped)
Also known as
Unipi Extension xS11, xS11
Source document
Extension xS11 Modbus map · v2.0
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Unipi Technology Unipi Extension xS11 I/O module

Integration in brief

Read inputs and relays as bit words at registers 0 and 1, or switch relays with FC05 on coils 0-12; inputs are coils 13-24.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Digital InputsBITMAP16Digital input statesRead
HR 1Relay OutputsBITMAP16Relay output statesRead/write
CO 0Relay Output 1BITRelay 1Read/write
CO 13Digital Input 1BITDigital input 1Read
HR 3Counter of Digital Input 1UINT32 CDABDI 1 counterRead/write

Enable Modbus control & writes

Modbus RTU is the native interface; nothing needs enabling. Factory settings are address 15, 19200 bps, 8N1.

Communication loss & watchdog

Master watchdog (MWD): enable it with the MWD Enable bit of the MWD status register and set the timeout in register 1008 (default 5000 ms). A watchdog reboot is flagged by the MWD Reboot Detected bit and coil 1000; the map does not describe the timeout behaviour further.

Byte order & addressing

Network setup

Unipi Technology Unipi Extension xS11 I/O module Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

74 of 74 shown
Unipi Technology Unipi Extension xS11 I/O module Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 0x0000Relay Output 1Relay output state.BITRead/write
CO1doc 0x0001Relay Output 2Relay output state.BITRead/write
CO2doc 0x0002Relay Output 3Relay output state.BITRead/write
CO3doc 0x0003Relay Output 4Relay output state.BITRead/write
CO4doc 0x0004Relay Output 5Relay output state.BITRead/write
CO5doc 0x0005Relay Output 6Relay output state.BITRead/write
CO6doc 0x0006Relay Output 7Relay output state.BITRead/write
CO7doc 0x0007Relay Output 8Relay output state.BITRead/write
CO8doc 0x0008Relay Output 9Relay output state.BITRead/write
CO9doc 0x0009Relay Output 10Relay output state.BITRead/write
CO10doc 0x000ARelay Output 11Relay output state.BITRead/write
CO11doc 0x000BRelay Output 12Relay output state.BITRead/write
CO12doc 0x000CRelay Output 13Relay output state.BITRead/write
CO13doc 0x000DDigital Input 1Digital input state (read with FC01).BITRead
CO14doc 0x000EDigital Input 2Digital input state (read with FC01).BITRead
CO15doc 0x000FDigital Input 3Digital input state (read with FC01).BITRead
CO16doc 0x0010Digital Input 4Digital input state (read with FC01).BITRead
CO17doc 0x0011Digital Input 5Digital input state (read with FC01).BITRead
CO18doc 0x0012Digital Input 6Digital input state (read with FC01).BITRead
CO19doc 0x0013Digital Input 7Digital input state (read with FC01).BITRead
CO20doc 0x0014Digital Input 8Digital input state (read with FC01).BITRead
CO21doc 0x0015Digital Input 9Digital input state (read with FC01).BITRead
CO22doc 0x0016Digital Input 10Digital input state (read with FC01).BITRead
CO23doc 0x0017Digital Input 11Digital input state (read with FC01).BITRead
CO24doc 0x0018Digital Input 12Digital input state (read with FC01).BITRead
CO25doc 0x0019User Programmable LED 1BITRead/write
CO26doc 0x001AUser Programmable LED 2BITRead/write
CO27doc 0x001BUser Programmable LED 3BITRead/write
CO1000doc 0x03E8MWD reset indicationSet when the master watchdog has reset the module.BITRead/write
CO1002doc 0x03EAReset group MCUWrite 1 to reset the module processor.BITWrite
CO1003doc 0x03EBSave current configuration and use on startupWrite 1 to store the current settings as power-up defaults.BITWrite
HR0doc 0x0000Digital InputsBITMAP16Readbit 0 = Digital Input 1; bit 1 = Digital Input 2; bit 2 = Digital Input 3; bit 3 = Digital Input 4; bit 4 = Digital Input 5; bit 5 = Digital Input 6; bit 6 = Digital Input 7; bit 7 = Digital Input 8; bit 8 = Digital Input 9; bit 9 = Digital Input 10; bit 10 = Digital Input 11; bit 11 = Digital Input 12
HR1doc 0x0001Relay OutputsBITMAP16Read/writebit 0 = Relay Output 1; bit 1 = Relay Output 2; bit 2 = Relay Output 3; bit 3 = Relay Output 4; bit 4 = Relay Output 5; bit 5 = Relay Output 6; bit 6 = Relay Output 7; bit 7 = Relay Output 8; bit 8 = Relay Output 9; bit 9 = Relay Output 10; bit 10 = Relay Output 11; bit 11 = Relay Output 12; bit 12 = Relay Output 13
HR2doc 0x0002Group MasterWatchDog (MWD) StatusBITMAP16Read/writebit 0 = MWD Enable; bit 1 = MWD Reboot Detected
HR3doc 0x0003Counter of Digital Input 1Pulse counter for this input; writable to preset.UINT32CDABRead/write
HR5doc 0x0005Counter of Digital Input 2Pulse counter for this input; writable to preset.UINT32CDABRead/write
HR7doc 0x0007Counter of Digital Input 3Pulse counter for this input; writable to preset.UINT32CDABRead/write
HR9doc 0x0009Counter of Digital Input 4Pulse counter for this input; writable to preset.UINT32CDABRead/write
HR11doc 0x000BCounter of Digital Input 5Pulse counter for this input; writable to preset.UINT32CDABRead/write
HR13doc 0x000DCounter of Digital Input 6Pulse counter for this input; writable to preset.UINT32CDABRead/write
HR15doc 0x000FCounter of Digital Input 7Pulse counter for this input; writable to preset.UINT32CDABRead/write
HR17doc 0x0011Counter of Digital Input 8Pulse counter for this input; writable to preset.UINT32CDABRead/write
HR19doc 0x0013Counter of Digital Input 9Pulse counter for this input; writable to preset.UINT32CDABRead/write
