  4. INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway

Heat pump gateway (VRF / split AC gateway) · Modbus register map

Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway Modbus register map

Updated 29 October 2026

Short answer

This Intesis interface connects to a Panasonic Aquarea hydro unit and presents it as a Modbus RTU server. All points are single 16-bit holding registers: system on/off and operating mode, zone setpoints and actual temperatures, DHW tank on/off and setpoint, water temperatures, present power draw, error code, unit configuration, and requests such as powerful, quiet and sterilisation. Some registers apply only to newer K/L/M series units.

This page lists 51 Modbus registers for the Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Equipment type
Heat pump gateway (VRF / split AC gateway)
Registers
51 (18 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code)
Source document
INMBSPAN001A100 User Manual - Panasonic Aquarea H/J/K/L/M Air-to-Water Units to Modbus RTU · User Manual Version 1.0.2 · rev. 2026-02-04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway

Integration in brief

Connect the gateway to the Aquarea hydro unit and the RS-485 bus, set the address on SW3 P1-P6 (default 1), then read holding registers with function 03 and write single registers with function 06: register 0 for on/off, 4 for mode, 12 and 33 for zone and tank setpoints.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0System on/offUINT16System on/offRead/write
HR 4Operating modeUINT16Operating modeRead/write
HR 12Zone 1 setpoint temperatureINT16Zone 1 setpointRead/write
HR 14Zone 1 actual temperatureINT16Zone 1 actual temperatureRead
HR 33Tank water setpointINT16Tank setpointRead/write
HR 32Tank water temperatureINT16Tank temperatureRead
HR 1Outdoor temperatureINT16Outdoor temperatureRead
HR 2Outlet water temperatureINT16Outlet water temperatureRead
HR 70Current error statusUINT16Error statusRead
HR 52Error codeUINT16Error codeRead

Enable Modbus control & writes

No software enable. Set the address and baud on the DIP switches with the gateway unpowered; it is powered by the Aquarea unit.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

