- Home
- Modbus register maps
- Unipi Technology
- Unipi Extension xG18 1-Wire temperature gateway
Sensor (1-Wire temperature gateway) · Modbus register map
Unipi Technology Unipi Extension xG18 1-Wire temperature gateway Modbus register map
Updated 19 November 2026
The Unipi Extension xG18 is an RS-485 Modbus RTU gateway for up to eight Unipi 1-Wire temperature sensors, one per channel. The map gives each channel's temperature in hundredths of a degree, a validity bit word, measuring intervals, the master watchdog and RS-485 configuration.
This page lists 31 Modbus registers for the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Unipi Technology’s own free documentation (linked below) and checked against it.
- Manufacturer
- Unipi Technology
- Model
- Unipi Extension xG18 1-Wire temperature gateway
- Equipment type
- Sensor (1-Wire temperature gateway)
- Registers
- 31 (16 writable)
- Transport
- Modbus RTU
- Default unit ID
- 15
- Default serial
- 19200 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- Unipi Extension xG18, xG18
- Source document
- Extension xG18 Modbus map · v1.1
Integration notes: Unipi Technology Unipi Extension xG18 1-Wire temperature gateway
Read temperatures CH1-CH8 at registers 1-8 (signed, x0.01 °C) and check the validity bits at register 9 before trusting a value.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Temperature CH1 | INT16 | Temperature CH1 | Read |
| HR 2 | Temperature CH2 | INT16 | Temperature CH2 | Read |
| HR 9 | Temperature validity | BITMAP16 | Temperature validity bits | Read/write |
| HR 1010 | Measuring interval CH1 (seconds) | UINT16 | CH1 measuring interval | Read/write |
| HR 1019 | Modbus Address Configuration (1-254) | UINT16 | Modbus address | Read/write |
Enable Modbus control & writes
Modbus RTU is the native interface; nothing needs enabling. Factory settings are address 15, 19200 bps, 8N1.
Communication loss & watchdog
Master watchdog (MWD): enable it with bit 0 of register 0 and set the timeout in register 1008 (default 5000 ms). A watchdog reboot is flagged in bit 1 of register 0 and in coil 1000; the map does not describe the timeout behaviour further.
Byte order & addressing
- 32-bit values (here only the PCB serial number) are low word first (CDAB).
- Changes to RS-485 settings and other configuration need the Save configuration coil to survive a power cycle.
Network setup
- Set the address register (1019) and the packed RS-485 configuration register (1018), then write 1 to the save coil (1003) so the settings are used on startup.
Unipi Technology Unipi Extension xG18 1-Wire temperature gateway Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 1000doc 0x03E8 | MWD reset indication | Set when the master watchdog has reset the module. | BIT | Read/write | ||||
| CO | 1002doc 0x03EA | Reset group MCU | Write 1 to reset the module processor. | BIT | Read/write | ||||
| CO | 1003doc 0x03EB | Save current configuration and use on startup | Write 1 to store the current settings as power-up defaults. | BIT | Read/write | ||||
| HR | 0doc 0x0000 | Group MasterWatchDog (MWD) Status | BITMAP16 | Read/write | bit 0 = MWD Enable; bit 1 = MWD Reboot Detected | ||||
| HR | 1doc 0x0001 | Temperature CH1 | 1-Wire temperature in 0.01 °C; reads -32768 by default (no reading). | INT16 | × 0.01 | °C | Read | ||
| HR | 2doc 0x0002 | Temperature CH2 | 1-Wire temperature in 0.01 °C; reads -32768 by default (no reading). | INT16 | × 0.01 | °C | Read | ||
