- INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
VRF / split AC gateway · Modbus register map
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) Modbus register map
Updated 19 November 2026
Multi-unit Modbus server that joins a Fujitsu VRF network and exposes every configured indoor unit as its own 100-register block, plus outdoor-unit status blocks and 'all units' broadcast commands. Modbus RTU and Modbus TCP run at the same time. The map lists the first indoor unit and the first outdoor unit; other units follow a fixed formula.
This page lists 46 Modbus registers for the Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.
- Manufacturer
- Intesis (HMS Networks)
- Model
- INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
- Equipment type
- VRF / split AC gateway
- Registers
- 46 (33 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF
Integration notes: Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Configure the indoor units, IDs and Modbus port in Intesis MAPS, send the project, then poll each unit's 100-register block from (ID+1) x 100. Write on/off, mode, fan and setpoint (tenths) in the same block.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 100 | IU on/off | INT16 | Indoor unit on/off | Read/write |
| HR 101 | IU operation mode | INT16 | Operation mode | Read/write |
| HR 102 | IU fan speed | INT16 | Fan speed | Read/write |
| HR 105 | IU temperature setpoint | INT16 | Setpoint (x10) | Read/write |
| HR 106 | IU ambient temperature | INT16 | Room temperature (x10) | Read |
| HR 114 | IU unit error | INT16 | Unit error flag | Read |
| HR 115 | IU unit error code | INT16 | Error code | Read |
| HR 118 | IU communication error | INT16 | Gateway-to-unit communication error | Read |
Enable Modbus control & writes
Indoor units must be added in the MAPS 'Fujitsu VRF configuration' and the project sent to the gateway.
Byte order & addressing
- Every register is a 16-bit signed integer; there are no 32-bit values (unless stated in this file).
- Read with FC03 or FC04; write with FC06 or FC16.
- Undefined addresses in the 0..20000 poll range read back 0; the manual also says invalid addresses return a Modbus exception code.
- Broadcast registers 3..16 act on every configured unit and are write-only.
Network setup
- All Modbus settings (RTU slave number, baud 1200..115200, parity, stop bits, RS-485 or RS-232, TCP port, IP) are set with the Intesis MAPS tool over the USB console port or Ethernet.
- Factory IP is 192.168.100.246 with DHCP enabled.
- Modbus RTU and Modbus TCP can be used at the same time.
- Port B carries Modbus RTU on B1, B2 and B3 (SGND). The manual prints the B1/B2 polarity both ways in two sections, so check the terminal label. A DIP switch enables 120 ohm termination and bias.
Watch out for
- Indoor block number comes from the MAPS ID (+1), so ID 0 lives at 100, not 0.
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Gateway energy saving | INT16 | Read/write | 0 = Disable energy saving; 1 = Enable energy saving | ||||
| HR | 1 | Gateway error | INT16 | Read | 0 = Normal; 1 = Error | ||||
| HR | 2 | Gateway error code | INT16 | Read | 0 = No error; 1 = Communication error; 2 = No configuration error | ||||
| HR | 3 | On (all units) | INT16 | Write | 1 = Switch all units on | ||||
| HR | 4 | Off (all units) | INT16 | Write | 1 = Switch all units off | ||||
| HR | 5 | Mode Auto (all units) | INT16 | Write | 1 = Set Auto | ||||
| HR | 6 | Mode Heat (all units) | INT16 | Write | 1 = Set Heat | ||||
| HR | 7 | Mode Dry (all units) | INT16 | Write | 1 = Set Dry | ||||
| HR | 8 | Mode Fan (all units) | INT16 | Write | 1 = Set Fan | ||||
| HR | 9 | Mode Cool (all units) | INT16 | Write | 1 = Set Cool | ||||
| HR | 10 | Fan speed Auto (all units) | INT16 | Write | 1 = Set fan Auto | ||||
| HR | 11 | Fan speed Quiet (all units) | INT16 | Write | 1 = Set fan Quiet | ||||
| HR | 12 | Fan speed Low (all units) | INT16 | Write | 1 = Set fan Low | ||||
| HR | 13 | Fan speed Med-Low (all units) | INT16 | Write | 1 = Set fan Mid-Low | ||||
