VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway Modbus register map

Updated 24 October 2026

Short answer

Modbus RTU server that plugs into the CN65/CN12/CN6 connector on a Fujitsu indoor unit's control board with the supplied cable. Holding registers give on/off, mode, fan (up to 6 speeds), both vanes, economy, antifreeze, setpoint and limits, room and return temperatures, filter sign, alarm and error code, plus window-contact and external-temperature functions.

This page lists 35 Modbus registers for the Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
Equipment type
VRF / split AC gateway
Registers
35 (18 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus
Source document
Intesis INMBSFGL001I000 Modbus RTU Gateway - Fujitsu Air Conditioning - User Manual · User Manual v1.5 EN · rev. 2024-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway

Integration in brief

Plug the supplied cable into CN65/CN12/CN6 on the indoor board, set the fan-speed count and baud on SW1 and the address on SW2, power-cycle, then poll holding registers 0-11 with function 03 and write with 06.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0AC unit On/OffUINT16On/offRead/write
HR 1AC unit modeUINT16ModeRead/write
HR 2AC unit fan speedUINT16Fan speedRead/write
HR 4AC unit temperature setpointUINT16SetpointRead/write
HR 5AC unit temperature referenceUINT16Room temperatureRead
HR 10AC unit alarm statusUINT16Alarm flagRead
HR 11Error codeUINT16Error codeRead

Enable Modbus control & writes

No enable step; register 7 (gateway disablement) must be 0 for commands to reach the unit.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

35 of 35 shown
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0AC unit On/OffUINT16Read/write0 = Off; 1 = On
HR1AC unit modeAvailable modes depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR2AC unit fan speedSpeed count (3-6) set on SW1; available speeds depend on the unit.UINT16Read/write0 = Auto; 1 = Quiet; 2 = Low; 3 = Med; 4 = High
HR3AC unit vane positionUp/down vane; availability depends on the indoor unit.UINT16Read/write1 = Position-1 (Horizontal); 2 = Position-2 (Horizontal); 3 = Position-3 (Medium); 4 = Position-4 (Vertical); 10 = Swing
HR4AC unit temperature setpointSetpoint 16..30 °C (61..86 °F). SW2 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write0 = Undetermined; 32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR5AC unit temperature referenceRoom temperature, 18..30 °C. SW2 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead0 = Undetermined; 32768 = No temperature sent from the remote controller (0x8000)
HR6Window contactVirtual window contact written from Modbus.UINT16Read/write0 = Closed; 1 = Open
HR7Gateway disablementStops the gateway passing commands; stored in NVM.UINT16Read/write0 = INMBSFGL001I000 enabled; 1 = INMBSFGL001I000 disabled
HR8AC remote control disablementBlocks the Fujitsu wired remote.UINT16Read/write0 = Remote control enabled; 1 = Remote control disabled
HR9AC unit operation timeHours the unit has been on.UINT16hRead/write
HR10AC unit alarm statusUINT16Read0 = No alarm condition; 1 = Alarm condition
HR11Error codeFujitsu error number (manual section 7); 65535 = communication error.UINT16Read0 = No error present; 65535 = Communication error (gateway or remote controller with the AC unit)
HR13Open window switch-off timeoutCountdown after window opens before switch-off (0..30, default 30).UINT16minRead/write
HR14Modbus RTU baud rateBaud rate in use (set on DIP switches).UINT16Read
HR15Modbus slave addressRange 1..63.UINT16Read
HR21Number of fan speeds3..6, as set on SW1.UINT16Read
HR22External ambient temperature (Modbus)Modbus room sensor; RAC caveat in gotchas. SW2 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Initialisation value, no external sensor value (0x8000)
HR23AC real temperature setpointSetpoint applied in the unit, 16..31 °C. SW2 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead
HR24Current AC max setpointUpper setpoint limit reported by the unit. SW2 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR25Current AC min setpointLower setpoint limit reported by the unit. SW2 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR26AC unit horizontal vane positionLeft/right vane; manual prints 1 and 5 with an ellipsis for positions in between.UINT16Read/write0 = Auto; 1 = Position 1; 5 = Position 5; 10 = Swing
HR31Window contact status (feedback)UINT16Read0 = Not active; 1 = Active (window open)
HR36External On/Off disablementUINT16Read/write0 = Not active; 1 = Active
HR40Window contact On/Off disablementWhether the window-contact function is in use.UINT16Read0 = Window contact disabled (not working); 1 = Window contact enabled (in use)
HR43Filter resetWrite 1 to reset the filter sign.UINT16Write1 = Reset
HR44Filter statusUINT16Read0 = Off; 1 = Lit
HR49Device IDReads 0x0D00.UINT16Read
HR50Software versionUINT16Read
HR56Antifreeze operationUINT16Read/write0 = Disabled; 1 = Enabled
HR64EconomyUINT16Read/write0 = Disabled; 1 = Enabled
HR65Input reference temperatureReference temperature in use. SW2 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = No external sensor value, no virtual temperature (0x8000)
HR66Return path temperatureIndoor unit return-air sensor. SW2 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR97Block periodic sendings1 = only forward Modbus writes that change the value.UINT16Read/write0 = Non-blocked; 1 = Blocked
HR98Master/Slave (gateway role)UINT16Read0 = Slave; 1 = Master
HR99ResetWrite 1 to restart the gateway.UINT16Write1 = Reset

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway

What Modbus registers does the Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway have?

This map lists 35 registers: 35 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables give a 'protocol address' (base 0) and a 'PLC address' (base 1); the protocol address is the wire address and is used for 'documented'.

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway?

Start with HR 0 AC unit On/Off (On/off); HR 1 AC unit mode (Mode); HR 2 AC unit fan speed (Fan speed); HR 4 AC unit temperature setpoint (Setpoint); HR 5 AC unit temperature reference (Room temperature); HR 10 AC unit alarm status (Alarm flag); HR 11 Error code (Error code).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway?

No enable step; register 7 (gateway disablement) must be 0 for commands to reach the unit.

Where is the official Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway Modbus documentation?

The source is Intesis INMBSFGL001I000 Modbus RTU Gateway - Fujitsu Air Conditioning - User Manual (User Manual v1.5 EN), revision 2024-01, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsfgl001i000.pdf.