HR21doc 0x0015Counter of Digital Input 10Pulse counter for this input; writable to preset.UINT32CDABRead/write
HR23doc 0x0017Counter of Digital Input 11Pulse counter for this input; writable to preset.UINT32CDABRead/write
HR25doc 0x0019Counter of Digital Input 12Pulse counter for this input; writable to preset.UINT32CDABRead/write
HR31doc 0x001FUser-programmable LED statesBITMAP16Read/writebit 0 = User LED 1; bit 1 = User LED 2; bit 2 = User LED 3
HR32doc 0x0020Synchronised Relay OutputsBITMAP16Read/writebit 0 = Synchronised RO 1; bit 1 = Synchronised RO 2; bit 2 = Synchronised RO 3; bit 3 = Synchronised RO 4; bit 4 = Synchronised RO 5; bit 5 = Synchronised RO 6; bit 6 = Synchronised RO 7; bit 7 = Synchronised RO 8; bit 8 = Synchronised RO 9; bit 9 = Synchronised RO 10; bit 10 = Synchronised RO 11; bit 11 = Synchronised RO 12; bit 12 = Synchronised RO 13
HR33doc 0x0021Synchronised Relay Output LocksBITMAP16Read/writebit 0 = Synchronised RO Lock 1; bit 1 = Synchronised RO Lock 2; bit 2 = Synchronised RO Lock 3; bit 3 = Synchronised RO Lock 4; bit 4 = Synchronised RO Lock 5; bit 5 = Synchronised RO Lock 6; bit 6 = Synchronised RO Lock 7; bit 7 = Synchronised RO Lock 8; bit 8 = Synchronised RO Lock 9; bit 9 = Synchronised RO Lock 10; bit 10 = Synchronised RO Lock 11; bit 11 = Synchronised RO Lock 12; bit 12 = Synchronised RO Lock 13
HR1000doc 0x03E8Firmware VersionUINT16Read
HR1001doc 0x03E9Number of I/OsPacked counts: bits 0-7 DOs, bits 8-15 DIs.UINT16Read
HR1002doc 0x03EANumber of peripheralsPacked counts: bits 0-3 RS485 lines, bits 4-7 AOs, bits 8-15 AIs.UINT16Read
HR1003doc 0x03EBFirmware IDUINT16Read
HR1004doc 0x03ECHardware IDUINT16Read
HR1005doc 0x03EDPCB Serial NumberUINT32CDABRead
HR1008doc 0x03F0MasterWatchDog (MWD) Timeout (in 1ms)Master watchdog timeout; default 5000 ms.UINT16msRead/write
HR1009doc 0x03F1VRef of MCUUINT16Read
HR1010doc 0x03F2Debounce time (in 100us) for DI 1Input debounce time in 100 us steps.UINT16× 0.1msRead/write
HR1011doc 0x03F3Debounce time (in 100us) for DI 2Input debounce time in 100 us steps.UINT16× 0.1msRead/write
HR1012doc 0x03F4Debounce time (in 100us) for DI 3Input debounce time in 100 us steps.UINT16× 0.1msRead/write
HR1013doc 0x03F5Debounce time (in 100us) for DI 4Input debounce time in 100 us steps.UINT16× 0.1msRead/write
HR1014doc 0x03F6Debounce time (in 100us) for DI 5Input debounce time in 100 us steps.UINT16× 0.1msRead/write
HR1015doc 0x03F7Debounce time (in 100us) for DI 6Input debounce time in 100 us steps.UINT16× 0.1msRead/write
HR1016doc 0x03F8Debounce time (in 100us) for DI 7Input debounce time in 100 us steps.UINT16× 0.1msRead/write
HR1017doc 0x03F9Debounce time (in 100us) for DI 8Input debounce time in 100 us steps.UINT16× 0.1msRead/write
HR1018doc 0x03FADebounce time (in 100us) for DI 9Input debounce time in 100 us steps.UINT16× 0.1msRead/write
HR1019doc 0x03FBDebounce time (in 100us) for DI 10Input debounce time in 100 us steps.UINT16× 0.1msRead/write
HR1020doc 0x03FCDebounce time (in 100us) for DI 11Input debounce time in 100 us steps.UINT16× 0.1msRead/write
HR1021doc 0x03FDDebounce time (in 100us) for DI 12Input debounce time in 100 us steps.UINT16× 0.1msRead/write
HR1022doc 0x03FEEnable DirectSwitch functionalityBITMAP16Read/writebit 0 = Enable DirectSwitch on DI 1; bit 1 = Enable DirectSwitch on DI 2; bit 2 = Enable DirectSwitch on DI 3; bit 3 = Enable DirectSwitch on DI 4; bit 4 = Enable DirectSwitch on DI 5; bit 5 = Enable DirectSwitch on DI 6; bit 6 = Enable DirectSwitch on DI 7; bit 7 = Enable DirectSwitch on DI 8; bit 8 = Enable DirectSwitch on DI 9; bit 9 = Enable DirectSwitch on DI 10; bit 10 = Enable DirectSwitch on DI 11; bit 11 = Enable DirectSwitch on DI 12
HR1023doc 0x03FFInvert DirectSwitch PolarityBITMAP16Read/writebit 0 = Invert DirectSwitch Polarity on DI 1; bit 1 = Invert DirectSwitch Polarity on DI 2; bit 2 = Invert DirectSwitch Polarity on DI 3; bit 3 = Invert DirectSwitch Polarity on DI 4; bit 4 = Invert DirectSwitch Polarity on DI 5; bit 5 = Invert DirectSwitch Polarity on DI 6; bit 6 = Invert DirectSwitch Polarity on DI 7; bit 7 = Invert DirectSwitch Polarity on DI 8; bit 8 = Invert DirectSwitch Polarity on DI 9; bit 9 = Invert DirectSwitch Polarity on DI 10; bit 10 = Invert DirectSwitch Polarity on DI 11; bit 11 = Invert DirectSwitch Polarity on DI 12
HR1024doc 0x0400Enabled DirectSwitch ToggleBITMAP16Read/writebit 0 = Enable DirectSwitch Toggle on DI 1; bit 1 = Enable DirectSwitch Toggle on DI 2; bit 2 = Enable DirectSwitch Toggle on DI 3; bit 3 = Enable DirectSwitch Toggle on DI 4; bit 4 = Enable DirectSwitch Toggle on DI 5; bit 5 = Enable DirectSwitch Toggle on DI 6; bit 6 = Enable DirectSwitch Toggle on DI 7; bit 7 = Enable DirectSwitch Toggle on DI 8; bit 8 = Enable DirectSwitch Toggle on DI 9; bit 9 = Enable DirectSwitch Toggle on DI 10; bit 10 = Enable DirectSwitch Toggle on DI 11; bit 11 = Enable DirectSwitch Toggle on DI 12
HR1027doc 0x0403RS485 Configuration - see Description sheetBits 0-12 baud code, bit 13 parity on, bit 14 odd parity; default 14 (19200 8N1).UINT16Read/write
HR1028doc 0x0404Modbus Address Configuration (1-254)Modbus RTU slave address (default 15).UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Unipi Technology Unipi Extension xS11 I/O module