| HR | 14 | Fan speed Med-High (all units) | INT16 | Write | 1 = Set fan Mid-High | ||||
| HR | 15 | Fan speed High (all units) | INT16 | Write | 1 = Set fan High | ||||
| HR | 16 | Temperature setpoint (all units) | Tenths of a degree. Cool 19..30, Heat 17..30. | INT16 | × 0.1 | °C | Write | ||
| HR | 100doc (ID+1)*100 +0 | IU on/off | Indoor unit ID 0 shown; see notes for other IDs. | INT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 101doc (ID+1)*100 +1 | IU operation mode | INT16 | Read/write | 0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool | ||||
| HR | 102doc (ID+1)*100 +2 | IU fan speed | 4-speed: 0 Auto,1 Quiet,2 Low,3 Med,4 High. 6-speed: 3 Med-Low,4 Med-High,5 High. | INT16 | Read/write | ||||
| HR | 103doc (ID+1)*100 +3 | IU vane position up-down | INT16 | Read/write | 1 = Pos 1; 2 = Pos 2; 3 = Pos 3; 4 = Pos 4; 10 = Swing | ||||
| HR | 104doc (ID+1)*100 +4 | IU vane position left-right | INT16 | Read/write | 1 = Pos 1; 2 = Pos 2; 3 = Pos 3; 4 = Pos 4; 5 = Pos 5; 10 = Swing | ||||
| HR | 105doc (ID+1)*100 +5 | IU temperature setpoint | Tenths of a degree (°C or °F per MAPS setting). Cool 19..30, Heat 17..30 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 106doc (ID+1)*100 +6 | IU ambient temperature | Tenths of a degree (°C or °F per MAPS setting). 0..63.5 °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 107doc (ID+1)*100 +7 | IU temperature limit valid | INT16 | Read | 0 = Invalid; 1 = Valid | ||||
| HR | 108doc (ID+1)*100 +8 | IU heat setpoint upper limit | Tenths; 10..30 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 109doc (ID+1)*100 +9 | IU heat setpoint lower limit | Tenths; 10..30 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 110doc (ID+1)*100 +10 | IU cool setpoint upper limit | Tenths; 10..30 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 111doc (ID+1)*100 +11 | IU cool setpoint lower limit | Tenths; 10..30 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 112doc (ID+1)*100 +12 | IU auto setpoint upper limit | Tenths; 10..30 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 113doc (ID+1)*100 +13 | IU auto setpoint lower limit | Tenths; 10..30 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 114doc (ID+1)*100 +14 | IU unit error | INT16 | Read | 0 = No error; 1 = Error | ||||
| HR | 115doc (ID+1)*100 +15 | IU unit error code | 0 = no error, any other value = Fujitsu error code. | INT16 | Read | ||||
| HR | 116doc (ID+1)*100 +16 | IU filter alarm | INT16 | Read | 0 = Normal; 1 = Alarm | ||||
| HR | 117doc (ID+1)*100 +17 | IU filter alarm reset | INT16 | Write | 1 = Reset | ||||
| HR | 118doc (ID+1)*100 +18 | IU communication error | INT16 | Read | 0 = No error; 1 = Error | ||||
| HR | 119doc (ID+1)*100 +19 | IU emergency | INT16 | Read | 0 = Off; 1 = On | ||||
| HR | 120doc (ID+1)*100 +20 | IU allow full control from RC | INT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 121doc (ID+1)*100 +21 | IU allow on/off from RC | INT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 122doc (ID+1)*100 +22 | IU allow mode from RC | INT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 123doc (ID+1)*100 +23 | IU allow setpoint from RC | INT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 124doc (ID+1)*100 +24 | IU thermo off | Values as printed in the manual. | INT16 | Read/write | 0 = Thermo OFF; 1 = Thermo ON | |||
| HR | 10025doc (ID+1)*25+10000+0 | OU capacity save | Outdoor unit ID 0 shown; see notes for other IDs. | INT16 | Read | 0 = Not set; 1 = 100%; 2 = 90%; 3 = 80%; 4 = 70%; 5 = 60%; 6 = 50%; 7 = 40% | |||
| HR | 10026doc (ID+1)*25+10000+1 | OU forced off | INT16 | Read | 0 = Not forced; 1 = Forced off | ||||
| HR | 10027doc (ID+1)*25+10000+2 | OU error | INT16 | Read | 0 = No error; 1 = Error | ||||
| HR | 10028doc (ID+1)*25+10000+3 | OU error code | 0 = no error, any other value = error code. | INT16 | Read |
Notes on this map
- Only indoor unit ID 0 and outdoor unit ID 0 are listed. For indoor ID n add n x 100 to the listed indoor address (ID 1 on/off = 200); for outdoor ID n add n x 25 (ID 1 error = 10052).
