  3. Intesis (HMS Networks)
  4. INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)

VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) Modbus register map

Updated 19 November 2026

Short answer

Multi-unit Modbus server that joins a Fujitsu VRF network and exposes every configured indoor unit as its own 100-register block, plus outdoor-unit status blocks and 'all units' broadcast commands. Modbus RTU and Modbus TCP run at the same time. The map lists the first indoor unit and the first outdoor unit; other units follow a fixed formula.

This page lists 46 Modbus registers for the Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Equipment type
VRF / split AC gateway
Registers
46 (33 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF
Source document
Intesis Modbus Server - Fujitsu VRF User Manual · User Manual r1.0 EN · rev. 2020-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)

Integration in brief

Configure the indoor units, IDs and Modbus port in Intesis MAPS, send the project, then poll each unit's 100-register block from (ID+1) x 100. Write on/off, mode, fan and setpoint (tenths) in the same block.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100IU on/offINT16Indoor unit on/offRead/write
HR 101IU operation modeINT16Operation modeRead/write
HR 102IU fan speedINT16Fan speedRead/write
HR 105IU temperature setpointINT16Setpoint (x10)Read/write
HR 106IU ambient temperatureINT16Room temperature (x10)Read
HR 114IU unit errorINT16Unit error flagRead
HR 115IU unit error codeINT16Error codeRead
HR 118IU communication errorINT16Gateway-to-unit communication errorRead

Enable Modbus control & writes

Indoor units must be added in the MAPS 'Fujitsu VRF configuration' and the project sent to the gateway.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