51 of 51 shown
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0System on/offUINT16Read/write0 = Off; 1 = On
HR1Outdoor temperature-127 to 127 °C.INT16°CRead
HR2Outlet water temperatureFlow water, -127 to 127 °C.INT16°CRead
HR3Inlet water temperatureReturn water, -127 to 127 °C.INT16°CRead
HR4Operating modeValues 1-7 can be written; 8-11 are read-only states.UINT16Read/write1 = Heat; 2 = Heat + tank; 3 = Tank; 4 = Cool + tank; 5 = Cool; 6 = Auto; 7 = Auto + tank; 8 = Auto heat; 9 = Auto heat + tank; 10 = Auto cool; 11 = Auto cool + tank
HR5Heat mode water temperature setting methodUINT16Read/write1 = Compensation curve; 2 = Direct
HR6Cool mode water temperature setting methodUINT16Read/write1 = Compensation curve; 2 = Direct
HR9Zone 1/Zone 2 on/offOnly with two zones configured (register 82 = 2).UINT16Read/write1 = Zone 1 on / Zone 2 off; 2 = Zone 1 off / Zone 2 on; 3 = Zone 1 on / Zone 2 on
HR10Zone 1 sensorUINT16Read1 = Water temperature; 2 = External room sensor; 3 = Internal room sensor; 4 = Room thermistor; 5 = Pool sensor
HR11Zone 2 sensorUINT16Read1 = Water temperature; 2 = External room sensor; 3 = Internal room sensor; 4 = Room thermistor; 5 = Pool sensor
HR12Zone 1 setpoint temperatureWater shift, water, room or pool setpoint, depending on setup and mode.INT16°CRead/write
HR13Zone 2 setpoint temperatureWater shift, water, room or pool setpoint, depending on setup and mode.INT16°CRead/write
HR14Zone 1 actual temperatureRoom, water or pool value matching the setpoint type.INT16°CRead
HR15Zone 2 actual temperatureRoom, water or pool value matching the setpoint type.INT16°CRead
HR16Zone 1 temperature setting modeUINT16Read1 = Room temperature; 2 = Compensation curve (water); 3 = Direct (water); 4 = Pool temperature
HR17Zone 2 temperature setting modeUINT16Read1 = Room temperature; 2 = Compensation curve (water); 3 = Direct (water); 4 = Pool temperature
HR18Zone 1 min setpointLower limit for the current setpoint type.INT16°CRead
HR19Zone 1 max setpointUpper limit for the current setpoint type.INT16°CRead
HR20Zone 2 min setpointLower limit for the current setpoint type.INT16°CRead
HR21Zone 2 max setpointUpper limit for the current setpoint type.INT16°CRead
HR30Tank on/offDomestic hot water tank.UINT16Read/write0 = Off; 1 = On
HR32Tank water temperatureCurrent DHW tank temperature.INT16°CRead
HR33Tank water setpoint40 to 55 or 75 °C depending on unit.INT16°CRead/write
HR34Tank heaterUINT16Read1 = Internal; 2 = External
HR35Tank min setpointINT16°CRead
HR36Tank max setpointINT16°CRead
HR45Tank mode energy consumptionPresent power draw in tank mode.UINT16WRead
HR46Heat mode energy consumptionPresent power draw in heat mode.UINT16WRead
HR47Cool / heat recovery mode energy consumptionPresent power draw in cool mode.UINT16WRead
HR52Error code0 = none; 1xxx = Uxx, 2xxx = Hxx, 3xxx = Fxx.UINT16Read
HR64De-ice statusUINT16Read0 = Off; 1 = On
HR70Current error statusReads 1 until the gateway has talked to the unit.UINT16Read0 = No error; 1 = Error
HR81Tank connectionUINT16Read/write0 = No; 1 = Yes
HR82Number of zonesUINT16Read/write1 = 1 zone; 2 = 2 zones
HR83Zone 1 setupUINT16Read/write1 = Room; 2 = Pool
HR84Zone 2 setupUINT16Read/write1 = Room; 2 = Pool
HR85DirectionWhere the heat pump is currently delivering heat.UINT16Read1 = Room; 2 = Tank
HR86Outdoor typeUINT16Read1 = STD; 2 = TCAP; 3 = HWT
HR111SG Ready control patternK series onward.UINT16Read1 = Normal; 2 = HP stop; 3 = Capacity 1; 4 = Capacity 2
HR112Water pressure0-5080 mbar; K series onward.UINT16mbarRead
HR117Model seriesUINT16Read1 = H series; 2 = J series; 3 = K series; 4 = L series; 5 = M series
HR183Water outlet temperature targetINT16°CRead
HR197Powerful (request)Temporary boost.UINT16Read/write1 = Off; 2 = On 30 min; 3 = On 60 min; 4 = On 90 min
HR198Quiet (request)UINT16Read/write1 = Off; 2 = Level 1; 3 = Level 2; 4 = Level 3
HR200System reset (request)UINT16Write0 = No request; 1 = Request
HR202Sterilization (request)Starts a tank sterilisation cycle.UINT16Write0 = No request; 1 = Request
HR460Gateway IDReads 3328 (0x0D00).UINT16Read3328 = INMBSPAN001A100
HR463Gateway resetWrite 1 to restart the gateway.UINT16Read/write
HR464Baud rateUINT16Read0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200; 4 = 38400; 5 = 57600; 6 = 76800; 7 = 115200
HR465Gateway Modbus server address1-63.UINT16Read
HR466DIP switch valueSwitch positions as a binary number.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway

What Modbus registers does the Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway have?

This map lists 51 registers: 51 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each register is listed with a 'Modbus address (base 0)' (protocol address) and a 'PLC address (base 1)'. This map uses the base-0 value as the wire address: System on/off is address 0 (PLC 1).

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway?

Start with HR 0 System on/off (System on/off); HR 4 Operating mode (Operating mode); HR 12 Zone 1 setpoint temperature (Zone 1 setpoint); HR 14 Zone 1 actual temperature (Zone 1 actual temperature); HR 33 Tank water setpoint (Tank setpoint); HR 32 Tank water temperature (Tank temperature); HR 1 Outdoor temperature (Outdoor temperature); HR 2 Outlet water temperature (Outlet water temperature); HR 70 Current error status (Error status); HR 52 Error code (Error code).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway?

No software enable. Set the address and baud on the DIP switches with the gateway unpowered; it is powered by the Aquarea unit.

Where is the official Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway Modbus documentation?

The source is INMBSPAN001A100 User Manual - Panasonic Aquarea H/J/K/L/M Air-to-Water Units to Modbus RTU (User Manual Version 1.0.2), revision 2026-02-04, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/inmbspan001a100-user-manual-v1-0-0-en.pdf.

More Intesis (HMS Networks) Modbus register maps

Source: INMBSPAN001A100 User Manual - Panasonic Aquarea H/J/K/L/M Air-to-Water Units to Modbus RTU · User Manual Version 1.0.2 · rev. 2026-02-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.