- The ID is the 'ID' field of the Fujitsu VRF configuration in MAPS (0..31), not the Fujitsu refrigerant address.
- Temperatures are tenths of a degree in °C or °F depending on the temperature scale chosen in MAPS; °C is shown here.
- Fan-speed register 102 has two value sets depending on whether the indoor unit has 4 or 6 speeds, so no single enum is given.
- The manual prints register 124 as '0 = Thermo OFF, 1 = Thermo ON'; it is copied as printed.
- The Fujitsu error code list is in the manual; not reproduced here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
What Modbus registers does the Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) have?
This map lists 46 registers: 46 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states the formula results are link-layer addresses with the first register at 0, so the printed numbers go on the wire unchanged. Indoor unit with MAPS ID n (0..31) uses (n+1) x 100 + offset; outdoor unit ID n uses (n+1) x 25 + 10000 + offset. This file lists ID 0 (indoor 100..124, outdoor 10025..10028).
What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)?
Start with HR 100 IU on/off (Indoor unit on/off); HR 101 IU operation mode (Operation mode); HR 102 IU fan speed (Fan speed); HR 105 IU temperature setpoint (Setpoint (x10)); HR 106 IU ambient temperature (Room temperature (x10)); HR 114 IU unit error (Unit error flag); HR 115 IU unit error code (Error code); HR 118 IU communication error (Gateway-to-unit communication error).
How do I enable Modbus control of the Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)?
Indoor units must be added in the MAPS 'Fujitsu VRF configuration' and the project sent to the gateway.
Where is the official Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) Modbus documentation?
The source is Intesis Modbus Server - Fujitsu VRF User Manual (User Manual r1.0 EN), revision 2020-02, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsfgl016o000.pdf.
More Intesis (HMS Networks) Modbus register maps
- Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485DAI001A000 gateway for Daikin Altherma 3 air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.2 (2025-07-18).
Also known as: IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485MIT001A000 Mitsubishi Electric Ecodan air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485MIT001A000 gateway on the CN105 socket of Mitsubishi Electric Ecodan air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.3 (2025-12-02).
Also known as: IN485MIT001A000, Ecodan Modbus, Mitsubishi Ecodan Modbus RTU, Intesis Ecodan, HMS Ecodan gateway - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Midea application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.22 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA004I000 / 008I000 / 032I000 XYE-bus air conditioner to Modbus RTU interface (4 to 32 units)
INMBSACA004I000 / INMBSACA008I000 / INMBSACA032I000, user manual v1.8 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSACA004I000, INMBSACA008I000, INMBSACA032I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
Hisense commercial-line indoor units on the AB remote-controller bus, user manual v1.6 (01/2024).
Also known as: INMBSHIS001R000, HS-RC-MBS-1, Intesis Hisense Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hitachi VRF, order codes INMBSHIT016O000 / INMBSHIT064O000 (legacy HI-AC-MBS-16 / HI-AC-MBS-64), user manual User Manual r1.2 EN.
Also known as: INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway
One LG indoor unit on the BYR (wired remote) bus via INMBSLGE001R000 (legacy code LG-RC-MBS-1), user manual v1.9 (01/2024).
Also known as: INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI001R000 Mitsubishi Heavy Industries AC to Modbus RTU gateway
Mitsubishi Heavy Industries indoor units (one, or up to 16 controlled together as one) on the XY remote-controller bus, user manual r6.4 (01/2024).
Also known as: INMBSMHI001R000, MH-RC-MBS-1, Intesis Mitsubishi Heavy Industries Modbus, Intesis MHI Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
Intesis Modbus Server - Mitsubishi Heavy Industries AC, order codes INMBSMHI128O000 (128 units, Superlink-II) and INMBSMHI048O000 (48 units, Superlink-I or II), user's manual r1.0 (05/2012).
Also known as: INMBSMHI128O000, INMBSMHI048O000, MH-AC-MBS-128, MH-AC-MBS-48, Intesis Modbus Server MHI Superlink - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway
One Midea commercial / VRF indoor unit on the XYE bus, user manual v1.11.
Also known as: INMBSMID001I000, Intesis Midea Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
INMBSMID004I000 / INMBSMID008I000 / INMBSMID032I000 / MD-AC-MBS-4 / MD-AC-MBS-8 / MD-AC-MBS-32, user manual v1.7 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32 - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway
One Mitsubishi Electric Domestic, Mr. Slim or City Multi indoor unit via INMBSMIT001I000, user manual r2.8 (11/2024).
