- INMBSHIS001R000 Hisense AC to Modbus RTU gateway
VRF / split AC gateway · Modbus register map
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway Modbus register map
Updated 17 November 2026
Modbus RTU server that connects to the AB remote-controller bus of a Hisense commercial indoor unit. Holding registers cover on/off, mode, fan, vane, setpoint, external temperature input, window contact, alarm and error code, min/max setpoints, return-air temperature and gateway configuration.
This page lists 30 Modbus registers for the Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.
- Manufacturer
- Intesis (HMS Networks)
- Model
- INMBSHIS001R000 Hisense AC to Modbus RTU gateway
- Equipment type
- VRF / split AC gateway
- Registers
- 30 (15 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- INMBSHIS001R000, HS-RC-MBS-1, Intesis Hisense Modbus
Integration notes: Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
Set address and baud on SW3/SW4, wire A+/B- to the EIA-485 bus and AB to the indoor unit, then write registers 0-4 and poll 5, 10, 11 and 66. Write room temperature to register 22 if a Modbus-side sensor should drive the unit.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | AC unit On/Off | UINT16 | On/off | Read/write |
| HR 1 | AC unit mode | UINT16 | Mode | Read/write |
| HR 4 | AC unit temperature setpoint | UINT16 | Setpoint | Read/write |
| HR 2 | AC unit fan speed | UINT16 | Fan speed | Read/write |
| HR 5 | AC unit temperature reference | UINT16 | Control temperature | Read |
| HR 10 | AC unit alarm status | UINT16 | Alarm flag | Read |
| HR 11 | Error code | UINT16 | Error code | Read |
Enable Modbus control & writes
No enable step; writes act at once unless register 7 (gateway disablement) is set to 1.
Byte order & addressing
- Temperature scale depends on SW4 (x1 / x10 / °F).
- With an external temperature written to 22, the gateway shifts the real setpoint (register 23) so the unit's own sensor tracks your setpoint; the wall controller may then show a different setpoint.
- FC16 writes must be one register long.
Network setup
- 8N2 (8N1 detected automatically), 9600 baud default, set on SW3/SW4.
- Slave address 1..63 on SW3.
- SW1 sets the gateway as AB-bus slave (default, needs a Hisense remote as master) or master.
- 120 ohm terminator selectable on SW4.
Watch out for
- When the gateway is AB-bus slave, a Hisense remote controller configured as master must be present.
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | AC unit On/Off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 1 | AC unit mode | Available modes depend on the indoor unit. | UINT16 | Read/write | 0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool | |||
| HR | 2 | AC unit fan speed | Available speeds depend on the indoor unit. | UINT16 | Read/write | 0 = Auto; 1 = Low; 2 = Mid; 3 = High; 4 = Super-high | |||
| HR | 3 | AC unit vane position | Availability depends on the indoor unit. | UINT16 | Read/write | 1 = POS1 (Horizontal); 2 = POS2 (Horizontal); 3 = POS3 (Med); 4 = POS4 (Vert); 5 = POS5 (Vert); 6 = POS6; 7 = POS7; 10 = Swing | |||
| HR | 4 | AC unit temperature setpoint | 16..32 °C (61..90 °F). SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read/write | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 5 | AC unit temperature reference | Temperature the indoor unit controls on. SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 6 | Window contact | Virtual window contact written from Modbus. | UINT16 | Read/write | 0 = Closed; 1 = Open | |||
| HR | 7 | Gateway disablement | Stored in non-volatile memory. | UINT16 | Read/write | 0 = Gateway enabled; 1 = Gateway disabled | |||
| HR | 8 | AC remote control disablement | Stored in non-volatile memory. | UINT16 | Read/write | 0 = Remote control enabled; 1 = Remote control disabled | |||
| HR | 9 | AC unit operation time | Hours the unit has been on, 0..65535. Non-volatile. | UINT16 | h | Read/write | |||
| HR | 10 | AC unit alarm status | UINT16 | Read | 0 = No alarm; 1 = Alarm | ||||