What Modbus registers does the Unipi Technology Unipi Extension xS11 I/O module have?

This map lists 74 registers: 31 coils, 43 holding registers. 54 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Unipi Technology Unipi Extension xS11 I/O module Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map lists each register in decimal and hex starting at 0; the number is the wire address.

What byte order does the Unipi Technology Unipi Extension xS11 I/O module use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Unipi Technology Unipi Extension xS11 I/O module?

Start with HR 0 Digital Inputs (Digital input states); HR 1 Relay Outputs (Relay output states); CO 0 Relay Output 1 (Relay 1); CO 13 Digital Input 1 (Digital input 1); HR 3 Counter of Digital Input 1 (DI 1 counter).

How do I enable Modbus control of the Unipi Technology Unipi Extension xS11 I/O module?

Modbus RTU is the native interface; nothing needs enabling. Factory settings are address 15, 19200 bps, 8N1.

What happens when the Unipi Technology Unipi Extension xS11 I/O module loses Modbus communication?

Master watchdog (MWD): enable it with the MWD Enable bit of the MWD status register and set the timeout in register 1008 (default 5000 ms). A watchdog reboot is flagged by the MWD Reboot Detected bit and coil 1000; the map does not describe the timeout behaviour further.

Where is the official Unipi Technology Unipi Extension xS11 I/O module Modbus documentation?

The source is Extension xS11 Modbus map (v2.0), published free by Unipi Technology at https://kb.unipi.technology/_media/files:products:extensions:unipi-extension-xs11-modbus-map-v2.0.pdf.

More Unipi Technology Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: Extension xS11 Modbus map · v2.0. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.