Also known as: INMBSMIT001I000, Intesis Mitsubishi Electric Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
Intesis Modbus Server - Mitsubishi Electric CC, order codes INMBSMIT050C000 / INMBSMIT100C000 (legacy ME-AC-MBS-50 / -100), user manual r1.4 (05/2021); talks to City Multi centralised controllers (G-50A, GB-50A, AG-150A, EB-50, EW-50, AE-200 and newer) through their XML interface over Ethernet.
Also known as: INMBSMIT050C000, INMBSMIT100C000, ME-AC-MBS-50, ME-AC-MBS-100, Intesis Modbus Server Mitsubishi Electric CC - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Intesis (HMS Networks) INMBSPAN001A100 gateway connected to Panasonic Aquarea H, J, K, L and M series air-to-water heat pumps, per user manual version 1.0.2 (2026-02-04).
Also known as: INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code) - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
Panasonic Etherea-line domestic split units, user's manual r1.5 (09/2025). Some registers only on 2013 (PKE series) and later models.
Also known as: INMBSPAN001I100, Intesis Panasonic Etherea Modbus, Intesis Panasonic domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001R000 Panasonic AC to Modbus RTU gateway
Panasonic / Sanyo ECOi and PACi indoor units (one, or up to 16 controlled together as one) on the R1R2 remote-controller bus, user manual v2.8 (09/2025).
Also known as: INMBSPAN001R000, PA-RC2-MBS-1, Intesis Panasonic Modbus, Intesis Sanyo Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
Intesis Modbus Server - Panasonic, order codes INMBSPAN016O000 / 064O000 / 128O000 (legacy PA-AC-MBS-16 / -64 / -128), user manual r1.1 (11/2020); Panasonic P-Link systems.
Also known as: INMBSPAN016O000, INMBSPAN064O000, INMBSPAN128O000, PA-AC-MBS-16, PA-AC-MBS-64, PA-AC-MBS-128, Intesis Modbus Server Panasonic VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway
Samsung commercial indoor units on the F3F4/V1V2 remote-controller bus, user's manual v1.5 (01/2024).
Also known as: INMBSSAM001R000, Intesis Samsung Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway
Samsung NASA-protocol commercial indoor units on the remote-controller bus, user's manual r1.4 (01/2024).
Also known as: INMBSSAM001R100, Intesis Samsung NASA Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM016O000 Samsung NASA (R1/R2) VRF to Modbus gateway (4 to 64 units)
Intesis Modbus Server - Samsung NASA, order codes INMBSSAM004O000 / 008O000 / 016O000 / 064O000 (legacy SM-ACN-MBS-4/8/16/64), user manual r1.4 (12/2020); Samsung NASA R1/R2 bus.
Also known as: INMBSSAM004O000, INMBSSAM008O000, INMBSSAM016O000, INMBSSAM064O000, SM-ACN-MBS-4, SM-ACN-MBS-8, SM-ACN-MBS-16, SM-ACN-MBS-64 - VRF / split AC gateway
Intesis (HMS Networks) INMBSTOS001R000 Toshiba AC to Modbus RTU gateway
Toshiba Digital Inverter (RAV) and VRF indoor units on the AB remote bus via INMBSTOS001R0xx, user manual r2.9 (01/2024).
Also known as: INMBSTOS001R000, INMBSTOS001R0xx, Intesis Toshiba Modbus
Other ac & vrf gateways register maps
- Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)
LG PAHCMR000 AHU Communication Kit (R32 and R410A Multi V / single split outdoor units with a PRLK EEV kit), installation manual IM_AHU_Comm_Kit_PAHCMR000_R32_06_26.
Also known as: PAHCMR000, LG AHU Communication Kit R32, LG AHU comm kit Modbus - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - VRF / split AC gateway (built-in indoor-unit Modbus)
Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)
Sinclair All DC Inverter UNI SPLIT indoor units with the built-in Modbus RTU interface, per the UNI SPLIT Modbus user's manual.
Also known as: Sinclair UNI SPLIT, UNI SPLIT Modbus, All DC Inverter UNI SPLIT - Split AC unit (VRF / split AC gateway built in)
Aermec LPG series DC inverter air conditioners (built-in Modbus)
Aermec LPG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; ModBus Protocol LPG series 5385759_02 (EN 25.05).
Also known as: LPG - Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI
All ac & vrf gateways Modbus register maps →
Source: Intesis Modbus Server - Fujitsu VRF User Manual · User Manual r1.0 EN · rev. 2020-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.