| HR | 11 | Error code | Hisense error code; see manual section 6. | UINT16 | Read | 0 = No error; 65535 = Gateway or remote controller cannot talk to the AC unit (-1) | |||
| HR | 13 | Open Window switch-off timeout | Minutes from window open to unit off, 0..30 (default 30). | UINT16 | min | Read/write | |||
| HR | 14 | Modbus RTU baud rate | Rate set on SW3/SW4 (2400..115200, default 9600). | UINT16 | Read | ||||
| HR | 15 | Modbus slave address | Address set on SW3, 1..63. | UINT16 | Read | ||||
| HR | 21 | Max number of fan speeds | UINT16 | Read | |||||
| HR | 22 | External ambient temperature (from Modbus) | Room temperature from a Modbus-side sensor; 0x8000 = none. SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read/write | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 23 | AC real temperature setpoint | Setpoint actually sent to the unit. SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 24 | Current AC max setpoint | SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 25 | Current AC min setpoint | SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 31 | Window status (feedback) | UINT16 | Read | 0 = Not active; 1 = Active (window open) | ||||
| HR | 34 | Left/Right vane pulse | UINT16 | Write | 1 = Pulse | ||||
| HR | 45 | Error reset | UINT16 | Write | 1 = Reset | ||||
| HR | 48 | Switch value | DIP-switch state. | UINT16 | Read | ||||
| HR | 49 | Device ID | Reads 0x2B00. | UINT16 | Read | ||||
| HR | 50 | Software version | UINT16 | Read | |||||
| HR | 66 | Return path temperature | SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 81 | Error address | Indoor unit number that reports the error. | UINT16 | Read | ||||
| HR | 98 | Master/Slave (gateway) | Role of the gateway on the AB bus. | UINT16 | Read/write | 0 = Slave; 1 = Master | |||
| HR | 99 | Reset | Restarts the gateway. | UINT16 | Write | 1 = Reset |
Notes on this map
- The manual declares every register a 16-bit unsigned holding register; the 'no value' marker written as -32768 is raw 0x8000 (32768), listed as an enum entry.
- Temperature registers follow the SW4 setting: x1 °C, x10 °C or °F (no °F x10). The register-table footnote calls x10 the default, but the DIP-switch table marks x1 degrees and Celsius as the factory setting, so scale 1 / °C is used here. Check SW4 on site: with x10 use scale 0.1; with °F the values are whole °F.
- Baud rate (14) is read-only here and is set on SW3/SW4; the manual does not list the numeric codes it returns, so no value table is given.
- FC16 is accepted but only with a length of 1 register per write.
- Error code list (Hisense codes) not reproduced; see manual section 6.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
What Modbus registers does the Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway have?
This map lists 30 registers: 30 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables give a 'protocol address' (base 0) and a 'PLC address' (base 1); the protocol address is the wire address and is used for 'documented'.
What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway?
Start with HR 0 AC unit On/Off (On/off); HR 1 AC unit mode (Mode); HR 4 AC unit temperature setpoint (Setpoint); HR 2 AC unit fan speed (Fan speed); HR 5 AC unit temperature reference (Control temperature); HR 10 AC unit alarm status (Alarm flag); HR 11 Error code (Error code).
How do I enable Modbus control of the Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway?
No enable step; writes act at once unless register 7 (gateway disablement) is set to 1.
Where is the official Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway Modbus documentation?
The source is Intesis INMBSHIS001R000 Modbus RTU (EIA-485) Interface for Hisense air conditioners - User's Manual (User's Manual v1.6 EN), revision 2024-01, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbshis001r000.pdf.
More Intesis (HMS Networks) Modbus register maps
- Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485DAI001A000 gateway for Daikin Altherma 3 air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.2 (2025-07-18).
