VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway Modbus register map

Updated 16 October 2026

Short answer

Modbus RTU server that connects to the P1P2 remote-controller bus of a Daikin VRV or Sky Air indoor unit. All points are 16-bit holding registers covering on/off, mode, fan, vanes, setpoint, room temperature, alarm and Daikin error code, plus window-contact and virtual-temperature features.

This page lists 25 Modbus registers for the Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
Equipment type
VRF / split AC gateway
Registers
25 (14 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSDAI001R000, Intesis Daikin VRV Modbus
Source document
INMBSDAI001R000 Modbus RTU Gateway - Compatible with VRV and Sky air conditioning systems commercialized by Daikin - User Manual · User Manual Version 1.0.1 · rev. 2024-03-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway

Integration in brief

Wire RS-485 A/B, set the address on SW3 and the baud on SW3/SW4, reboot, then read holding registers 0-11 with function 03 and write with function 06. Check SW1: without a Daikin wired remote on the P1P2 bus the gateway must be set as header.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0AC unit On/OffUINT16On/offRead/write
HR 1AC unit modeUINT16ModeRead/write
HR 2AC unit fan speedUINT16Fan speedRead/write
HR 4AC unit temperature setpointUINT16SetpointRead/write
HR 5AC unit temperature referenceUINT16Room temperatureRead
HR 10AC unit alarm statusUINT16Alarm flagRead
HR 11Error codeUINT16Error codeRead

Enable Modbus control & writes

No enable step. Set a slave address on SW3 and keep register 7 (gateway disablement) at 0 so Modbus commands reach the unit.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

25 of 25 shown
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0AC unit On/OffUINT16Read/write0 = Off; 1 = On
HR1AC unit modeAvailable modes depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR2AC unit fan speedAvailable speeds depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Low; 2 = Mid; 3 = High
HR3AC unit up/down vane positionAvailable positions depend on the indoor unit.UINT16Read/write1 = Position 1 (Horizontal); 2 = Position 2 (Horizontal); 3 = Position 3 (Medium); 4 = Position 4 (Vertical); 5 = Position 5 (Vertical); 10 = Swing
HR4AC unit temperature setpointSetpoint 16..31 °C (61..88 °F). SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Not initialised / no value (0x8000; manual writes -32768)
HR5AC unit temperature referenceUnit room temperature, 10..38 °C. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead
HR6Window contactVirtual window contact written from Modbus.UINT16Read/write0 = Closed; 1 = Open
HR7Gateway disablementStops the gateway passing commands; stored in NVM.UINT16Read/write0 = Gateway enabled; 1 = Gateway disabled
HR8AC remote control disablementBlocks the wired remote on the bus; stored in NVM.UINT16Read/write0 = Remote control enabled; 1 = Remote control disabled
HR9AC unit operation timeHours the unit has been on; stored in NVM.UINT16hRead/write
HR10AC unit alarm statusUINT16Read0 = No alarm condition; 1 = Alarm condition
HR11Error codeDaikin error number (manual error table); 65535 = no comms with AC unit.UINT16Read0 = No error present; 65535 = Communication error with the AC unit
HR13Open window switch-off timeoutCountdown after window opens before unit switches off (0..30, default 30).UINT16minRead/write
HR14Modbus RTU baud rateBaud rate in use (set on DIP switches).UINT16Read
HR15Device Modbus server addressRange 1..63.UINT16Read
HR21Maximum number of fan speedsUINT16Read
HR22External ambient temperature (Modbus)Room temperature written from Modbus (virtual temperature). SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Not initialised / no value (0x8000; manual writes -32768)
HR23AC real temperature setpointSetpoint actually applied in the indoor unit. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead
HR26AC unit left/right vane positionUINT16Read/write0 = Auto; 10 = Swing
HR48Switch valueCurrent DIP switch settings.UINT16Read
HR49Device IDReads 0x0801.UINT16Read
HR50Software versionUINT16Read
HR55Under voltage counterRange 0..300.UINT16Read/write
HR81Error addressAddress of the indoor unit reporting the error.UINT16Read
HR97Block periodic sendings1 = only forward Modbus writes that change the value (FW 1.5+).UINT16Read/write0 = Non-blocked; 1 = Blocked

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway

What Modbus registers does the Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway have?

This map lists 25 registers: 25 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables list a 'protocol address' (base 0) and a 'PLC address' (base 1). The protocol address is the wire address and is what 'documented' holds; PLC tools that add 1 should use the PLC column.

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway?

Start with HR 0 AC unit On/Off (On/off); HR 1 AC unit mode (Mode); HR 2 AC unit fan speed (Fan speed); HR 4 AC unit temperature setpoint (Setpoint); HR 5 AC unit temperature reference (Room temperature); HR 10 AC unit alarm status (Alarm flag); HR 11 Error code (Error code).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway?

No enable step. Set a slave address on SW3 and keep register 7 (gateway disablement) at 0 so Modbus commands reach the unit.

Where is the official Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway Modbus documentation?

The source is INMBSDAI001R000 Modbus RTU Gateway - Compatible with VRV and Sky air conditioning systems commercialized by Daikin - User Manual (User Manual Version 1.0.1), revision 2024-03-01, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsdai001r000.pdf.