Sensor (1-Wire temperature gateway) · Modbus register map

Unipi Technology Unipi Extension xG18 1-Wire temperature gateway Modbus register map

Updated 19 November 2026

Short answer

The Unipi Extension xG18 is an RS-485 Modbus RTU gateway for up to eight Unipi 1-Wire temperature sensors, one per channel. The map gives each channel's temperature in hundredths of a degree, a validity bit word, measuring intervals, the master watchdog and RS-485 configuration.

This page lists 31 Modbus registers for the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Unipi Technology’s own free documentation (linked below) and checked against it.

Manufacturer
Unipi Technology
Model
Unipi Extension xG18 1-Wire temperature gateway
Equipment type
Sensor (1-Wire temperature gateway)
Registers
31 (16 writable)
Transport
Modbus RTU
Default unit ID
15
Default serial
19200 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
CDAB low word first (word-swapped)
Also known as
Unipi Extension xG18, xG18
Source document
Extension xG18 Modbus map · v1.1
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Unipi Technology Unipi Extension xG18 1-Wire temperature gateway

Integration in brief

Read temperatures CH1-CH8 at registers 1-8 (signed, x0.01 °C) and check the validity bits at register 9 before trusting a value.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Temperature CH1INT16Temperature CH1Read
HR 2Temperature CH2INT16Temperature CH2Read
HR 9Temperature validityBITMAP16Temperature validity bitsRead/write
HR 1010Measuring interval CH1 (seconds)UINT16CH1 measuring intervalRead/write
HR 1019Modbus Address Configuration (1-254)UINT16Modbus addressRead/write

Enable Modbus control & writes

Modbus RTU is the native interface; nothing needs enabling. Factory settings are address 15, 19200 bps, 8N1.

Communication loss & watchdog

Master watchdog (MWD): enable it with bit 0 of register 0 and set the timeout in register 1008 (default 5000 ms). A watchdog reboot is flagged in bit 1 of register 0 and in coil 1000; the map does not describe the timeout behaviour further.

Byte order & addressing

Network setup

Unipi Technology Unipi Extension xG18 1-Wire temperature gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

31 of 31 shown
Unipi Technology Unipi Extension xG18 1-Wire temperature gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO1000doc 0x03E8MWD reset indicationSet when the master watchdog has reset the module.BITRead/write
CO1002doc 0x03EAReset group MCUWrite 1 to reset the module processor.BITRead/write
CO1003doc 0x03EBSave current configuration and use on startupWrite 1 to store the current settings as power-up defaults.BITRead/write
HR0doc 0x0000Group MasterWatchDog (MWD) StatusBITMAP16Read/writebit 0 = MWD Enable; bit 1 = MWD Reboot Detected
HR1doc 0x0001Temperature CH11-Wire temperature in 0.01 °C; reads -32768 by default (no reading).INT16× 0.01°CRead
HR2doc 0x0002Temperature CH21-Wire temperature in 0.01 °C; reads -32768 by default (no reading).INT16× 0.01°CRead
HR3doc 0x0003Temperature CH31-Wire temperature in 0.01 °C; reads -32768 by default (no reading).INT16× 0.01°CRead
HR4doc 0x0004Temperature CH41-Wire temperature in 0.01 °C; reads -32768 by default (no reading).INT16× 0.01°CRead
HR5doc 0x0005Temperature CH51-Wire temperature in 0.01 °C; reads -32768 by default (no reading).INT16× 0.01°CRead
HR6doc 0x0006Temperature CH61-Wire temperature in 0.01 °C; reads -32768 by default (no reading).INT16× 0.01°CRead
HR7doc 0x0007Temperature CH71-Wire temperature in 0.01 °C; reads -32768 by default (no reading).INT16× 0.01°CRead
HR8doc 0x0008Temperature CH81-Wire temperature in 0.01 °C; reads -32768 by default (no reading).INT16× 0.01°CRead
HR9doc 0x0009Temperature validityBITMAP16Read/writebit 0 = CH1; bit 1 = CH2; bit 2 = CH3; bit 3 = CH4; bit 4 = CH5; bit 5 = CH6; bit 6 = CH7; bit 7 = CH8
HR1000doc 0x03E8Firmware VersionUINT16Read
HR1001doc 0x03E9Number of I/OsPacked counts: bits 0-7 DOs, bits 8-15 DIs.UINT16Read
HR1002doc 0x03EANumber of peripheralsPacked counts: bits 0-3 RS485 lines, bits 4-7 AOs, bits 8-15 AIs.UINT16Read
HR1003doc 0x03EBFirmware IDUINT16Read
HR1004doc 0x03ECHardware IDUINT16Read
HR1005doc 0x03EDPCB Serial NumberUINT32CDABRead
HR1008doc 0x03F0MasterWatchDog (MWD) Timeout (ms)Master watchdog timeout; default 5000 ms.UINT16msRead/write
HR1009doc 0x03F1VRef of MCUUINT16Read
HR1010doc 0x03F2Measuring interval CH1 (seconds)Measurement interval for this channel (default 2 s).UINT16sRead/write
HR1011doc 0x03F3Measuring interval CH2 (seconds)Measurement interval for this channel (default 2 s).UINT16sRead/write
HR1012doc 0x03F4Measuring interval CH3 (seconds)Measurement interval for this channel (default 2 s).UINT16sRead/write
HR1013doc 0x03F5Measuring interval CH4 (seconds)Measurement interval for this channel (default 2 s).UINT16sRead/write
HR1014doc 0x03F6Measuring interval CH5 (seconds)Measurement interval for this channel (default 2 s).UINT16sRead/write
HR1015doc 0x03F7Measuring interval CH6 (seconds)Measurement interval for this channel (default 2 s).UINT16sRead/write
HR1016doc 0x03F8Measuring interval CH7 (seconds)Measurement interval for this channel (default 2 s).UINT16sRead/write
HR1017doc 0x03F9Measuring interval CH8 (seconds)Measurement interval for this channel (default 2 s).UINT16sRead/write
HR1018doc 0x03FARS485 Configuration - see Description sheetBits 0-12 baud code, bit 13 parity on, bit 14 odd parity; default 14 (19200 8N1).UINT16Read/write
HR1019doc 0x03FBModbus Address Configuration (1-254)Modbus RTU slave address (default 15).UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway

What Modbus registers does the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway have?

This map lists 31 registers: 3 coils, 28 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map lists each register in decimal and hex starting at 0; the number is the wire address.

What byte order does the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway?

Start with HR 1 Temperature CH1 (Temperature CH1); HR 2 Temperature CH2 (Temperature CH2); HR 9 Temperature validity (Temperature validity bits); HR 1010 Measuring interval CH1 (seconds) (CH1 measuring interval); HR 1019 Modbus Address Configuration (1-254) (Modbus address).

How do I enable Modbus control of the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway?

Modbus RTU is the native interface; nothing needs enabling. Factory settings are address 15, 19200 bps, 8N1.

What happens when the Unipi Technology Unipi Extension xG18 1-Wire temperature gateway loses Modbus communication?

Master watchdog (MWD): enable it with bit 0 of register 0 and set the timeout in register 1008 (default 5000 ms). A watchdog reboot is flagged in bit 1 of register 0 and in coil 1000; the map does not describe the timeout behaviour further.

Where is the official Unipi Technology Unipi Extension xG18 1-Wire temperature gateway Modbus documentation?

The source is Extension xG18 Modbus map (v1.1), published free by Unipi Technology at https://kb.unipi.technology/_media/files:products:extensions:unipi-extension-xg18-modbus-map-v1.0.pdf.