Also known as: IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485MIT001A000 Mitsubishi Electric Ecodan air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485MIT001A000 gateway on the CN105 socket of Mitsubishi Electric Ecodan air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.3 (2025-12-02).
Also known as: IN485MIT001A000, Ecodan Modbus, Mitsubishi Ecodan Modbus RTU, Intesis Ecodan, HMS Ecodan gateway - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Midea application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.22 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA004I000 / 008I000 / 032I000 XYE-bus air conditioner to Modbus RTU interface (4 to 32 units)
INMBSACA004I000 / INMBSACA008I000 / INMBSACA032I000, user manual v1.8 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSACA004I000, INMBSACA008I000, INMBSACA032I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Intesis Modbus Server - Fujitsu VRF, order code INMBSFGL016O000 (legacy FJ-AC-MBS-16), user manual r1.0 (02/2020); up to 16 indoor units configured in MAPS.
Also known as: INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hitachi VRF, order codes INMBSHIT016O000 / INMBSHIT064O000 (legacy HI-AC-MBS-16 / HI-AC-MBS-64), user manual User Manual r1.2 EN.
Also known as: INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway
One LG indoor unit on the BYR (wired remote) bus via INMBSLGE001R000 (legacy code LG-RC-MBS-1), user manual v1.9 (01/2024).
Also known as: INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI001R000 Mitsubishi Heavy Industries AC to Modbus RTU gateway
Mitsubishi Heavy Industries indoor units (one, or up to 16 controlled together as one) on the XY remote-controller bus, user manual r6.4 (01/2024).
Also known as: INMBSMHI001R000, MH-RC-MBS-1, Intesis Mitsubishi Heavy Industries Modbus, Intesis MHI Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
Intesis Modbus Server - Mitsubishi Heavy Industries AC, order codes INMBSMHI128O000 (128 units, Superlink-II) and INMBSMHI048O000 (48 units, Superlink-I or II), user's manual r1.0 (05/2012).
Also known as: INMBSMHI128O000, INMBSMHI048O000, MH-AC-MBS-128, MH-AC-MBS-48, Intesis Modbus Server MHI Superlink - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway
One Midea commercial / VRF indoor unit on the XYE bus, user manual v1.11.
Also known as: INMBSMID001I000, Intesis Midea Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
INMBSMID004I000 / INMBSMID008I000 / INMBSMID032I000 / MD-AC-MBS-4 / MD-AC-MBS-8 / MD-AC-MBS-32, user manual v1.7 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32 - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway
One Mitsubishi Electric Domestic, Mr. Slim or City Multi indoor unit via INMBSMIT001I000, user manual r2.8 (11/2024).
Also known as: INMBSMIT001I000, Intesis Mitsubishi Electric Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
Intesis Modbus Server - Mitsubishi Electric CC, order codes INMBSMIT050C000 / INMBSMIT100C000 (legacy ME-AC-MBS-50 / -100), user manual r1.4 (05/2021); talks to City Multi centralised controllers (G-50A, GB-50A, AG-150A, EB-50, EW-50, AE-200 and newer) through their XML interface over Ethernet.
Also known as: INMBSMIT050C000, INMBSMIT100C000, ME-AC-MBS-50, ME-AC-MBS-100, Intesis Modbus Server Mitsubishi Electric CC - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Intesis (HMS Networks) INMBSPAN001A100 gateway connected to Panasonic Aquarea H, J, K, L and M series air-to-water heat pumps, per user manual version 1.0.2 (2026-02-04).
Also known as: INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code) - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
Panasonic Etherea-line domestic split units, user's manual r1.5 (09/2025). Some registers only on 2013 (PKE series) and later models.
Also known as: INMBSPAN001I100, Intesis Panasonic Etherea Modbus, Intesis Panasonic domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001R000 Panasonic AC to Modbus RTU gateway
Panasonic / Sanyo ECOi and PACi indoor units (one, or up to 16 controlled together as one) on the R1R2 remote-controller bus, user manual v2.8 (09/2025).