| HR | 3doc 0x0003 | Temperature CH3 | 1-Wire temperature in 0.01 °C; reads -32768 by default (no reading). | INT16 | × 0.01 | °C | Read | ||
| HR | 4doc 0x0004 | Temperature CH4 | 1-Wire temperature in 0.01 °C; reads -32768 by default (no reading). | INT16 | × 0.01 | °C | Read | ||
| HR | 5doc 0x0005 | Temperature CH5 | 1-Wire temperature in 0.01 °C; reads -32768 by default (no reading). | INT16 | × 0.01 | °C | Read | ||
| HR | 6doc 0x0006 | Temperature CH6 | 1-Wire temperature in 0.01 °C; reads -32768 by default (no reading). | INT16 | × 0.01 | °C | Read | ||
| HR | 7doc 0x0007 | Temperature CH7 | 1-Wire temperature in 0.01 °C; reads -32768 by default (no reading). | INT16 | × 0.01 | °C | Read | ||
| HR | 8doc 0x0008 | Temperature CH8 | 1-Wire temperature in 0.01 °C; reads -32768 by default (no reading). | INT16 | × 0.01 | °C | Read | ||
| HR | 9doc 0x0009 | Temperature validity | BITMAP16 | Read/write | bit 0 = CH1; bit 1 = CH2; bit 2 = CH3; bit 3 = CH4; bit 4 = CH5; bit 5 = CH6; bit 6 = CH7; bit 7 = CH8 | ||||
| HR | 1000doc 0x03E8 | Firmware Version | UINT16 | Read | |||||
| HR | 1001doc 0x03E9 | Number of I/Os | Packed counts: bits 0-7 DOs, bits 8-15 DIs. | UINT16 | Read | ||||
| HR | 1002doc 0x03EA | Number of peripherals | Packed counts: bits 0-3 RS485 lines, bits 4-7 AOs, bits 8-15 AIs. | UINT16 | Read | ||||
| HR | 1003doc 0x03EB | Firmware ID | UINT16 | Read | |||||
| HR | 1004doc 0x03EC | Hardware ID | UINT16 | Read | |||||
| HR | 1005doc 0x03ED | PCB Serial Number | UINT32 | CDAB | Read | ||||
| HR | 1008doc 0x03F0 | MasterWatchDog (MWD) Timeout (ms) | Master watchdog timeout; default 5000 ms. | UINT16 | ms | Read/write | |||
| HR | 1009doc 0x03F1 | VRef of MCU | UINT16 | Read | |||||
| HR | 1010doc 0x03F2 | Measuring interval CH1 (seconds) | Measurement interval for this channel (default 2 s). | UINT16 | s | Read/write | |||
| HR | 1011doc 0x03F3 | Measuring interval CH2 (seconds) | Measurement interval for this channel (default 2 s). | UINT16 | s | Read/write | |||
| HR | 1012doc 0x03F4 | Measuring interval CH3 (seconds) | Measurement interval for this channel (default 2 s). | UINT16 | s | Read/write | |||
| HR | 1013doc 0x03F5 | Measuring interval CH4 (seconds) | Measurement interval for this channel (default 2 s). | UINT16 | s | Read/write | |||
| HR | 1014doc 0x03F6 | Measuring interval CH5 (seconds) | Measurement interval for this channel (default 2 s). | UINT16 | s | Read/write | |||
| HR | 1015doc 0x03F7 | Measuring interval CH6 (seconds) | Measurement interval for this channel (default 2 s). | UINT16 | s | Read/write | |||
| HR | 1016doc 0x03F8 | Measuring interval CH7 (seconds) | Measurement interval for this channel (default 2 s). | UINT16 | s | Read/write | |||
| HR | 1017doc 0x03F9 | Measuring interval CH8 (seconds) | Measurement interval for this channel (default 2 s). | UINT16 | s | Read/write | |||
| HR | 1018doc 0x03FA | RS485 Configuration - see Description sheet | Bits 0-12 baud code, bit 13 parity on, bit 14 odd parity; default 14 (19200 8N1). | UINT16 | Read/write | ||||
| HR | 1019doc 0x03FB | Modbus Address Configuration (1-254) | Modbus RTU slave address (default 15). | UINT16 | Read/write |
Notes on this map
- Word order: the description sheet states 16-bit values are big endian (AB) and 32-bit values are mid-little endian (CDAB, low word first).
- Registers marked Reserved - Do Not Use are left out.
- Baud codes for the RS-485 configuration register: 11 = 2400, 12 = 4800, 13 = 9600, 14 = 19200, 15 = 38400, 4097 = 57600, 4098 = 115200 bps.
- The PDF file name says v1.0 but the sheet itself is marked v1.1.