46 of 46 shown
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0Gateway energy savingINT16Read/write0 = Disable energy saving; 1 = Enable energy saving
HR1Gateway errorINT16Read0 = Normal; 1 = Error
HR2Gateway error codeINT16Read0 = No error; 1 = Communication error; 2 = No configuration error
HR3On (all units)INT16Write1 = Switch all units on
HR4Off (all units)INT16Write1 = Switch all units off
HR5Mode Auto (all units)INT16Write1 = Set Auto
HR6Mode Heat (all units)INT16Write1 = Set Heat
HR7Mode Dry (all units)INT16Write1 = Set Dry
HR8Mode Fan (all units)INT16Write1 = Set Fan
HR9Mode Cool (all units)INT16Write1 = Set Cool
HR10Fan speed Auto (all units)INT16Write1 = Set fan Auto
HR11Fan speed Quiet (all units)INT16Write1 = Set fan Quiet
HR12Fan speed Low (all units)INT16Write1 = Set fan Low
HR13Fan speed Med-Low (all units)INT16Write1 = Set fan Mid-Low
HR14Fan speed Med-High (all units)INT16Write1 = Set fan Mid-High
HR15Fan speed High (all units)INT16Write1 = Set fan High
HR16Temperature setpoint (all units)Tenths of a degree. Cool 19..30, Heat 17..30.INT16× 0.1°CWrite
HR100doc (ID+1)*100 +0IU on/offIndoor unit ID 0 shown; see notes for other IDs.INT16Read/write0 = Off; 1 = On
HR101doc (ID+1)*100 +1IU operation modeINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR102doc (ID+1)*100 +2IU fan speed4-speed: 0 Auto,1 Quiet,2 Low,3 Med,4 High. 6-speed: 3 Med-Low,4 Med-High,5 High.INT16Read/write
HR103doc (ID+1)*100 +3IU vane position up-downINT16Read/write1 = Pos 1; 2 = Pos 2; 3 = Pos 3; 4 = Pos 4; 10 = Swing
HR104doc (ID+1)*100 +4IU vane position left-rightINT16Read/write1 = Pos 1; 2 = Pos 2; 3 = Pos 3; 4 = Pos 4; 5 = Pos 5; 10 = Swing
HR105doc (ID+1)*100 +5IU temperature setpointTenths of a degree (°C or °F per MAPS setting). Cool 19..30, Heat 17..30 °C.INT16× 0.1°CRead/write
HR106doc (ID+1)*100 +6IU ambient temperatureTenths of a degree (°C or °F per MAPS setting). 0..63.5 °C.INT16× 0.1°CRead
HR107doc (ID+1)*100 +7IU temperature limit validINT16Read0 = Invalid; 1 = Valid
HR108doc (ID+1)*100 +8IU heat setpoint upper limitTenths; 10..30 °C.INT16× 0.1°CRead/write
HR109doc (ID+1)*100 +9IU heat setpoint lower limitTenths; 10..30 °C.INT16× 0.1°CRead/write
HR110doc (ID+1)*100 +10IU cool setpoint upper limitTenths; 10..30 °C.INT16× 0.1°CRead/write
HR111doc (ID+1)*100 +11IU cool setpoint lower limitTenths; 10..30 °C.INT16× 0.1°CRead/write
HR112doc (ID+1)*100 +12IU auto setpoint upper limitTenths; 10..30 °C.INT16× 0.1°CRead/write
HR113doc (ID+1)*100 +13IU auto setpoint lower limitTenths; 10..30 °C.INT16× 0.1°CRead/write
HR114doc (ID+1)*100 +14IU unit errorINT16Read0 = No error; 1 = Error
HR115doc (ID+1)*100 +15IU unit error code0 = no error, any other value = Fujitsu error code.INT16Read
HR116doc (ID+1)*100 +16IU filter alarmINT16Read0 = Normal; 1 = Alarm
HR117doc (ID+1)*100 +17IU filter alarm resetINT16Write1 = Reset
HR118doc (ID+1)*100 +18IU communication errorINT16Read0 = No error; 1 = Error
HR119doc (ID+1)*100 +19IU emergencyINT16Read0 = Off; 1 = On
HR120doc (ID+1)*100 +20IU allow full control from RCINT16Read/write0 = Allow; 1 = Not allow
HR121doc (ID+1)*100 +21IU allow on/off from RCINT16Read/write0 = Allow; 1 = Not allow
HR122doc (ID+1)*100 +22IU allow mode from RCINT16Read/write0 = Allow; 1 = Not allow
HR123doc (ID+1)*100 +23IU allow setpoint from RCINT16Read/write0 = Allow; 1 = Not allow
HR124doc (ID+1)*100 +24IU thermo offValues as printed in the manual.INT16Read/write0 = Thermo OFF; 1 = Thermo ON
HR10025doc (ID+1)*25+10000+0OU capacity saveOutdoor unit ID 0 shown; see notes for other IDs.INT16Read0 = Not set; 1 = 100%; 2 = 90%; 3 = 80%; 4 = 70%; 5 = 60%; 6 = 50%; 7 = 40%
HR10026doc (ID+1)*25+10000+1OU forced offINT16Read0 = Not forced; 1 = Forced off
HR10027doc (ID+1)*25+10000+2OU errorINT16Read0 = No error; 1 = Error
HR10028doc (ID+1)*25+10000+3OU error code0 = no error, any other value = error code.INT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)

What Modbus registers does the Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) have?

This map lists 46 registers: 46 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states the formula results are link-layer addresses with the first register at 0, so the printed numbers go on the wire unchanged. Indoor unit with MAPS ID n (0..31) uses (n+1) x 100 + offset; outdoor unit ID n uses (n+1) x 25 + 10000 + offset. This file lists ID 0 (indoor 100..124, outdoor 10025..10028).

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)?

Start with HR 100 IU on/off (Indoor unit on/off); HR 101 IU operation mode (Operation mode); HR 102 IU fan speed (Fan speed); HR 105 IU temperature setpoint (Setpoint (x10)); HR 106 IU ambient temperature (Room temperature (x10)); HR 114 IU unit error (Unit error flag); HR 115 IU unit error code (Error code); HR 118 IU communication error (Gateway-to-unit communication error).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)?

Indoor units must be added in the MAPS 'Fujitsu VRF configuration' and the project sent to the gateway.

Where is the official Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units) Modbus documentation?

The source is Intesis Modbus Server - Fujitsu VRF User Manual (User Manual r1.0 EN), revision 2020-02, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsfgl016o000.pdf.

More Intesis (HMS Networks) Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Intesis Modbus Server - Fujitsu VRF User Manual · User Manual r1.0 EN · rev. 2020-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.