Also known as: INMBSPAN001R000, PA-RC2-MBS-1, Intesis Panasonic Modbus, Intesis Sanyo Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
Intesis Modbus Server - Panasonic, order codes INMBSPAN016O000 / 064O000 / 128O000 (legacy PA-AC-MBS-16 / -64 / -128), user manual r1.1 (11/2020); Panasonic P-Link systems.
Also known as: INMBSPAN016O000, INMBSPAN064O000, INMBSPAN128O000, PA-AC-MBS-16, PA-AC-MBS-64, PA-AC-MBS-128, Intesis Modbus Server Panasonic VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway
Samsung commercial indoor units on the F3F4/V1V2 remote-controller bus, user's manual v1.5 (01/2024).
Also known as: INMBSSAM001R000, Intesis Samsung Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway
Samsung NASA-protocol commercial indoor units on the remote-controller bus, user's manual r1.4 (01/2024).
Also known as: INMBSSAM001R100, Intesis Samsung NASA Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM016O000 Samsung NASA (R1/R2) VRF to Modbus gateway (4 to 64 units)
Intesis Modbus Server - Samsung NASA, order codes INMBSSAM004O000 / 008O000 / 016O000 / 064O000 (legacy SM-ACN-MBS-4/8/16/64), user manual r1.4 (12/2020); Samsung NASA R1/R2 bus.
Also known as: INMBSSAM004O000, INMBSSAM008O000, INMBSSAM016O000, INMBSSAM064O000, SM-ACN-MBS-4, SM-ACN-MBS-8, SM-ACN-MBS-16, SM-ACN-MBS-64 - VRF / split AC gateway
Intesis (HMS Networks) INMBSTOS001R000 Toshiba AC to Modbus RTU gateway
Toshiba Digital Inverter (RAV) and VRF indoor units on the AB remote bus via INMBSTOS001R0xx, user manual r2.9 (01/2024).
Also known as: INMBSTOS001R000, INMBSTOS001R0xx, Intesis Toshiba Modbus
Other ac & vrf gateways register maps
- Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)
LG PAHCMS000 AHU Communication Kit for discharge (supply) air control with up to four LG outdoor units, installation manual IM_AHU_Comm_Kit_PAHCMS000_11_23.
Also known as: PAHCMS000, LG AHU Communication Kit discharge air, LG AHU comm kit PAHCMS000 Modbus - VRF / split AC gateway
Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air
RTD-NET on the Daikin P1/P2 bus (VRV, Sky Air, VAM/VKM), up to 16 indoor units as one group; RTD-10 with the same firmware uses the same layout.
Also known as: RTD-NET, RTD-10, Daikin RTD-NET - Heat pump (via ISG Modbus TCP gateway)
Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i)
Stiebel Eltron heat pumps run by a WPMsystem, WPM 3 or WPM 3i manager, reached through an ISG web (229336) or ISG plus (233493) with the Modbus TCP/IP software extension.
Also known as: ISG web Modbus TCP/IP, ISG plus Modbus TCP/IP, WPMsystem, WPM 3, WPM 3i - VRF / split AC gateway
Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners
Airzone Aidoo Pro units configured for Modbus output and connected to a direct-expansion AC unit; register table 'Registers for Direct Expansion units' of the Aidoo - Modbus integration manual (v. 201). The air-to-water table in the same manual is not covered.
Also known as: Aidoo Pro, Aidoo Pro Modbus, Airzone Aidoo Modbus - VRF / split AC gateway
Fujitsu General UTY-VMSX Modbus converter (one indoor unit)
Fujitsu General UTY-VMSX Modbus RTU converter, one per indoor unit, per interface specification part no. 9708438047-05.
Also known as: UTY-VMSX - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA
All ac & vrf gateways Modbus register maps →
Source: Intesis INMBSHIS001R000 Modbus RTU (EIA-485) Interface for Hisense air conditioners - User's Manual · User's Manual v1.6 EN · rev. 2024-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.