- Temperature scaling (x0.01 °C) comes from the default-values table, which shows the power-up value -32768 as -327.68 °C; a validity bit of 0 means an unconnected or faulty sensor.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway
What Modbus registers does the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway have?
This map lists 31 registers: 3 coils, 28 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map lists each register in decimal and hex starting at 0; the number is the wire address.
What byte order does the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway?
Start with HR 1 Temperature CH1 (Temperature CH1); HR 2 Temperature CH2 (Temperature CH2); HR 9 Temperature validity (Temperature validity bits); HR 1010 Measuring interval CH1 (seconds) (CH1 measuring interval); HR 1019 Modbus Address Configuration (1-254) (Modbus address).
How do I enable Modbus control of the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway?
Modbus RTU is the native interface; nothing needs enabling. Factory settings are address 15, 19200 bps, 8N1.
What happens when the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway loses Modbus communication?
Master watchdog (MWD): enable it with bit 0 of register 0 and set the timeout in register 1008 (default 5000 ms). A watchdog reboot is flagged in bit 1 of register 0 and in coil 1000; the map does not describe the timeout behaviour further.
Where is the official Unipi Technology Unipi Extension xG18 1-Wire temperature gateway Modbus documentation?
The source is Extension xG18 Modbus map (v1.1), published free by Unipi Technology at https://kb.unipi.technology/_media/files:products:extensions:unipi-extension-xg18-modbus-map-v1.0.pdf.
More Unipi Technology Modbus register maps
- Boiler gateway (OpenTherm to Modbus RTU)
Unipi Technology MM-OT101 Modbus / OpenTherm gateway
Unipi MM-OT101 DIN-rail gateway between Modbus RTU (RS-485) and OpenTherm/Plus boilers and thermostats, per its technical documentation.
Also known as: MM-OT101, MM-OT1010, Unipi OpenTherm gateway - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS11 I/O module
Unipi Extension xS11 RS-485 module per the Unipi Extension xS11 Modbus map v2.0.
Also known as: Unipi Extension xS11, xS11 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS51 I/O module
Unipi Extension xS51 RS-485 module per the Unipi Extension xS51 Modbus map v2.0.
Also known as: Unipi Extension xS51, xS51 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS52 resistance input module
Unipi Extension xS52 RS-485 module per the Unipi Extension xS52 Modbus map v2.0.
Also known as: Unipi Extension xS52, xS52 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS53 analog input module
Unipi Extension xS53 RS-485 module per the Unipi Extension xS53 Modbus map v2.0.
Also known as: Unipi Extension xS53, xS53 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS54 universal analog input module
Unipi Extension xS54 RS-485 module per the Unipi Extension xS54 Modbus map v2.0.
Also known as: Unipi Extension xS54, xS54
Other ac & vrf gateways register maps
- VRF / split AC gateway
Daikin EKMBDXB Modbus Interface DIII
EKMBDXB7V1 Modbus RTU interface on the DIII-net of Daikin VRV, Sky Air, split (via KRP928), VAM/VKM ventilation, VRV hydrobox, air curtains, ERQ control box, heating and applied units; design guide 4P642495-1A (2022.02).
Also known as: EKMBDXB7V1, Modbus Interface DIII - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485DAI001A000 gateway for Daikin Altherma 3 air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.2 (2025-07-18).
Also known as: IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Intesis Modbus Server - Fujitsu VRF, order code INMBSFGL016O000 (legacy FJ-AC-MBS-16), user manual r1.0 (02/2020); up to 16 indoor units configured in MAPS.
Also known as: INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI001R000 Mitsubishi Heavy Industries AC to Modbus RTU gateway
Mitsubishi Heavy Industries indoor units (one, or up to 16 controlled together as one) on the XY remote-controller bus, user manual r6.4 (01/2024).
Also known as: INMBSMHI001R000, MH-RC-MBS-1, Intesis Mitsubishi Heavy Industries Modbus, Intesis MHI Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
Panasonic Etherea-line domestic split units, user's manual r1.5 (09/2025). Some registers only on 2013 (PKE series) and later models.
Also known as: INMBSPAN001I100, Intesis Panasonic Etherea Modbus, Intesis Panasonic domestic Modbus
All ac & vrf gateways Modbus register maps →
Source: Extension xG18 Modbus map · v1.1. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.